Electrical Information
Input Voltage
Powered by SR driver low-voltage interface
Current Consumption
13mA
Nominal Power Consumption
200mW
Standby Power
< 1 W on luminaire level, including driver standby power
Occupancy Sensing
Type
Passive infrared (PIR)
Enable/Disable
Default enabled
Detection
Off/Auto-on; Red LED indicates "on"
Hold Time
1 - 120 minutes
Viewing Angle
X=72°, Y = 86° ( See detection pattern)
Background Light Level
Off or 5-100%
Prolong Time
0 minutes - infinity
Grace Fading
0-25 sec
Response Time/Fading to Switch On/Off
0.7Sec
Daylight Sensing
Enable/Disable
Default enabled
Auto-calibration
Upon power-up
Viewing Angle
40° (half value sensitivity); 2% cut-off point at 75°
Task Tuning
Full Light Setting
5-100%
Environment & Approbation
Operating Ambient Temperature Range
0°C to 55°C
Operating Humidity
0 – 95% non condensing
Storage Temperature
-25°C to 85°C
Storage Humidity
0-95% non condensing
Max Case Temperature (Tcase)
55°C
Agency Approbations
UL, CSA; Tested and approved for use in plenums; FCC ID:
2AF2N-SNS100; IC: 20659-SNS100
Certification
California Title 20
Limited Warranty
5 years
Digital Interface
Xitanium SR
Other
Status Indicators
Red, Yellow. Yellow LED on: Vacancy & Sensor is functional;
Red LED on: Motion is detected
No. Drivers per Sensor
Four drivers per sensor maximum; Wiring polarity must be maintained
Field Configuration
via NFC, parameters set via Philips Field Apps
Operation and Configuration via Mobile App
EasySense operates immediately upon installation and energization without further commissioning. If changes from
default settings are desired, EasySense can be configured via an app through NFC embedded within the sensor.
The "Philips field app" can be accessed on the Google Play Store. For a complete description of the features and default
settings—as well as details on the app and recommended Android phones—refer to www.philips.com/easysense.
FCC and IC
This device complies with part 15 of the FCC rules for the United States and Industry Canada (IC) license-exempt RSS
standard(s). Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation. Any
changes or modifications not expressly approved by Philips could void the user's authority to operate this equipment.
This product is intended for commercial use only.
Ce dispositif est conforme à la partie 15 des règles de la Federal Communications Commission (FCC) des États-Unis et
d'Industrie Canada (IC) exempts de licence RSS norme(s). Son fonctionnement est assujetti aux deux conditions suivantes
: (1) Ce dispositif ne doit pas provoquer de brouillage préjudiciable, et (2) il doit accepter tout brouillage reçu, y compris
le brouillage pouvant entraîner un mauvais fonctionnement. Tous les changements ou modifications non expressément
approuvés par Philips, sont susceptibles d'annuler le droit de l'utilisateur à se servir de cet équipement. Ce produit est
exclusivement destiné à un usage commercial.
© 2016 Philips Lighting Holding B.V. All rights reserved.
Philips reserves the right to make changes in specifications
and/or to discontinue any product at any time without notice
or obligation and will not be liable for any consequences
resulting from the use of this publication.
philips.com/easysense
PLt-1621QG_EasySenseCMP QIG
02/16
page 1 of 2
Document #: 4435 290 61451 REV. A
Philips Lighting North America Corporation
10275 W. Higgins Road, Rosemont IL 60018
Tel: 800-322-2086 Fax: 888-423-1882
Customer/Technical Service: 800-372-3331
OEM Support: 866-915-5886
Philips Lighting Canada Ltd.
281 Hillmount Rd, Markham, ON, Canada L6C 2S3
Tel. 800-668-9008
Sensors
EasySense
Ceiling-Mount
Philips EasySense Quick Installation Guide
Sensor Part Number
Commercial Product Name
EasySense Ceiling-Mount Sensor
Compatible LED Drivers
Driver Model Number
Description
XI040C110V054VPT1
Xitanium 40W 0.1-1.1A 27-54V 120-277V SR
XI075C200V054VPT1
Xitanium 75W 0.1-2.0A 27-54V 120-277V SR
Specifications available at www.philips.com/XitaniumSR.

Wiring Diagram

Connectors
EASYSENSE
WHITE
SR-
RED
SR+
GROUND
LINE
NEUTRAL
36-inch 18AWG solid lead wires in
plenum-rated jacket from sensor stripped
to 3/8". Connect white wire to brown (SR-)
and red wire to purple (SR+) on driver.
Connection
Four drivers per sensor maximum.
Polarity must be maintained.
White
Black
Green
Purple
Brown
Order Code
SNS100CMP (510651)
LED+
LED+
LED-
XITANIUM SR
LED-
NC
LED DRIVER
RSET2
SGND
NFC ANTENNA
Color
Connection
Color
Neutral
Red
LED+
Line
Blue
LED-
Ground
Orange
RSET2
SR+
Green
SGND
SR-

Advertisement

loading

Summary of Contents for Philips EasySense

  • Page 1: Wiring Diagram

    EasySense can be configured via an app through NFC embedded within the sensor. XI040C110V054VPT1 Xitanium 40W 0.1-1.1A 27-54V 120-277V SR The “Philips field app” can be accessed on the Google Play Store. For a complete description of the features and default XI075C200V054VPT1 Xitanium 75W 0.1-2.0A 27-54V 120-277V SR settings—as well as details on the app and recommended Android phones—refer to www.philips.com/easysense.
  • Page 2 (SR-) terminal on the driver. Connect the red wire from the sensor to the purple (SR+) terminal on the driver. Follow fixture manufacturer’s instructions for accessing the driver. Note: Up to (4) drivers maximum can be connected to (1) EasySense. Polarity must be maintained. 3.193 [81.09] REF. Configuring Sensor Parameters EasySense operates upon energization with no further commissioning.

This manual is also suitable for:

Sns100cmp510651