SPLIT SYSTEMS

INSTALLATION GUIDE

(R410A Models)
Issue 12, December 2018

Advertisement

loading

Summary of Contents for TemperZone OSA 66RKS

  • Page 1: Installation Guide

    SPLIT SYSTEMS INSTALLATION GUIDE (R410A Models) Issue 12, December 2018...
  • Page 2: Installation Requirements

    INSTALLATION REQUIREMENTS Piping Piping Insulation Use clean sealed refrigeration grade piping. Suction Liquid ii. Pipe to be cut ONLY with a pipe cutter. iii. Use long radius bends (2 x pipe dia.) iv. Insulate the suction (gas) line, seal all insulation joints and insulate the liquid lines on all units with EEV's in outdoor unit.
  • Page 3: Refrigerant Charging

    For further information on measuring Superheat, visit our website. Commissioning Each outdoor unit is supplied with a Commissioning Sheet to assist installers completing the Start Up Procedure outlined in the Installation & Maintenance Refrigerant Pipe Sizes pamphlet. The sheet includes a pulley adjustment guide for belt driven indoor Suction/Liquid line sizes given in the following tables are interconnecting pipe units if applicable. We recommend you complete the form, send a copy to sizes and are not necessarily the same size as the pipe stub connections exiting temperzone and keep the original yourself for possible future reference. the Indoor or Outdoor unit. On any unit with variable capacity compressors, do not oversize the Manufacturer's Note interconnecting piping as this will reduce the refrigerant velocities significantly The manufacturer reserves the right to make changes at any time without notice with the associated danger of not returning the oil to the compressor. or obligation. Should any instruction in this guide conflict with any Installation & Maintenance pamphlet supplied with a unit, then the most recently dated publication should be considered correct.
  • Page 4 (R410A) Line Length g/m Beyond Additional Oil Suction Liquid (R410A) ml/m Oil Type OSA 66RKS Scroll ZP24 KSE-PFZ 3.15 None up to 40 POE 32-3MAF (or equivalent) OSA 87RKS Scroll ZP31KSE-PFZ 3.65*** None up to 40 POE 32-3MAF (or equivalent)
  • Page 5 Table 2 SPLIT SYSTEM PIPING REQUIREMENTS ( Units Supplied Pre-Charged ) Standard Unit Limitations Common to Both Standard & Extended Line Lengths Extended Line Lengths Approximate Maximum Vertical Separation Refrigerant Charging Oil Charging Performance Outdoor Unit Indoor Unit Precharge Additional Maximum Loss Max Line above above for 10m Line...
  • Page 6 Phone (08) 8340 - 0607 CHRISTCHURCH Fax (08) 8340 - 2118 Phone 0-3-379 3216 Fax 0-3-379 5956 PERTH Phone (08) 6399 - 5900 Fax (08) 6399 - 5932 SINGAPORE temperzone Ltd TOWNSVILLE 1 Claymore Drive #08-13 Phone (07) 4773 - 9566 Rear Block, Orchard Towers Fax (07) 4773 - 9166 Singapore 229594 Phone SNG 6733 - 4292 BRISBANE Fax SNG 6235 - 7180 Phone (07) 3308 - 8333 Email sales@temperzone.com.sg Fax (07) 3308 - 8330 NEWCASTLE JAKARTA Phone (02) 4962 - 1155 temperzone Ltd Fax (02) 4961 - 5101 Suite 1110, Antam Office Park, Tower B Jl TB. Simatupang No. 1, Jagakarsa LAUNCESTON Jakarta 12530 Mobile +62 (0) 8111 175 005 Phone (03) 6331 - 4209 Email t.chriswanda@temperzone.co.id Fax (03) 6333 - 0224 Visit our website www.temperzone.biz 12/18 Pamphlet No. 3735...