NOTES: 1) CUT YELLOW, BROWN AND ORANGE WIRES GOING FROM CONTROL BOX TO BACK-CHECK SWITCH ON OPERATOR CAM. 2) YELLOW AND ORANGE FROM CAM SWITCH USED FOR COIL ACTIVATION SEE FIGURE 2. 3) YELLOW TERM (5) BROWN TERM (1) ORANGE TERM (3) FROM CONTROL BOX TO ISO RELAY CONTACTS.
Page 3
C3938 P/S 24 VAC WIZARD INTERIOR NOTES: 1) ON THE C2150 CONTROL TURN FUNCTION "SP" ON. IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC. FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS, CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564.
Page 4
PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM QUICK-DISCONNECT C4320-1 ROCKER SWITCH AUTOMATIC HOLD OPEN...
Page 5
LO21B/U GREEN NOTES: 1) PARALLEL ACT, COM, SAF FOR PAIR DOORS. OR MAY REQUIRE HORTON C7215 SIMULTANEOUS ACTIVATION MODULE. CONTACT BEA TECH SUPPORT FOR MORE INFO IF NECESSARY IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC. FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM.
Page 6
IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC. FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS, CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOT LEAVE ANY PROBLEM UNRESOLVED.
Page 7
EXTERIOR IRIS 24 V TRANSFORMER * RECEIVER (A), EMITTER (A) RECEIVER (B), EMITTER(B) WH= WHITE, BL= BLACK RA WH 1 MICROCELL ONE RA BL EA WH 3 5 NC EA BL 4 NO 3 COM RB WH 1 2 12-24 VAC/DC 1 2 3 4 RB BL 1 12-24 VAC/DC...
Page 9
ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM SUPERSCAN QUICK- DISCONNECT CABLE C4320-1 ROCKER SWITCH AUTOMATIC HOLD OPEN BREAKOUT SWITCH...
Page 10
EB WH 3 EB BL NOTES: 1 ) BEA RECOMMENDS USING THE LO-21 2 ) LO-21 RED AND BLACK WIRES MUST CONNECT TO THE CORRECT MOTOR POLARITY, RED=POSITIVE, BLACK=NEGATIVE. 3 ) WHEN USING DC VOLTAGE, POLARITY MUST BE MAINTAINED AS ORANGE: (-) 4 ) NOTE REF LO21: CONNECT THE DASHED LINES GREEN,BLUE,BLACK/WHITE,PURPLE, &...
Page 11
WIZARD EXTERIOR 24 V TRANSFORMER NOTES: 1) REDIRECT WIZARD RELAY MODE WITH REMOTE BY SELECTING F1 THEN 1,LOCK,LOCK. IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC. FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS, CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564.
Page 12
DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM C2150 CONTROL NURSES STATION PUSHBUTTON DAY / NIGHT SWITCH TITLE: HORTON 2150 MICRO-PROCESSOR DRAWN BY: SIZE: SCALE: NONE...
Page 13
WIZARD EXTERIOR 24 V TRANSFORMER * RECEIVER (A), EMITTER (A) RECEIVER (B), EMITTER(B) WH= WHITE, BL= BLACK RA WH 1 MICROCELL ONE RA BL EA WH 3 5 NC EA BL 4 NO 3 COM RB WH 1 2 12-24 VAC/DC 1 2 3 4 RB BL 1 12-24 VAC/DC...
Page 14
LEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM C4320-1 ROCKER SWITCH AUTOMATIC HOLD OPEN...
Page 15
LEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM RIGHT APPRCH SIDE SSCAN C4320-1 ROCKER SWITCH AUTOMATIC HOLD OPEN BREAKOUT SWITCH...
Page 17
(SEE NOTE) (SEE NOTE) NOTE: SWITCH MUST OPEN 10 DEGREES FROM DOOR CLOSING IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC. FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS, CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOT LEAVE ANY PROBLEM UNRESOLVED.
Page 18
ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM MOTOR C4320-1 ROCKER SWITCH AUTOMATIC HOLD OPEN...
Page 19
ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM MOTOR C4320-1 ROCKER SWITCH AUTOMATIC HOLD OPEN...
Page 20
2. EXTERNAL SWITCH IS REQUIRED IF INHIBIT DESIRED AT SWING SIDE SUPERSCANS, SWITCH OPENS UPON INHIBIT POINT. 3. THE KNOWING ACT SWITCH IS CONNECTED AT THE AUX INPUT AND CAN BE ANY DRY CONTACT DEVICE SUCH AS A PUSHPLATE, CARD READER, ETC. THE AUX INPUT IS REQUIRED FOR ALL INITIAL ACTIVATION WHEN FUNCTION "FA"...