2. Sensor Connection

Figure 6. EAFR-08 Arc Light Fiber Optic Loop Sensor
(High Temperature).
Table 5. Technical Data for the EAFR-08 Arc Light Fiber
Optic Loop Sensor (High Temperature).
Light Intensity Threshold
Detection radius
Maximum Length
Diameter
Bending Radius
Operating Temperature
If any of the EAFR-06, 07 , 08 loop sensor ends
N
otee:
need to be covered to avoid light detection from
outside the protected zone, consult your nearest
Eaton representative for more information.

1.5 Sensor Type Dependencies

Different sensor types can be utilized in different arc flash
protection relays of the EAFR series. Table 6 describes the
dependencies.
Table 6. EAFR Series Relays and Arc Sensor
Dependencies.
EAFR-01
EAFR-06
Point Sensor
Plastic Loop
Sensor
EAFR-101
Yes
No
EAFR-102
No
Yes
EAFR-110P Yes
No
EAFR-110F
No
Yes
4
Arc Sensor User Manual MN026008EN February 2016 www.eaton.com
8,000 Lux
360 Degrees
50 m (164 ft)
1.2 mm (0.047 in.)
1 cm (0.394 in.)
-40 to 125°C (-40 to 257°F)
EAFR-01
EAFR-01
Glass Loop
High Temperature
Sensor
Loop Sensor
No
No
Yes
Yes
No
No
Yes
Yes
2. Sensor Connection

2.1 Arc Light Point Sensor EAFR-01 Connection

1.
Open the sensor side covers and then detach the
pluggable connectors from the sensor PCB. Prepare
the three twisted shielded pair cable connection (see
Figure 7).
N
otee:
There is no "In" or "Out" end of the cable. Either
end of the cable can be used.
Figure 7. Sensor Side Covers Removed and Pluggable
Connectors Detached.
2.
Before connecting the cable to the connector, make
sure that the connecting order is correct (+, signal,
shield). The appropriate pin information is shown on
the bottom shell of the sensor. Plug the wires into the
connector and fasten them by using a screw driver (see
Figure 8).
Figure 8. Location of the PIN Information and Securing
the Cable.
3.
Connect the other end of the cable to a sensor channel
on EAFR-101 or EAFR-110P relay (see Figure 9).