Actuator Connections; Recommended Preparation Of Openings In Wood And Metal Stud Walls - Greenheck ODFD Series Installation, Operation And Maintenance Instructions

11/2 hour combination fire smoke or curtain fire dampers out of wall or out of floor vertical or horizontal mount
Table of Contents

Advertisement

4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL OPENINGS continued....
• Retaining angles must be attached to the sleeve using
one or more of the following methods of attachment:
• Tack or spot welds
• #10 (19mm) sheet metal screws
1
in. (6mm) bolts and nuts
4
3
in. (4.7mm) steel pop rivets
16
Attachments must be spaced a minimum of 6 in.
(152mm) on center and a maximum of 2 in. (51mm) from
corners. The angles must be attached to all 4 sides of
the sleeve. A minimum of two attachments are required
on each side, top and bottom. The angles need not be
attached to each other at the corners.
c
!
Do not tear the thermal blanket during
aution
installation.
Dampers are tested for correct operation and are
square and straight before shipment from the factory.
Dampers must be installed square and straight and
must not be twisted or racked. Failure to install the
damper square and straight may prevent the damper
blades from operating open and closed.

5. ACTUATOR CONNECTIONS

Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring
and piping diagrams developed in compliance with
applicable codes, ordinances and regulations (see
Electrical Guidelines).
Recommended Preparation of Openings in
6
Wood and Metal Stud Walls
• Frame wall openings as shown (see Figure 5 & 5A)
• Gypsum wall board must be fastened 12 in. (305mm)
on center to all stud and runner flanges surrounding
opening (see Figure 5 & 5A).
• Prepare opening between studs and sleeve assembly
as shown (Figure 6 & 7).
• All construction and fasteners must meet the
requirements of the appropriate wall design (See UL
Fire Resistance Directory) and/or local codes.
Figure 5A
10
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
Metal stud only
2 i
6 i
6 i
2 i
Wall
Figure 4: Sleeved damper with Thermal
Blanket (duct continuation).
Note: Thermal blanket is riveted to the damper sleeve and
the seam is taped with acrylic adhesive tape, FSK facing
tape 152 5CWnt, manufactured by Venture Tape Company.
24 in. o.c.
Maximum
(metal studs)
12 in.
24 in. o.c.
Maximum
16 in. o.c.
Maximum
(wood studs)
Floor Runner
Figure 5
Retaining Angle
Thermal Blanket
(installed around
entire outside
surface of sleeve)
n .
M a
x .
n .
M a
x .
n .
M a
x .
n .
M a
x .
24 in. o.c.
Ceiling Runner
Maximum
(metal studs)
2 in. (51mm)
2 Panhead
Screws
2 in. (51mm)
16 in. o.c.
Maximum
(wood studs)