Securing The Damper/Sleeve Assembly To Wall And Floor Openings; Actuator Connections; Installation - Greenheck FSD-311V Installation, Operation And Maintenance Instructions

Combination fire smoke dampers
Hide thumbs Also See for FSD-311V:
Table of Contents

Advertisement

Type R and O
Factory Furnished
Duct Collars Qualify
As Breakaway
Connections
Duct
Damper with type R or O transition factory
Fig. 2
furnished.
Sleeve Gauge
Duct Dimension
14 ga. (0.075 in.)
- 10 ga. (0.138
All duct sizes
in.)
[2mm - 3.5mm]
36 in. (914mm) max. width
16 ga. (0.060 in.)
24 in. (610mm) max. width
[1.5mm]
24 in. (610mm) diameter
16 ga. (0.060 in.)
All duct sizes
[1.5mm]
18 ga. (0.048 in.)
85 in. (2159mm) wide and
[1.2mm]
20 ga. (0.036 in.)
55 in. - 84 in. wide
[0.9mm]
(1397mm - 2134mm)
22 ga. (.030 in.)
31 in. - 54 in. wide
[0.76mm]
(787mm - 1372mm)
24 ga. (0.024)
13 in. - 30 in. wide
[0.6mm]
(330mm - 762mm)
26 ga. (0.018 in.)
12 in. wide and under
[0.46mm]
See page 6 for additional information on breakaway sleeve connections.
Sleeve thickness must not be less than the gauge of the connecting duct.
UL Standard 555 requires all ducts to terminate at fire damper sleeves.
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL OPENINGS
Damper/sleeve assemblies must be installed in wall
openings using retaining angles on at least one side of
the wall as described below:
• Retaining angles for 11/2 hour rated dampers with a
width and height 48 in. (1219mm) or less must be a
minimum of 20 ga. (1mm). Retaining angles for all 3
hour rated dampers and all dampers with a width or
height greater than 48 in. (1219mm) must be a minimum
of 16 gauge (1.5mm). The leg of the retaining angle
on the damper sleeve shall be a minimum of 11/4 in.
(32mm). The leg of the retaining angle on the wall/floor
shall be long enough to cover the annular space and
overlap the wall/floor by a minimum of 1 in. (25mm).
4
Wall or Floor
Sleeve
Damper
Type C, O, R
Type of Duct
to Sleeve
Connection
Permitted
Rigid or
Breakaway
Rigid only
over
Breakaway only
(305mm)
• Retaining angle must be attached to the damper using
one or more of the following methods of attachment
(refer to label on outside of sleeve for 'No Screw' area):
• Tack or spot welds
• #10 (
/
in. max. [19mm]) sheet metal screws
3
4
/
in. (6mm) bolts and nuts
1
4
/
in. (5mm) steel pop rivets
3
16
A minimum of two connections per side, top, and bottom,
12 in. (305mm) O.C. (on center) maximum for openings of
48 in. W x 32 in. H (1219mm x 812mm) and less, and 6 in.
(152mm) O.C. for openings 100 in. W x 32 in. H (2540mm
x 32mm) or less. The angles must be attached to all 4
sides of the sleeve with butt joints at each corner. A
minimum of two attachments are required on each side,
top and bottom. Ensure that attachment device does not
interfere with the operation of the damper and the free
movement of the damper blades. The angles need not be
attached to each other at the corners. Do not secure the
retaining angle to the fire separation (see Fig. 3).
• Retaining angles should not be fastened to the wall
material. The angles should only sandwich the wall and
allow for damper expansion during periods of intense
heat.
Retaining
Angle
*only applicable for damper sizes above 36 in. x 36 in.
Both vertical and horizontal damper installations are
Fig. 3
typified by these drawings.
Damper
Maximum Single
Model
Section Size
FSD-311V
50 x 32

5. ACTUATOR CONNECTIONS

Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and
piping diagrams developed in compliance with applicable
codes, ordinances and regulations (see Electrical
Guidelines).
Wall or
Floor
Retaining
Angle
Sleeve
Duct
Damper
Maximum Multiple
Section Size
100 x 32