Are your rooms too warm/too cold?
+
Press + or – to increase or decrease the room
temperature setpoint in increments of 0.5 ° C /
1 ° F. Proceed as follows:
+
Press
or
to adjust the setpoint
temporarily.
Press
to save the value or wait for the
program to exit automatically.
To permanently modify the temperature
setpoints, use parameters P05 and P07.
To lock the setpoints, use parameters P06
and P08.
Does symbol
appear on the display?
(Only with battery-powered version)
Symbol
is displayed when the batteries are low.
Replace them with 2 new alkaline batteries type AAA.
Proceed as follows:
Get 2 new alkaline batteries type AAA
Remove the battery holder, then the batteries, insert
the new batteries and, within 1.5 minutes, replace the
battery holder
Ensure the exhausted batteries are disposed of
correctly, in compliance with environmental
requirements
Do you want to change parameters?
+
If you want to change control parameters,
proceed as follows:
+
Press
and
simultaneously for 5 seconds
Release them and parameter "P02" is
displayed
+
Press
or
to scroll to the parameter that
needs to be adjusted
Press
to select this parameter
+
Press
or
to adjust the value
Press
to confirm and save the adjusted
value
Select and modify other parameters
The program automatically returns to the
normal screen after a timeout.
CB1B1420en_01/ 2013-03-07
Parameter list
Parameter
Description
Setting range (default)
no.
P02
Selection of ° C
1 = ° C (default)
or ° F
2 = ° F
P03
Standard
1 = room temperature
temperature
(default)
display
2 = setpoint
P04
Temperature
-3...3 ° C
sensor
Step 0.5 ° C
calibration
(-6...6 ° F, step 1 ° F)
Default: 0 ° C
P05
Comfort setpoint
5...35 ° C, step 0.5 ° C
(41...95 ° F, step 1 ° F)
Default: 20 ° C, 68 ° F
P06
Comfort setpoint
0 = OFF (default)
lock
1 = ON
locked according
to setting in P05
P07
Economy
5...35 ° C, step 0.5 ° C
setpoint
(41...95 ° F, step 1 ° F)
Default: 16 ° C, 61 ° F
P08
Economy
0 = OFF (default)
setpoint lock
1 = ON
locked according
to setting in P07
P09
Buzzer
0 = OFF
1 = ON (default)
P10
Show frost
0 = OFF (default)
protection icon
1 = ON
P21
Button scanning
0.2 = 0.25 s
rate for the
0.5 = 0.5 s
capacitive
1.0 = 1.0 s (default)
buttons (touch
1.5 = 1.5 s
keys, RDD100.1
only)
Note: a shorter
scanning rate
means shorter
battery life.
P22
Reload factory
0 = OFF (default)
settings
1 = Reload
P23
Software version
No adjustment possible
information
Subject to alteration