Setting Up
Section 2
How to enter the configuration Menu
Use the scroll buttons to select the MENU item and press the UNMARKED
button. The screen will display 'Password?' Press the buttons in the following
sequence within 5 seconds to enter the default password: ON, BACKLIGHT,
CAL and UNMARKED. This password can be changed via a PC and the
SetPortable software.
How to change an option
To change an option, use the first two keys, labelled with the << and >>
symbols, to change the current selection, and the third key (labelled QUIT) to
finish changing the selection. If the QUIT key is pressed and the parameter has
been modified then the user is prompted with a save changes message. Two
keys are soft key function labelled, one with YES and one with NO. Press the
desired button.
For example, to configure the start-up option, from the configuration Menu
follow the steps below:
Scroll the menu
list to the left until
START is selected
12
1
2
DISPY ALARM ZERO PUMP
<<
>>
QUIT
ALARM ZERO PUMP START
<<
>>
QUIT
3
4
PUMP
START
Detecting Gas Saving Lives
Detective+
Detective+
Press the
UNMARKED button
to enter the START
submenu