Download Print this page

Sanyo ECOi C0705DXHN8 Brochure & Specs page 6

2 and 3 pipe electric vrf systems

Advertisement

ECOi 3 Way - features at a glance
ECOi 3 Way is one of the most advanced VRF heat
recovery
systems
available.
Not
only
high-efficiency and performance for simultaneous
heating and cooling, its sophisticated design makes
installation and maintenance much easier.
• Simultaneous heating and cooling for total control
• Single footprint size for all unit capacities (8-16HP)
• DC inverter technology combined with R410A for
excellent efficiency
• System configuration from 8HP to 48HP
• Diversity ratio 50-130%
• Sound levels: from 54.5dB(A)
• Quiet mode offers a further 3dB(A) reduction
• Extended pipe runs of up to 150m
• COPs to 4.1
• Provides cooling down to -10°C ambient
• Connectability of 40 indoor units from 24HP upwards
Extended operating range - better output at lower
temperatures
The operating range for heating has been extended to
-20°C. The remote controller temperature setting for heating
operation has also been extended from 16°C to 30°C.
8HP ~ 48HP
Cooling: -10˚C DB ~ 43˚C DB
Heating: -20˚C WB ~ 15˚C WB
There is improved performance at lower ambient conditions
due to SANYO's unique wrap-around outdoor unit coil design
and active defrost management.
Higher COPs - lower running costs
HP
8
10
12
14
16
18
20
22
3.78
3.45
3.41
3.45
3.38
3.57
3.46
3.44
EER Cooling
COP Heating
4.09
3.95
3.81
3.91
3.79
4.01
3.96
3.88
9
offering
24
26
28
30
32
34
36
38
40
3.45
3.41
3.4
3.41
3.38
3.45
3.41
3.42
3.42
3.92
3.84
3.8
3.85
3.79
3.93
3.88
3.84
3.88
UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB
Solenoid Valve Kit
Up to max. 40 indoor units
3 Way ECOi Multi enables
simultaneous
heating
cooling operation by each
solenoid valve kit.
42
44
46
48
Timer remote controller
3.4
3.41
3.40
3.38
3.84
3.81
3.83
3.79
RCS-TM80BG
UK Conditions: Cooling Indoor 23˚C DB 50% RH Outdoor 30˚C Heating Indoor 20˚C Outdoor 0˚C
Rating Conditions: Cooling Indoor 27˚C DB 19˚C WB Outdoor 35˚C DB 24˚C WB Heating Indoor 20˚C DB Outdoor 7˚C DB 6˚C WB
Fully-automatic simultaneous Cooling/Heating operation and heat recovery
System Example
• Any design and layout can be used in a single system
• Cooling operation is possible down to an outdoor
temperature of -10°C
and
[Cooling]
[Heating]
[Heating]
Liquid pipe
Discharge pipe
medium-temperature,
high-temperature,
medium-pressure liquid pipe
high-pressure gas pipe
Up to 5 indoor units with individual remote control
can be connected off 1 SVK box.
Box dimensions: L 166mm X 147mm X 217mm
Solenoid Valve Kit
ATK-RZP56BG
ATK-RZP160BG
[Stop]
[Cooling]
[Cooling]
Same operation
Suction pipe
low-temperature,
low-pressure gas pipe
Solenoid Valve Kit
10