echoflex RVS-A-XW Installation Manual

Wireless vacancy/occupancy pir or dual-tech sensor

Advertisement

Quick Links

This guide covers all models of RVS vacancy and RCS occupancy ceiling sensors.
These models include:
RVS-A-XW
Vacancy sensor with small motion short range lens (1000 sq. ft.)
RVS-B-XW
Vacancy sensor with large motion large range lens (1900 sq. ft.)
RVS-DA-XW Dual-tech vacancy sensor with small motion short range lens (1000 sq. ft.)
RVS-DB-XW Dual-tech vacancy sensor with large motion large range lens (1900 sq. ft.)
The RCS models are identical to the RVS with the addition of a battery to provide power for
support of auto-on occupancy sensor applications.
The character X in the model number is replaced with U for 902MHz, Y for 868MHz
radios, and J for 928MHz radios.
The product box includes the sensor, installation guide, lens mask, and two wire straps
for ceiling tile mounting.
i
Note:
i
Note:
RVS - Vacancy, RCS - Occupancy Sensor Description
The RVS/RCS (also referred to as the sensor in this guide) is a wireless, energy harvesting
sensor. The models include a single method PIR (passive infrared) sensor or a dual
technology method of occupancy detection using a PIR sensor and audio interface (any
reference to audio in this guide applies to DT models only). The combination of PIR sensor
and audio sensing adds additional assurance of positive occupant detection. Passive
microphone technology provides coverage of audible human activity across most of the
PIR detection range. Innovative noise filtering is used to prevent false triggers that could
keep lights on in empty rooms. Used for indoor applications, the detector is optimized
for ceiling heights of 8 - 10 feet (2.4 - 3 meters).
Wireless Vacancy/Occupancy
pir or dual-tech Sensor
Installation Guide
The sensor cover is removable however it must be properly
seated for normal operation
The RVS is a solar powered device that absorbs solar energy
from artificial or natural light sources. Before assigning the RVS
sensor to a receiver or controller, the sensor should be exposed
to a good light source for a minimum of 2 minutes.
RVS-RCS Installation Guide
RVS/RCS
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for echoflex RVS-A-XW

  • Page 1 Installation Guide This guide covers all models of RVS vacancy and RCS occupancy ceiling sensors. These models include: RVS-A-XW Vacancy sensor with small motion short range lens (1000 sq. ft.) RVS-B-XW Vacancy sensor with large motion large range lens (1900 sq. ft.) RVS-DA-XW Dual-tech vacancy sensor with small motion short range lens (1000 sq.
  • Page 2: Sensor Operation

    100 seconds. A LED under the PIR lens will blink when an occupied state telegram is sent. A linked Echoflex controller has an occupancy timer that is reset only when receiving an occupied state telegram so the lights will remain on so long as the sensor continues to sense occupancy.
  • Page 3: Mounting The Sensor

    controllers receive an occupied state telegram before their occupancy timer expires, the lights will remain on. PIR Motion Detection The sensors use a PIR sensor element that detects motion by measuring the infrared energy emitted by objects. The sensors are calibrated to detect the temperature range of the human body.
  • Page 4: Lens Masking

    Select a location to mount the sensor on the ceiling by identifying the movement patterns that will be the most common in the space. • For smaller office spaces where hand motion on a desktop is common, locate the sensor off to one end of the desk, in line with the desk edge or slightly behind so the PIR lens has direct line-of-sight to the keyboard desktop area.
  • Page 5: Test Operating Modes

    Linking the Sensor to a Receiver This process requires the controller or receiver to be mounted, powered and within range of the sensor to be linked. The sensor is a solar powered device that absorbs energy through a solar panel; storing it for use during low light periods.
  • Page 6 LIGHT LEVEL TEST TABLE The green LED will blink according to the energy produced by the solar cell Blinks Foot Candles Charge Level < 40 < 3.7 Non-operational 40-65 3.8 to 6 PIR only operational mode > 65 > 6 Audio mode operational The test will repeat every 2 seconds and run for a duration of 100 seconds.
  • Page 7 1. To enter sensor setting mode, press and hold the teach button until the green LED begins to blink (about 6 seconds). 2. A quick press of the button at this level will allow you to scroll between the test/ setting modes.
  • Page 8 IECC 2015 For the latest info on Echoflex Solutions sensors scan the QR code Copyright 2015-2018 Echoflex Solutions, Inc. | Specifications subject to change without notice. Document 8DC-5543 | Revision 2.0| 8188M21-5543-1 | Rev F Echoflex Solutions, Inc. #1, 38924 Queens Way | Squamish | BC | Canada | V8B 0K8 Toll Free: 888-324-6359 | Phone: (778) 733-0111 | Fax: (604) 815-0078 Email: info@echoflexsolutions.com | www.echoflexsolutions.com...

This manual is also suitable for:

Rvs-b-xwRvs-db-xwRvs-da-xw

Table of Contents