Oil discharge monitoring and control system, according regulation 31 annex i of marpol 73/78, imo resolution mepc.108 49 and imo resolution mepc.240 65
Summary of Contents for VAF instruments OILCON MARK 6M
Page 1
Technical Manual Instructions for installation, operation and maintenance ® OILCON MARK 6M According regulation 31 Annex I of MARPOL 73/78, IMO Resolution MEPC.108(49) and IMO Resolution MEPC.240(65) Oil Discharge Monitoring and Control System Publication nr TIB-641-GB-1117 Supersedes TIB-641-GB-0617...
Oilcon Oil Discharge Monitor and Control System. For IOM information of associated equipment supplied by VAF Instruments, refer to the separate manual supplied with those products. This manual contains important information for the installer, the operator and for your maintenance department.
While every precaution has been taken in the preparation of this manual, no responsibility for errors or omissions is assumed. Neither is any liability assumed for damages resulting from the use of the information contained herein. Specifications can be changed without notice. ® Oilcon is a registered trademark of VAF Instruments B.V.
2 PRODUCT DESCRIPTION ® The Oilcon Oil Discharge Monitoring and Control System continuously samples ballast water being discharged overboard and measures the oil content and controls the discharge of the ballast water and plays therefore a central role in the Oil Discharge Monitor and Control System. ®...
2.2 PRODUCT CONFIGURATION ® The Oilcon Oil Discharge Monitoring and Control System comprises the elements labelled as: Main Control Unit (MCU). Electro Pneumatic Unit (EPU) o I/S signal cable o Starter box Skid assembly Pump/motor assembly ...
2.2.2 Electro Pneumatic Unit (EPU) Reference drawings Dimensional drawing and parts list EPU 1-2 sample valves Mark 6M 0806-1287 The Electro Pneumatic Unit (EPU) contains the control electronics and the solenoid valves to switch the pneumatic signals. It also contains the Zener barriers for the input signals from the flowmeter(s), skid flow meter and measurement cell.
2.2.3 Skid assembly Reference drawings Dimensional drawing and parts list ballast skid Mark 6M 0806-1288 The skid assembly contains the necessary items to handle the sampled ballast water and to measure the oil content. In the skid assembly there is a pneumatically operated shuttle valve (5), and a window wash pump (1).
2.2.6 Sample probe valve assembly Reference drawings Dimensional drawing sample valve Mark 6 0806-1077 Part list sampling probe pipe connection Ø15 mm Ballast Monitor Mark 6M 0806-1265 Part list isolating valve Ø15 Ballast Monitor Mark 6 0806-1268 For taking a representative sample of the ballast water to measure the oil level content, a sample probe valve assembly is provided.
Page 14
CONTROL Sample point: 1 22-11-11 window wash Oil type: 5 10:38 Concentration discharge Flow m3/h dirty Skid Flow com: O Speed 10.0 pos: O Discharge rate l/nm segregated Total oil com: C Latitude 5321.756N pos: C Longitude 00711.854E EPU: OK free: 1927296 kB Figure 2 For correct operation of the system it is important, that during operations an un-interrupted supply of...
3 TECHNICAL SPECIFICATION 3.1 GENERAL Range 0 – 1000 ppm Type of oils In accordance with type approval certificate oils as per MEPC 108(49) and biofuel blends as per MEPC 240(65) Accuracy In accordance with IMO Resolution MEPC 108 (49), the system response is within the accuracy specified.
Output signals USB Flash drive with a type A connector USB 1.0 compatible and formatted according to FAT16 Serial output Alarm relay (X3) NO/NC contact, rating 250 VAC – 5 A or 30 VDC – 5 A Failure-24V relay (X4) NO/NC contact, rating 250 VAC –...
3.7 BIOFUEL GUIDELINES AND DEFINITIONS According MEPC.1/Circ.761 the following definitions are given. Bio-fuels are ethyl alcohol, fatty acid methyl esters (FAME), vegetable oils (triglycerides) and alkanes (C10-C26), linear and branched with a flashpoint of either 60°C or less or more than 60°C, as identified in chapters 17 and 18 of the IBC Code or the MEPC.2/Circular/tripartite agreements.
4 SAFETY INSTRUCTIONS 4.1 SAFETY PRECAUTIONS All precautions have been taken to ensure, in so far as reasonable practical, that the equipment has been designed and constructed to be safe and without risk to health or the environment when properly used. Provided that the recommendations contained in this manual are carefully adhered to, no circumstances are foreseen where the equipment will present a health or safety hazard.
5 UNPACKING Let the equipment acclimatize inside the closed box for at least one hour at the location where the ® Oilcon Oil Discharge Monitoring and Control System will be installed. When the equipment is taken out of the box, please leave the special protection supplied with the equipment as long as possible in place to avoid any damage.
Page 22
Orifice Plate Thickness: 6 mm Material: Stainless Steel Diameter and bore: Specific to each installation Figure 7: Electronic Differential Pressure Transmitter and Orifice Plate Skid Assembly Weight: 20 kg Dimensions: 500 mm x 420 mm x 177 mm (W x H x D) Air Connections: 6 mm and 10 mm tube Water connections:...
6 INSTALLATION 6.1 INTRODUCTION This specification sets out the requirements for the installation, operation and maintenance of an ® Oilcon Oil Discharge Monitoring and Control System on board a typical tanker. It should be studied carefully before actually commencing any operation or work. For the purpose of installation the system can be divided into 4 categories: 1.
6.2.2 Air supply ® For a trouble free and satisfactory operation of the pneumatic components in the Oilcon Discharge Monitoring and Control System a supply of clean, dry air at a constant pressure is essential. Air supply conditions EPU Valve control 4,0 bar nom., 7 bar max.
CAUTION: BEFORE THE SYSTEM IS PUT INTO OPERATION OR TESTED ALL PIPEWORK MUST BE FLUSHED AND CLEARED FROM DIRT OR FOREIGN MATTER. Reference drawings Dimensional drawing and parts list ballast skid Mark 6M 0806-1288 Schematic installation diagram Oilcon Monitor System with 1x dP/I transmitter Mark 6 0806-8035 ...
Before connecting the system piping to the pump, the unit is to be securely fastened to the bulkhead. Long or heavy piping sections shall not be supported from the pump but by separate supports. ALIGNMENT: No inspection or corrections to pump/motor alignment are necessary. Install the oil reservoir and top up the reservoir with the supplied oil.
Where it is not possible to mount into a vertical pipe then a horizontal section may be used and the probe located as shown in drawing 0806-1265. VAF Instruments recommend that whenever possible the sample probe should be installed on the upstream side of the orifice plate.
5 x pipe diameters after the orifice plate. It must be stressed that if above installation requirements cannot be met, VAF Instruments should be consulted for advice. VAF Instruments cannot held be responsible for any flowmetering system installed incorrectly or without due consultation.
6.3.8 dP/I transmitter The electronic differential pressure transmitter is a two- wire transmitter which converts the differential pressure developed by the flow sensor into a 4–20mA signal. Select a location for the transmitter that is close to the orifice plate, not exceeding 16m and where the ambient temperature will not exceed 90°C nor be less than -40°C.
WARNING: IN HAZARDOUS ZONES WITH EXPLOSION PROOF REQUIREMENTS THE COVERS MUST BE TIGHTENED WITH AT LEAST 7 TURNS. IN HAZARDOUS ZONES WITH INTRINSICALLY SAFE OR NON-INCENDIVE REQUIREMENTS, THE CIRCUIT ENTITY PARAMETERS AND APPLICABLE INSTALLATION PROCEDURES MUST BE OBSERVED. CABLE ACCESS TO WIRING CONNECTIONS IS OBTAINED BY ONE OF THE TWO CABLE CONDUIT OUTLETS.
The replacement of components can only be done by personnel trained to act on equipment intended for use in potentially explosive atmospheres. Spare parts must only be genuine parts supplied by VAF Instruments. During installation there is no need to operate the system and thus to switch the EPU on.
Maximum fuse current 16A. Cable terminations for individual conductors should be finished with a pin terminal crimped on the conductor. Cables are not supplied by VAF Instruments, unless specifically ordered. 6.5.1 Electro Pneumatic Unit (EPU)
6.5.2 Starter box The starter box is used to switch and control the electrical supply to the sample pump motor and contains a relay and thermal relay to protect the pump for overheating. It may be mounted to any suitable location adjacent to the EPU or pump motor. The unit is mounted by four holes which accept 4 mm bolts.
6.7 INSTALLATION CHECKLIST 6.7.1 General installation checks 1. Is all pipework of correct materials and dimensions? 2. Is all pipework adequately supported? 3. Does the maximum distance from furthest sample probe to the skid give a system response time of less than 40sec? 4.
6.7.3 Starting interlock and/or overboard valve control IMO Resolution MEPC 108 (49) entitled: ® “Guidelines and specifications for Oilcon Oil Discharge Monitoring and Control Systems for tankers” ® Oil tankers of 150 gross tonnage and above shall be fitted with an Oilcon Oil Discharge Monitoring control system approved by the Administration and designed and installed in compliance with the Guidelines and Specifications for Oil Discharge Monitoring and Control Systems for Oil Tankers...
0806-5019. This also incorporates a starting interlock. VAF Instruments advise that prior consultation is made with the classification society surveyor in each case to ensure that the arrangement will be acceptable both as to the operation and with regard to safety.
0.015 Internal surface area of the pipe 0.001 2 ∙ 0.015 2 ∙ 0.001 0.013 ∙ ∙ 0.013 1.33 ∙ 10 0.5 Sample flow rate ∙ Therefore ∙ . ∙ . ∙ ∙ 30.5 6.7.5 Final check Has completed system been inspected as a whole with regard to safety?
Figure 13 Figure 14 Figure 15 All cable connections to EPU and Connection Box Skid Strip the cable Guide the stripped cable through the synthetic insert M Fold back the screen over the synthetic insert M Push the synthetic insert M in the cable gland N ...
6.8.5 Multi Cable Transit (Bulkhead Penetration) Reference drawings Multi cable transit Ballast Monitor Mark 6 0806-8070 Figure 22 Figure 23 Figure 24 Installation of MCT Place insert-blocks U Place cables and air pipes in accordance with size of the insert-blocks ...
6.8.6 Water and Airline connections Skid Reference drawings Dimensional drawing and parts list EPU 1-2 sample valves Mark 6M 0806-1287 Dimensional drawing and parts list ballast skid Mark 6M 0806-1288 Bulkhead penetration and piping diagram Mark 6M 0806-8038 CC DD Figure 25...
6.8.7 System settings. Figure 29 Figure 30 Fresh water regulator JJ. Water pressure set knob, set pressure to 1,5 bar KK. Fresh water filter Air regulator LL. Air pressure set knob, set pressure to 4 bar minimum Figure 31 Starter Box MM.
7 OPERATING INSTRUCTIONS 7.1 LAYOUT OF THE MCU ® Operation of the Oilcon Oil Discharge Monitoring and Control System is controlled and recorded by the MCU. A representation of the control panel of the MCU, as fitted in the Cargo Control Room, is shown below.
A printout of the data can be made following the procedure as describe in section 7.2.1.3. A printer is not provided by VAF Instruments. Since all data is saved in the internal memory of the MCU and can by copied to a USB flash drive there is no actual need for a printer.
7.2 OPERATING THE MCU AND MENU LAYOUT The MCU has a menu layout as show below. STARTUP WARNING 1.2.1 CONFIG 1.2.2 1.2.3 1.2.4 1.2.5 1.2.6 1.2.7 1.2.8 1.2.9 1.2.10 1.3.1 1.2.11 DATA PRINTER 1.2.12 1.2.13 1.2.14 1.3.2 1.2.15 1.2.16 SELFTEST 1.5.1 SETUP 1.5.2.1...
Page 47
In the different menus the following keys are available: Navigation Operations BACK Previous menu SAMPLE Start sampling operations Scroll up STOP Stop sampling operations DOWN Scroll down FLUSH Start flush sequence Previous screen W WASH Start windows wash sequence Next screen Next setting Previous setting Menus...
7.2.1 Standby mode (menu 1) When the MCU and EPU are both powered on and the key switch is turned to the “Control” position, the MCU goes into the standby mode in menu 1. CONTROL Sample point: 1 22-11-11 standby Oil type: 5 10:38 Concentration...
7.2.1.1 Information mode (menu 1.1) The information mode is entered when the < ? > key is pressed in menu 1. The mode gives additional information about system operation and operational actions which can be taken if e.g. an alarm situation occurs. Depending from which menu the information mode is activated, different texts will be displayed.
7.2.1.2 Configuration mode (menu 1.2) The configuration mode is entered when the <CONFIG> key is pressed in the menu 1. The mode is used to set up the system during installation and this should only be done by a trained service engineer.
Page 51
When the <PRV> or <NXT> key is pressed, the previous or next setting is selected and value entered in the current menu is automatically stored. The following settings in the configuration menu (menu 1.2.1 up to menu 1.2.16) can be set: Menu Description Range...
7.2.1.3 Data mode (menu 1.3) The data mode is entered when the <DATA> key is pressed in the menu 1. The mode is used to print out logged data with a printer or copy this data to a USB flash drive. In the data mode a selection has to be made whether the data is printed to a printer or copied to a USB flash drive.
The MCU logs data at the following intervals: at the start and at the end of the discharge operation; at ten minutes intervals (or less, if set by the operator); at the occurrence of any alarm; if automatic or manual mode is selected;...
7.2.1.5 Setup mode (menu 1.5) The setup mode is entered when the <SETUP> key is pressed in the menu 1. The mode is used to setup the system for a specific discharge operation. When the setup menu is entered, 3 options are available: ...
Page 55
Total oil limit According to the regulations the maximum “total oil limit” should never exceed: 1/30.000 of the last cargo by a new ship 1/15.000 of the last cargo by an old ship Reset total oil Accoring to the regulations only at the start of each new ballast voyage it is allowed to reset the total oil amount.
7.2.1.5.2 Setup mode (menu 1.5.2) The setup mode is entered when the <CHANGE> key is pressed in the menu 1.5.2. In order to setup the system for a specific ballast water discharge, it is necessary to enter specific parameter settings. In the setup mode the settings can be changed by either entering a numeric value or by selecting a preset value.
Page 57
The following settings in the setup menu (menu 1.5.2.1 up to menu 1.5.2.13) can be set: Menu Description Range Remark 1.5.2.1 Sample point 1…6 The value to be entered is the number of the sample point from which a sample is taken. 1.5.2.2 Discharge mode clean ballast / dirty ballast...
7.2.1.5.3 Calibration flush mode (menu 1.5.3.0) After the <FLUSH> key in the setup mode (menu 1.5) is pressed, the system prepares to go into sampling mode by initiating a calibration flush sequence. The calibration flush sequence is used to clean the system prior to sampling and to check the condition of the detector cell and the system.
7.2.1.5.4 Idle mode (menu 1.5.3) After the flush sequence has finished and idle mode has been reached the system is ready for discharge operations. The system stays idle until the operator enters the next command. From idle mode the following modes can be selected: ...
7.2.1.5.4.2 Shutdown mode (menu 1.5.3.2) The shutdown mode is entered when the <STOP> key is pressed in menu 1.5.3. If the shutdown mode is entered from idle mode (menu 1.5.3) the system will initiates a shutdown sequence. The shutdown sequence consists of approximately 2 minutes backward flush and 2 minutes forward flush.
7.2.1.5.4.3 Idle setup mode (menu 1.5.3.3) The idle setup mode is entered when the <CHANGE> key is pressed in menu 1.5.3. In menus 1.5.2.1 – 1.5.2.13 the system has been setup for a specific discharge operation. Next the system goes through the calibration flush sequence, cleaning and calibrating the system and reading it for discharging ballast water.
7.2.1.5.4.4 Self test mode (menu 1.5.3.4) The selftest mode is entered when the <SELFTEST> key is pressed in menu 1.5.3. In the self test mode and internal loop is checked and an overview is displayed of all alarms since the MCU is last powered down. CONTROL Sample point: 1 22-11-11...
7.2.1.5.4.5.1 Information mode (menu 1.5.3.5.1) The information mode is entered when the < ? >key is pressed in menu 1.5.3.5. The mode gives additional information about system operation and operational actions which can be taken if e.g. an alarm situation occurs. Depending from which menu the information mode is activated, different texts will be displayed.
7.2.1.5.4.5.3 Manual flush mode (menu 1.5.3.5.3) The manual flush mode is entered when the <FLUSH> key is pressed in menu 1.5.3.5 After the <FLUSH> key is pressed, the system initiates a manual flush sequence. The sequence consists of approximately 12 seconds window wash and a total of 3 minute forward flush and calibration.
7.2.1.5.4.5.5 Self test mode (menu 1.5.3.5.5) The selftest mode is entered when the <SELFTEST> key is pressed in menu 1.5.3.5.5. In the self test mode and internal loop is checked and an overview is displayed of all alarms since the MCU is last powered down. CONTROL Sample point: 1 22-11-11...
7.3 SHORT REFERENCE GUIDE FOR OPERATING THE MCU NOTE: ® The Oilcon Oil Discharge Monitoring and Control System must be operated as directed under the regulations given in Marpol 73/78, to prevent discharge of oil contaminated water overboard. Where instructions in this manual may apparently conflict with the Marpol requirements, then at all times the Marpol regulations are leading.
Page 67
Press the SETUP key to enter the setup mode. Check if all parameter in the setup are correct and change them if necessary. o Sample point 1…6 o Discharge mode clean ballast/dirty ballast o Total oil limit 0…40,000 l o Reset total oil Yes/No o Discharge alarm...
Increase the speed of the cargo pump. Watch the discharge rate on the MCU, it will increase as the speed of the cargo pump is increased. NOTE: If the discharge rate approaches the maximum permissible (i.e. 30 l/NM), it can be reduced by slowing down the cargo pump.
7.4 MISCELLANEOUS This section is to describe problems that may be encountered during operation and the possible reasons. 7.4.1 Oil content reading higher than expected During a normal discharge run of ballast water the ppm reading should be between 50 to 150 ppm assuming that sufficient time has been left to allow the oil to settle out in the tank.
7.5 OPERATIONAL ALARMS NOTE: ® At all times the Oilcon Oil Discharge Monitoring and Control System must be operated as directed by MARPOL 73/78 to prevent discharge of oil contaminated water overboard. There are necessarily a number of alarm conditions in the MCU. Irrespective of what caused the alarm, the result is the same.
Alarm Description ® If for any reason there is no flow through the Oilcon Oil Discharge Monitoring and Control System the NO FLOW alarm is activated. The Sample pump will be stopped automatically to prevent any damage to the pump or motor. No flow If in flush or shutdown mode the system will return to standby mode.
7.6.1.1 Flowmeter In the event of failure of the discharge flow metering system, the flow rate should be estimated by the best means available and entered into the MCU manually as described above. The flowrate can be estimated by: cargo pump characteristic curves, a copy of which should be included in this manual;...
7.7 SYSTEM OVERRIDES The MCU provides a number of output signals to allow flexible means of controlling the ballast water discharge system. Two outputs are under the direct control of the MCU and these are used to automatically control the discharge system: to stop the discharge when the alarm points are reached and to permit discharge when the discharge rate of oil is within limits.
7.7.3 Discharge control answer-back It is necessary for the MCU to know if the command output has been obeyed correctly. Hence, an input is provided to signal the “status” of the discharge control system. The input could be from e.g. a micro switch on the overboard valve.
8 MAINTENANCE 8.1 MAINTENANCE GENERAL The Oil Discharge Monitor and Control System is an assembly of components forming a complete system. It comprises a mix of pneumatic, electronic and mechanical components. Once a control system is functioning correctly there is no test, or tests, which can be applied to guarantee successful operation for a stated period of time.
8.2 ROUTINE MAINTENANCE ® There is little routine maintenance that can be carried out on the Oilcon Oil Discharge Monitoring and Control System. The major requirement is to ensure that the lubricator in the system is kept topped up and a regular check of the air regulator housings for excess water. 8.2.1 Sample pump/motor lubricator The sealing device of the sample pump requires no maintenance or adjustment.
No maintenance on this unit is envisioned. Should the unit fail to operate, a replacement unit should be installed. If any water leakage through the end cap bleed holes is detected, the assembly should be delivered to a qualified VAF Instruments service point for overhaul. 8.2.6 2-Way pneumatic valve(s) No maintenance on this unit is envisioned.
8.3 TEST AND CHECK-OUT PROCEDURE CAUTION: UNDER NO CIRCUMSTANCES SHOULD THE PUMP RUN WITHOUT LIQUID. THE PUMP HOUSING MUST FIRST BE FILLED WITH LIQUID, OTHERWISE THE PUMP WILL SEIZE AND DAMAGE WILL OCCUR. Before a test is carried out, the person in charge should familiarise himself/herself with the operation of the system and ensure the following conditions are met: ...
Page 79
CONTROL Sample point: 1 22-11-11 sample Oil type: 5 10:38 Concentration M 400 discharge Flow M 1000 m3/h dirty Skid Flow com: C Speed M 15.0 pos: C Discharge rate l/nm segregated Total oil com: C Latitude 5321.756N pos: C Longitude 00711.854E EPU: OK...
Page 80
21. Check the display of the MCU for correct information. CONTROL Sample point: 1 22-11-11 idle Oil type: 5 10:38 Concentration M 400 discharge Flow M 2000 m3/h dirty Skid Flow com: C Speed M 15.0 pos: C Discharge rate l/nm segregated Total oil...
Page 81
CONTROL Sample point: 1 22-11-11 sample Oil type: 5 10:38 Concentration M 400 discharge Flow M 1000 m3/h dirty Skid Flow com: O Speed M 15.0 pos: O Discharge rate l/nm segregated Total oil com: C Latitude 5321.756N pos: C Longitude 00711.854E EPU: OK...
Page 82
41. Press the <NXT> key until “speed ind.” is selected. Use the “+” and “-” keys to change the ship’s speed to “automatic”. 42. Press the <NXT> key until “flowrate ind.” is selected. Use the numeric keys to change the flow rate to “automatic”.
Page 83
CONTROL Sample point: 1 2 22-11-11 sample Oil type: 8 10:38 Concentration discharge Flow m3/h dirty Skid Flow com: O Speed 10.0 pos: O Discharge rate l/nm segregated Total oil com: C Latitude 5321.756N pos: C Longitude 00711.854E EPU: OK free: 1927296 kB STOP FLUSH...
Page 84
65. Press the <ACK> key to stop the alarm. The MCU returns back to “idle mode”. 66. Press the <SAMPLE> key to start the “sample mode” 67. Check that the ship’s speed, flow rate and oil concentration are all displayed on the MCU Wait for the overboard discharge valve to open.
9 REPAIR OR REPLACEMENT SAFETY PRECAUTIONS: MAKE SURE THAT ALL SAFETY REQUIREMENTS AS DESCRIBED IN SECTION 4.1 ARE MET BEFORE ANY WORK IS COMMENCED. NOTE: If any work is carried out on the monitor, the following precautions should be taken before any work is commenced: ...
WINDOW WASH PUMP Drawing 0871-1213 shows the window wash pump and will help to visualize the different parts. NOTE When the pump is disassembled for repairs, all matched parts should be handled carefully to avoid damage to lapped or honed surfaces. CAUTION Repair work must be carried out by qualified specialist personnel.
12. Seal the hole of the motor shaft using e.g. tape or a plug diameter 30 mm. Protect the sleeve on the motor shaft from damage. If a new motor is being installed the bushing (27) is supplied fitted to the original VAF Instruments spare part.
1. If the electric motor was removed or replaced, inspect the surface of the bushing (27) for scratches. If the surface is damaged, the VAF Instruments motor and bushing will need to be replaced completely, as these items are critical for the gas tight seal.
9.4 DIFFERENTIAL PRESSURE TRANSMITTER – FUJI Do not open the cover from the amplifier with active DC power supply in hazardous area. 9.4.1 Zero adjustment of DPT – FUJI 1. Keep the transmitter energised for at least 10 minutes. 2. Remove the covers from the DPT electronics housing. 3.
9.5 DIFFERENTIAL PRESSURE TRANSMITTER – ABB Do not open the cover from the amplifier with active DC power supply in hazardous ara. 9.5.1 Zero adjustment of DPT – ABB 1. Keep the transmitter energised for at least 10 minutes. 2. Remove the covers from the DPT electronics housing and slide away the tagplate. 3.
If the ODME cannot be repaired following the guidelines as described in section 15, contact VAF Instruments for instructions. In the event parts of the ODME have to be sent back for repair, send it directly to: VAF Instruments B.V. Vierlinghstraat 24 3316 EL Dordrecht...
15 TROUBLE SHOOTING AND FAULT FINDING 15.1 INTRODUCTION FAULT FINDING GUIDE The first requirement when attempting to find a fault in the system, is to ensure that the monitor is correctly set up to run. A large number of service problems can be directly related to a simple mechanical fault, which appears to cause a large number of seemingly unrelated problems.
MCU. If the fault cannot be rectified from this guide, please contact VAF Instruments to request specialist assistance.
Page 94
Correct Functioning Path When Faulty The No Flow alarm is now enabled. Refer to section 15.11.1.2 Any problem with the fresh water supply will be highlighted at this point. At this point the calibration is checked. Refer to section 15.3.1 Since the monitor is operating on fresh water, the ZERO ERROR alarm will be activated, if there is any contamination.
15.3 CALIBRATION ALARMS 15.3.1 Zero error alarm Probable causes Action Sample pump cavitating Check the pressure gauge settings on the Skid Assembly. For correct settings see section 15.11.2 Flushing water contaminated Check flushing water for oil, dirt or of it contains air. ...
15.3.2 Path dirty alarm Probable causes Action Windows of detector cell dirty Operate the window wash pump a few times by pressing [WINDOW WASH] during the flush cycle. This should clean the windows sufficiently to cancel the alarm. If the alarm persists it is necessary to clean the windows in the measurement cell manually as described in section 9.1.
9 in EPU for data transmission. Term.1/2 or 5/6 for data transmission from MCU Term.3/4 or 8/9 for data transmission from EPU If the alarm is persistent, please contact VAF Instruments 15.4.5 Led feedback error Probable causes Action ...
15.4.6 Flow overrange failure Probable causes Action Overboard discharge flowrate to Check the overboard discharge flowrate and reduce if high. necessary. Flowmeter not functioning Check the connections of the related flowmeter. correct. Check the calibration of the related flowmeter. ...
15.4.9 Discharge rate failure Probable causes Action Discharge rate to high. Check the overboard discharge rate and reduce it to clear the alarm. Also consult section 7.5 15.4.10 Total discharge oil limit alarm Probable causes Action The maximum oil limit is ...
To check the fuse, remove the front panel from the EPU. The fuse is located on the back face of the front panel. if problems remain the power supply should be replaced with a spare one and shipped to VAF Instruments for repair.
15.7 AIR SUPPLY PROBLEMS 15.7.1 Air supply failure Probable causes Action No air supply Check the air supply to the EPU, normally set to 4.0 bar (0.4 MPa). Check the ship’s control air supply. Check all connections for leakage. ...
15.9 PNEUMATIC VALVE PROBLEMS For repair procedures of pneumatic valves consult section 8.2.5. 15.9.1 Valve not functioning Probable causes Action No air supply Check the air supply unit regulator in the air supply line to the valve, normally set to 4.0 bar (0.4 MPa). ...
15.10 WINDOW WASH PUMP PROBLEMS For disassembly and re-assembly procedures of the window wash pump consult section 8.2.4. 15.10.1 Pump does not work Probable causes Action Air supply failure Check the air supply to solenoid V12 in the EPU, minimum 5.0 bar (0.5 MPa).
15.11 SAMPLE PUMP PROBLEMS 15.11.1 Electrical problems 15.11.1.1 Pump runs but the green indicator on the starter box is off Probable causes Action Indicator failure. Check power supply to indicator lamp. Check indicator lamp. 15.11.1.2 Pump should be running but is off Probable causes Action 3-phase power supply failure.
15.11.2.1 No flow Probable causes Action No fresh water supply. Check if the 3-phase power supply is switched on. (low discharge pressure < 2 bar Check the fuses of the 3-phase power supply. the during flushing). water supply to the pump. (<...
15.12 DIFFERENTIAL PRESSURE TRANSMITTER PROBLEMS NOTE: For disassemble and re-assemble instructions consult section 8.2.7. 15.12.1 No line current Probable causes Action Transmitter connections. Check the wiring polarity and continuity. Check for shorts or ground loops. Check if the power supply connector is connected to the main board.
In case the fault finding guide does not result in a proper working of the system, the fault finding form can be used. This form should be filled in and returned to VAF Instruments Service department. The form is included in this technical manual 641.
Page 108
Cell K-Factor: ………………… The following steps have to be followed in order for VAF Instruments to determine if the ODM system is having a malfunction. If during the complete procedure an alarm is triggered, push the Alarm rest button and write down the Alarm.
Page 109
Action Step Description Make sure the EPU in the engine room is switched ON. Reset the MCU by pushing the Reset button. Turn the key switch of the MCU to Control Mode. Wait for 1 minute and write down any alarm which comes up. Acknowledge the alarm by pressing “ACK”...
Certificate Type ® EC type examination certificate Oilcon Oil Discharge Monitoring and DNV-GL Control System Det Norske Veritas – Oilcon Mark 6M Germanischer Lloyd ® Confirmation of Product Type Oilcon Oil Discharge Monitoring and Approval Control System American Bureau of...
18 ABBREVIATIONS 18.1 ABBREVIATIONS Automatic Transmission Fluid Cargo Control Room Differential Pressure Transmitter Electro Pneumatic Unit Global Position System International Maritime Organization Installation, Operation and Maintenance Main Control Unit Normally Open Normally Closed Multi Cable Transit I/S signal cable Intrinsically safe signal cable 18.2 SYMBOL LIST...
19 SPARE PARTS 19.1 STANDARD SPARES ® Standard spare parts supplied with every Oilcon Oil Discharge Monitoring and Control System delivery: Description Stock number Quantity Standard spare parts OIL DISCHARGE MONITOR system 0390-1301 O-ring I.D. 53.70 x 1.78 mm Bulkhead seal lubricant 500ml Cleansing brush Slow fuse 630 mA slow...
Page 171
Description Stock number Quantity Window wash maintenance kit See drawing 0871-1213 Spare parts kit 0390-1403 See drawing number for the kit content Description Stock number Quantity Electrical items spares kit 0390-1211 LED Green (starter box) LED Red (starter box) Fuses 500 mA slow (EPU) Fuses 630 mA slow (EPU) Other spare parts might be needed occasionally.
20 WARRANTY CONDITIONS 1. Without prejudice to the restrictions stated hereinafter, the contractor guarantees both the soundness of the product delivered by him and the quality of the material used and/or delivered for it, insofar as this concerns faults in the product delivered which do not become apparent during inspection or transfer test, which the principal shall demonstrate to have arisen within 12 months from delivery in accordance with sub article 1A exclusively or predominantly as a direct consequence of unsoundness of the construction used by the contractor or as a consequence of...
Page 173
4. Defects not covered by the guarantee are those which occur partially or wholly as a result of: a. non-observance of the operation and maintenance instructions or other than foreseeable normal usage; b. normal wear and tear; c. assembly/installation by third parties, including the principal; d.
Page 175
Vierlinghstraat 24, 3316 EL Dordrecht, The Netherlands Specifications subject to change without notice. P.O. Box 40, 3300 AA Dordrecht, The Netherlands VAF Instruments B.V. is an ISO 9001 Certified Company. T +31 78 618 3100 sales@vaf.nl, www.vaf.nl Agents and distributors in more than 50 countries.