Installation Instructions
1.4.5 Removing Current Sensors and Busbars
Remove the current sensor and busbars using the following procedure. Refer to Illustration 1.7.
1.
Remove the terminal label.
2.
Remove the 3 retaining nuts (M10), 1 from each output terminal busbar.
3.
Remove the 6 screws (M4) that connect the current sensors to the base plate, 2 from each sensor.
4.
Lift the 3 current sensors and busbars from the unit.
1
Current sensor
2
IGBT busbar retaining nut
3
Current sensor base plate screw (M4)
Illustration 1.7 Current Sensors and Busbars
8
500 A Current Sensor Kit for
E1/E2 Enclosure Sizes
®
VLT
FC 102, FC 103, FC 202, FC 302
4
5
6
Danfoss A/S © 10/2016 All rights reserved.
Output terminal busbar
Output terminal busbar retaining nut (M10)
Terminal label
MI92Q102