5.2.3
Guidelines for Compressor Overhaul Interval
The compressor overhaul interval is largely affected by the compressor operating conditions, type and
status of refrigerant and oil, and the system/equipment in which the compressor is operated.
The table below lists overhaul intervals recommended by MAYEKAWA which are categorized based on
the compressor operating conditions.
Table 5-4 Standard Package Operation Conditions and Overhaul Interval Guidelines
Category of operating condition
Relatively stable operating condition
Relatively changing operating condition
Frequently started/stopped, and relatively
changing operating condition
Note 1: The above guidelines are only applicable when the compressor is operated within the operation
limits specified separately.
(Refer to Section 2.3.2 "Operation Limits" in this manual.)
Note 2: The above guidelines are only applicable when the compressor undergoes daily and periodic
inspections Specified separately.
(Refer to Section 5.2.1 "Daily Management" in this manual.)
Note 3: Inspect the compressor at the intervals of specified period or operating hours, whichever comes
first.
Note 4: The above guidelines do not constitute any warranty.
Screw Compressor i-series
Chapter 5 Maintenance and Inspection
Application example
Refrigeration and cold
storage
Ice maker/chiller
Heat pump
5.2 Maintenance and Inspection List
5-6
2203M4JE-MY-iS2-N_2017.04.
Recommended Overhaul
Interval
Every 5 years or 40,000
operating hours
Every 4 years or 30,000
operating hours
Every 3 years or 20,000
operating hours