Bryant 569J Series Installation, Start-Up And Service Instructions Manual page 33

Air--cooled condensing units 60 hz, with puronr (r--410a) refrigerant
Table of Contents

Advertisement

10 Ton Circuit A Charging Chart R410a Refrigerant
60
140
54
120
48
Add Charge if
42
Above the Curve
100
36
30
80
24
18
60
12
6
40
0
-6
20
50
100 150 200 250 300 350 400 450 500 550 600
350 700 1050 1400 1750 2100 2450 2800 3150 3500 3850
Pressure at Liquid Valve (PSIG / Kpa)
12.5 Ton Circuit A Charging Chart R410a Refrigerant
60
140
54
120
48
Add Charge if
42
Above the Curve
100
36
30
80
24
18
60
12
6
40
0
-6
20
50
100 150 200 250 300 350 400 450 500 550 600
350 700 1050 1400 1750 2100 2450 2800 3150 3500 3850
Pressure at Liquid Valve (PSIG / Kpa)
Remove Charge if
Below the Curve
38AU501102
C
Fig. 27 - - 569J*12D/E/F Charging Chart (RTPF)
Remove Charge if
Below the Curve
38AU501141
D
Fig. 28 - - 569J*14/D/E Charging Chart (RTPF)
10 Ton Circuit B Charging Chart R410a Refrigerant
60
140
54
120
48
Add Charge if
42
Above the Curve
100
36
30
80
24
18
60
12
6
40
0
-6
20
50
100 150 200 250 300 350 400 450 500 550 600
350 700 1050 1400 1750 2100 2450 2800 3150 3500 3850
Pressure at Liquid Valve (PSIG / Kpa)
12.5 Ton Circuit B Charging Chart R410a Refrigerant
60
140
54
120
48
Add Charge if
42
Above the Curve
100
36
30
80
24
18
60
12
6
40
0
-6
20
50
100 150 200 250 300 350 400 450 500 550 600
350 700 1050 1400 1750 2100 2450 2800 3150 3500 3850
Pressure at Liquid Valve (PSIG / Kpa)
33
Remove Charge if
Below the Curve
38AU501102
C
C150418
Remove Charge if
Below the Curve
38AU501141
D
C150419