TEIP11, TEIP11-PS I/P SIGNAL CONVERTER | OI/TEIP11/TEIP11-PS-EN REV. M
... 2 Use in potentially explosive atmospheres
... Flameproof (enclosure), ATEX 'Ex d'
Temperature classes for the following versions:
TEIP11 Doc. 901068-SMD and TEIP11-PS Doc. 901068-SMD and
TEIP11-PS Doc. 901069-SMD
Temperature class
T4
T4
T6
TEIP11 Doc. 901068 and TEIP11-PS Doc. 901068 and TEIP11-PS
Doc. 901069
Temperature class
T6
T6
T5
T4
T5
T4
T5
T4
T4
Ex limit values
L
i
50 mA
60 mA
100 mA
120 mA
150 mA
Special conditions
The I/P signal converter TEIP11-PS Doc. 901068 or TEIP11-PS Doc.
901069 must be set up outdoors as a pneumatic power supply
when used with combustible gases.
The supplied gas must be kept sufficiently free of air and oxygen
to prevent a potentially explosive atmosphere from forming.
The gas must always be routed to the outside.
Input current
Ambient temperature
120 mA
–55 to 60 °C
100 mA
–55 to 85 °C
60 mA
–55 to 40 °C
Input current
Ambient temperature
50 mA
–55 to 60 °C
60 mA
–55 to 55 °C
60 mA
–55 to 70 °C
60 mA
–55 to 85 °C
100 mA
–55 to 55 °C
100 mA
–55 to 85 °C
120 mA
–55 to 45 °C
120 mA
–55 to 80 °C
150 mA
–55 to 70 °C
U
i
42.5 V
2.125 W
38.8 V
2.328 W
30 V
28 V
25.5 V
3.825 W

FM / CSA

Intrinsically safe FM
FM 'intrinsically safe' (not for metal field housing units)
I.S.: CL I/Div 1/Grp A B C D
FM 'intrinsically safe' (only for metal field housing units)
I.S.: CL I-II-II/Div 1/Grp A B C D E F G
range
S.: CL II/Div 2/Grp G
S.: CL III/Div 2
Non-incendive FM
N.I.: CL I/Div 2/Grp A B C D (not for metal field housing units)
N.I.: CL I/Div 2/Grp A B C (only for metal field housing units)
Intrinsically safe CSA
CSA 'intrinsically safe' (not for metal field housing units)
I.S.: CL I/Div 1/Grp A B C D
range
CL I / Div 2 / Grp A B C D
CSA 'intrinsically safe' (only for metal field housing units)
I.S.: CL I/Div 1/Grp A B C D
CL II / Div 1 / Grp E F G
CL III
CL I / Div 2 / Grp A B C D
CL II / Div 2 / Grp E F G
Non-incendive CSA
FM 'explosion proof' (only for metal field housing units)
X.P.: CL I/Div 1/Grp B C D
D.I.P.: CL II III/Div 2/Grp E F G
CSA 'explosion proof' (only for metal field housing units)
P
i
X.P.: CL I/Div 1/Grp B C D
3.0 W
3.36 W