Mitsubishi Electric MELSEC Q Series Programming Manual page 61

Structured. fundamentals
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

■The following figure shows the examples of index setting and their actual processing devices.
(With the setting of Z0=20 and Z1=-5)
Ladder example
X0
MOV
EN
ENO
K20
s
MOV
EN
ENO
K-5
s
X1
MOV
EN
ENO
s
K2X50Z0
X0
MOV
EN
ENO
K20
s
MOV
EN
ENO
K-5
s
X1
MOV
EN
ENO
s
D0Z0
d
Z0
d
Z1
d
K1M38Z1
d
Z0
d
Z1
d
K3Y12FZ1
Actual processing device
X1
MOV
EN
ENO
K2X64
s
d
Description
K2X50Z0
K2X(50 + 14) = K2X64
Converts K20 to a hexadecimal number.
K1M38Z1
K1M(38 - 5) = K1M33
X1
MOV
EN
ENO
D20
s
d
Description
D (0 + 20) = D20
D0Z0
K3Y12FZ1
K3Y(12F - 5) = K3Y12A
4 PROGRAM CONFIGURATION
K1M33
K3Y12A
Hexadecimal number