Salda AmberAir Compact 4 CX P Mounting And Installation Instructions Manual page 29

Air handling unit with heat recovery system
Hide thumbs Also See for AmberAir Compact 4 CX P:
Table of Contents

Advertisement

Connector
Contact No.
X1
1
2
3
4
X2
1
2
3
4
X3
1
2
3
4
5
6
X4
1
2
3
4
5
6
7
8
X5
1
2
3
4
5
6
7
8
X6
1
2
3
4
5
6
X7
1
2
3
4
5
www.salda.lt
Contact name
MCB FDI TACHO K_1(GND)
MCB FDI TACHO A_1(+10V)
MCB FDI TACHO K_2(GND)
MCB FDI TACHO A_2(+10V)
PE
GND
+24VDC
MCB HOLO
MCB DI1
+12VDC
MCB DI2
+12VDC
MCB DI3
+12VDC
MCB DI4
+12VDC
MCB DI5
+12VDC
MCB DI6
+12VDC
MCB DI7
+12VDC
MCB AI1 (NTC)
GND
MCB AI2 (NTC)
GND
MCB AI3 (NTC)
GND
MCB AI4 (0-10V)
GND
MCB AI5 (NTC)
GND
MCB AI6 (NTC)
GND
MCB AI7 (NTC)
GND
+24VDC
+3,3VDC
GND
I2C_SDA
I2C_SCL
A
Dunctional block name
MCB
Supply fan speed RPM
Extract fan speed RPM
Rotor speed RPM
Heater automatic protection (NC)
Heater manual protection / Water heater protection – thermostat (NC)
Supply air fan failure (NC)
Fire protection input (NC)
By-pass closed (NC)
Rotor alarm (NC) / Heat exchanger pressure relay (NC).
Extract air fan failure (NC)
Supply air temperature sensor
Outdoor air temperature sensor
Exhaust air temperature sensor
Heat exchanger pressure transmitter
Extract air temperature sensor
Reserved
Hydraulic heater water temperature sensor
Connection with EX2-X47
AmberAir Compact 4 CX P
29