AIR SUPPLY UNITS VEGA 350 E VEGA 700 E VEGA 1100 E/W Installation and maintenance manual Subject to technical modification VEGA_P0102_AZ_0002...
General information Warranty Transportation and storage Notes Description Maintenance Table Safety precautions Components Operating conditions Maintenance Cover opening VEGA 350 E, VEGA 700 E Cover opening VEGA 1100 E/W Filter Electrical heater Water heater Control box Dimensions Mounting Start-up Technical data...
Page 3
VEGA 350E/700E/1100E/1100W 0.17 kW; 1.87 A; IP-34 TOTAL: www.salda.lt gu072489 / 2014.03 Stick the auxiliary label on the unit (on an easily accessible place) or on the dashed place of a technical manual in order to keep the important information about the unit.
Supply air flow from 350 to 1000 m3/h. Easy installation: • 6 possible mounting positions; • extremely low height - space saving design. Simple service: • qualitative and ergonomic design (integrated control box); • safe and easy doors opening for filter replacement Economical usage: www.salda.lt...
Unit is designed for ventilation and conditioning systems to supply to a room only clean air (free of chemical compounds causing metal corrosion, of substances aggressive to zinc, plastic and rubber, and of particles of solid, adhesive and fibred materials). • Minimum and maximum permissible air flow temperature between -20°C and +40°C. • Maximum outside humidity 90%. www.salda.lt...
6. Press the upper part of the clip and the hook to the casing (f) and fasten with the same pin as shown in pictures (g, h); 7. Open the cover and keep it hanging on the holders; 8. Retain the reverse order when closing the cover. www.salda.lt...
Page 9
Change the supply air filter after the alert of the control system. The alert about filter contamination is active if the working hours of the unit till the filter change notice are set in Flex control panel. VEGA 350 E, VEGA 700 E VEGA 1100 E/W •...
VEGA 350E/700E/1100E/1100W VEGA 350 E, VEGA 700 E VEGA 1100 E/W • Electrical heaters do not require additional servicing. • The heater has 2 thermal protections: automatic restore which is activated at +50°C and manual restore which is activated at +100°C.
- Three anti-frost protections of water heater are used: outdoor air sensor, return water temperature sensor, air flow thermostat behind water heater. VEGA 1100 W • It is not necessary to take off the screw that fastens the control box during the installation, it is enough to unfasten it a little. VEGA 350 E, VEGA 700 E www.salda.lt...
Page 12
W1, mm W2, mm W3, mm H1, mm H2,mm ø D,mm 350 E 1000 1060 700 E 1200 1260 1025 VEGA L1, mm L2, mm L3, mm W1, mm W2, mm W3, mm H1, mm H2,mm 1100 E/W 1300 1400 www.salda.lt...
MAKE SURE that the air intake damper opens and closes correctly. • The current used by the unit shall be tested for compliance with the maximum allowed current indicated in this document. • Using the remote controller select the necessary fan rotation speed and supply air temperature. www.salda.lt...
0,000 1000 1200 1400 QV, M3/H v1 (max) v2 (mid) v3 (min) P1, kW P2, kW P3, kW VEGA 350 E VEGA 700 E VEGA 1100 E/W Air filter class width L [mm] height H [mm] depth W [mm] model Subject to technical modification.
Page 16
Circulation pump of the heater filter for outdoor air outdoor air temperature sensor air temperature sensor SV1 Heater’s valve actuator PS** external differential pressure switch (optional) VEGA 350 E, VEGA 700 E Outdoor air Supply air VEGA 1100 E Outdoor air Supply air...
The system is not stopped. 5. FOR THE SUPPLIED AIR TEMPERATURE SENSOR Contacts Ain1 are provided for the connection of supply air temperature sensor, GND in connection X1. Supply air temperature sensor’s technical characteristics are provided in the table below. www.salda.lt...
Connection speed 19200 19200 Parity EVEN EVEN Stop bit ModBus type – RTU, MB slave addres – 1. Port settings: RS485, 19200bps, 1STOP, PARITY-NONE Remote control don’t support MB protocol, not connect to MB line. Data address from 0x00 www.salda.lt...
Page 21
Fault signal (electric heater manual reset protection to 100 °C is active, contaminated filters, external signal if con- External fault signal nected ex.,: fire protection) Note: If you noticed any of named fault indications, turn off the power supply, remove fault reason, switch power supply again. www.salda.lt...
Page 39
Check the settings in the remote controller (fan rotation speed, time, date, event, etc.). • Check if the air intake damper is not closed. • Check if the air filter is not contaminated. • Check if the fan needs to be cleaned. • Check if the ventilation system needs to be cleaned. www.salda.lt...
These conditions are readily discernable when the equipment is returned to our factory for inspection. If the direct client determines that equipment is found to be faulty, or a breakdown occurred, he should inform the manufacturer within five working days and deliver the equipment to manufacturer. Delivery costs should be covered by customer. www.salda.lt...