OWNER’S MANUAL Electric Operated Boilers □ □ MODELS: M24E24A M36E24A □ □ M24E36A M36E36A □ □ M24E42/48A M36E42/48A FOR YOUR SAFETY: WARNING: DO NOT STORE OR USE GASOLINE OR OTHER IMPROPER INSTALLATION, ADJUSTMENT, FLAMMABLE VAPORS OR LIQUIDS IN THE ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE VICINITY OF THIS OR ANY OTHER APPLIANCE.
INTRODUCTION To the Kitchen Manager: 1. Read this manual carefully and in its entirety. Contact Market Forge Ind., Inc. for clarification if necessary. 2. Protect your kitchen personnel from scalding and other serious injury by providing training programs to acquaint all equipment operators with the correct and safe methods of operation.
INSTALLATION INSTRUCTIONS ELECTRIC OPERATED BOILERS WARNING: MODELS: • M24E24A • M36E24A • M24E36A • M36E36A READ THIS BEFORE OPENING THE SHIPPING CONTAINER! • M24E42/48A • M36E42/48A CAUTION: BE SURE TO READ: DO NOT AT ANY TIME LAY THE EQUIPMENT DOWN ON ITS BACK, SIDE, TOP OR FRONT. Doing so may damage the equipment and invalidate the warranty.
INSTALLATION INSTRUCTIONS SERVICE CONNECTIONS: CAUTION: Before connecting water to this unit, Electric Operated water supply should be analyzed to make sure hardness is no greater than 2.0 grains and pH Power Supply – Use wire suitable for at least level is within the range of 7.0-8.5. Water which C nominal amp per line wire: fails to meet these standards should be treated 24kW...
OPERATING INSTRUCTIONS CONTROL PANEL: MODELS: • M24E24A • M24E36A • M24E42/48A • M36E24A • M36E36A • M36E42/48A OPERATING THE STEAM GENERATOR: OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS FOR STEAM GENERATORS OPERATING INSTRUCTIONS FIRST CHECK TO BE SURE THAT: A. WATER SWITCH IS IN THE OFF POSITION.
ADJUSTMENTS SETTING THE BOILER CONTROL PRESSURE SWITCHES: PRESSURE CONTROL SWITCH ADJUSTMENT: If boiler fails to maintain steam pressure in operating range, pressure control switch may require adjustment. 1. Start boiler and allow pressure to build up to operating level - 15 PSI (1kg/cm²). 2.
GENERAL TROUBLE SHOOTING TROUBLE POSSIBLE CAUSE REMEDY Water does not enter the a. Water main shut-off. a. Turn on. boiler. b. Power not reaching unit. b. Check main fuse or circuit. c. Probes dirty. c. Remove and clean. d. Water level control board d.
Page 9
TROUBLE POSSIBLE CAUSE REMEDY Water enters boiler very a. Dirty Strainer screen in a. Clean or replace strainer screen, slowly. solenoid valve. part no. 08-4871. Water level in gauge glass a. Top shut off on water gauge is a. Open. fluctuates up and down.
GENERAL TROUBLE SHOOTING TROUBLE POSSIBLE CAUSE REMEDY Short contact button life a. Filling or dressing. a. Do not file silver tips. Rough and / or overheating of b. Interrupting excessively high spots or discoloration will not contacts. current. harm tips or impair their c.
Page 11
RESET LW2 FW - HIGH This test procedure is to be used LED 1 to determine if the control is working properly. LED 2 intended to determine why the control may have failed. If testing shows that the control is LED 3 operating properly,...
ILLUSTRATED PARTS LIST CONTROL BOX ASEMBLY, WITH & WITHOUT COVER ITEM NO. PART NO. DESCRIPTION 08-6549 Switch, Power 94-5127 Switch, Manual Reset 10-5052 Light, Red 94-5003 Control Box Lexan 08-6469 Fuse Holder 98-1680 Board, Water Level Control 08-6472 Relay Tube 08-6475 Relay Base 98-3877...
MAINTENANCE Cleaning the Boiler: Market Forge recommends that the boiler be cleaned periodically due to impurities introduced through the water supply. All water supplies contain some mineral deposits and impurities; the degree varies with geographic location. Market Forge is recommending a cleaning schedule that will keep your equipment in proper, safe working order where water supplies are relatively pure.
Page 26
MAINTENANCE 3. Clean rust, scale and lime deposits from the inside of the boiler with a wire brush. DO NOT DAMAGE COPPER HEATING ELEMENTS - BRUSH LIGHTLY. WORK DEPOSITS TO REAR CORNER AND REMOVE WITH PUTTY KNIFE. 4. After removing all debris, flush out with clean water through the hand-hole and drain . 5.
APPLICATION INSTRUCTIONS Application Instructions for Total Concept Descaler Cleaning of the Boiler Size: Case of 4 -1 Gallon Bottles / Part No. 20-0307 or 1-1 Gallon Bottle / Part No. 20-0307X GENERAL NOTES: Total Concept is designed to be used with water Figure 3 between 160°F to 200°F.
Page 28
APPLICATION INSTRUCTIONS Application Instructions for Total Concept Descaler Cleaning of the Boiler Size: Case of 4 -1 Gallon Bottles / Part No. 20-0307 or 1-1 Gallon Bottle / Part No. 20-0307X Figure 6 Figure 9 6. Energize compartment to release steam 9.