1MRS757799 C
4.3.6
REC615 and RER615
Installation Manual
The allowed range for the fixing screws' tightening torque is
0.7...1 Nm.
5.
Install the plug-in unit into the case.
A070579 V5 EN
Figure 17:
Rack mounted protection relay

Wall mounting protection relay

A mounting kit is needed for wall mounting the protection relay. In addition to the
detailed mounting instructions, the wall mounting kit includes:
Wall mounting frame and rail parts
Back plate
Screws
Dimensions for screw holes
1.
Drill screw holes according to the dimensional drawing.
2.
Mount the wall mounting frame and the rails.
3.
Install the back plate.
4.
Loosen the four M5 fixing screws in the case to fit the case into the mounting
frame.
5.
Mount the case between the rails.
Section 4
Mounting
29