Section 4
Mounting
4.3.2
18
Only use adjustable torque screwdrivers.

Flush mounting protection relay

All the mounting elements are integrated in the protection relay.
Requirements for installation:
Panel cut-out of 165.5 × 161.5 mm
Depth behind the panel 153 mm
A protection relay equipped with optical connections requires a
minimum depth of 180 mm. The allowed minimum bending radius
has to be checked from the optical cable manufacturer.
1.
Loosen the four M5 fixing screws in the case to fit the case into the panel cut-out.
2.
Mount the case to the panel cut-out.
1MRS757799 C
REC615 and RER615
Installation Manual