Danfoss ECL Comfort 210 Operating Manual page 52

Application
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A217/A317
MENU > Settings > Tank temperature
Stop difference
One DHW tank temperature sensor:
Set the number of degrees above the desired DHW temperature that will
stop the DHW heating (charging).
Two DHW tank temperature sensors:
Set the number of degrees above or below the desired DHW temperature,
but measured by the lower tank temperature sensor that will stop the DHW
heating (charging).
See Appendix "Parameter ID overview"
–50 ... 50: Set the number of degrees.
52 | © Danfoss | 2018.03
One DHW tank temperature sensor (example with positive 'Stop
difference' value):
1x194
Temp.
DHW heating
One DHW tank temperature sensor (example with negative 'Stop
difference' value):
Temp.
DHW heating
Two DHW tank temperature sensors, upper and lower
Temp.
DHW heating
Stop difference
Desired DHW temp.
Time
Stop difference
Desired DHW temp.
Time
Upper DHW temp. sensor
Stop difference
Desired DHW temp.
Lower DHW temp. sensor
Time
VI.LG.U3.02

Advertisement

Table of Contents
loading

Table of Contents