Foreword Dear customer, thank you very much for deciding in favour of the DS 500. Please read this installation and operation manual carefully before mounting and initiating the device and follow our advice. A riskless operation and a correct functioning of the DS 500 are only guaranteed in case of careful observation of the described instructions and notes.
10.3 DS 500 with 12 channels ....................18 10.4 Power supply DS 500 standard version 100 - 240 VAC ..........18 X2.1 and X2.2 by standard version 100 - 240 VDC, wired ex works ......18 10.5 Power supply by special version 24 VDC ............... 19 10.6...
Page 4
Table of contents Connect the DS 500 with a PC .................29 Operation DS 500 ......................30 13.1 Main menu (Home) ......................30 13.1.1 Initialization ........................30 13.1.2 Main menu after initialization ................... 31 13.2 Shutdown ........................... 31 13.3 Settings ..........................32 13.3.1...
Page 5
Calibrate touch-screen ....................104 13.14.3 Cleaning ........................104 13.14.4 System Status ......................104 13.14.5 About DS 500 ......................105 13.15 Consumption report with cost settings, export data and webserver ......106 13.15.1 Consumption report (optional)..................106 13.15.2 Cost settings (optional) ....................108 13.16...
Page 6
Screenshots export ....................119 13.17.3 Export System Settings ....................120 13.17.4 Export Report ......................120 13.17.5 Import system settings ....................121 Screenshot function ....................122 14.1 Screenshot saving ......................122 Cleaning ........................123 DS 500 V1.55 Page 6 of 124...
This instruction manual has to be available at any time at the operation site of the DS 500. Regional and national regulations respectively, have to be observed in addition to this instruction manual if necessary.
It is imperative to connect the plant to earth or to connect ing to the regulations. protective conductor accord Do not use plug adapters at the power plug. Have the power plug replaced by qualified skilled persons, if required. DS 500 V1.55 Page 8 of 124...
Page 9
E.g. flexible insulating tubing, type BIS 85 (Bierther GmbH). The additional insulation of the connecting leads (mains connection, alarm and indicator relays) can be implemented as follows: - Terminals (connectors) – Flexible insulating tubing for the connecting leads – Connecting cable DS 500 V1.55 Page 9 of 124...
From recording of the measured data, automatic sensor identification, indication on a big colour screen, alerting, storage up to remote read-out via web server, all that is possible with DS 500. By means of the CS-Soft, software alarms can be sent via SMS or e-mail.
Intended use Intended use The DS 500 data logger serves for the stationary measured data acquisition and storage of analogue and digital input signals. The DS 500 data logger is exclusively designed and constructed for the proper application purpose that is described herein and must only be used correspondingly.
Technical data DS 500 Technical data DS 500 Dimensions of housing 280 x 200 x 95 mm 18 x PG 12 for sensors and supply, alarm relay Connections 1 x RJ 45 Ethernet connection Version panel mounting Cutout panel 250 x 156 mm...
Panel and wall mounting Panel and wall mounting Cut-out panel Dimension of housing 270 x 170 x 90 mm Dimension of holes for wall mounting D = 6 mm DS 500 V1.55 Side 16 of 124...
Connection diagrams of the different sensor types 11 Connection diagrams of the different sensor types By/With consumption sensors and dew point sensors from CS Instruments there is the possibility to provide values as analogue current signal 4 – 20 mA for further working process.
Analog IN + VA 400 Sensor Analog IN - VA 420 I (500µA) The digital data transmission between DS 500 and the sensors FA +VB 24Vdc 400/410 and VA 400/420 occurs via the SDI bus line. -VB GND Ext. Anzeige...
VA 500 VA 520 Analog IN + Sensor Analog IN - The digital data transmission between DS 500 and the sensors I (500µA) FA 500/ FA 510 and VA 500/520 occurs via RS 485 (Modbus). Braun / Brown +VB 24Vdc...
100 kilo ohm external essential + RS485 R = 4K7 - RS485 Analog IN + Attention: Analog IN - The DS 500 is counting a I (500µA) consumption unit, by +VB 24Vdc switching „power on“. -VB GND Ext. Anzeige...
Please make sure that the circuit is closed in any case. 4 .. 20 mA I (500µA) (e.g. CS pressure sensors 1,6/16/40/100/250/400 bar or +VB 24Vdc temperature sensors with 4 - 20 mA) -VB GND Ext. à +4 ...20mA Anzeige DS 500 V1.55 Side 24 of 124...
Page 25
To route the current signal of 4 - 20 mA to an external display, PLC, extern Sensor SPS, ZLT Analog IN - ZLT etc. please use support Pin 9. 4 .. 20 mA I (500µA) +VB 24Vdc -VB GND Ext. à +4 ...20mA Anzeige DS 500 V1.55 Page 25 of 124...
Page 26
To route the current signal of 4 - 20 mA to an external display, PLC, extern Sensor SPS, ZLT Analog IN - ZLT etc. please use support Pin 9. 4 .. 20 mA I (500µA) +VB 24Vdc -VB GND Ext. à +4 ...20mA Anzeige DS 500 V1.55 Page 26 of 124...
+ RS485 - RS485 ß 0...1 / 10 / 30 Vdc Sensor with voltage output in 4-wire technology Analog IN + Sensor Analog IN - I (500µA) +VB 24Vdc -VB GND Ext. Anzeige DS 500 V1.55 Side 27 of 124...
+VB 24Vdc -VB GND Ext. Anzeige 11.7 Connection with RS485 + RS485 RS485 - RS485 Sensor with RS485 interface Analog IN + Sensor Analog IN - I (500µA) +VB 24Vdc -VB GND Ext. Anzeige DS 500 Page 28 of 124...
Reboot the DS 500: See chapter, 13.5.8 Factory Reset The DS 500 can be connected with the PC by a crossover cable, which has a RJ45 plug on each side, or an Ethernet cable with a crossover adapter. Crossover cable with RJ45-plug...
13.1 Main menu (Home) From the main menu, you can reach every available item 13.1.1 Initialization After switching on the DS 500 all channels are initialized and the main menu will appear. Attention: For the first initiation, there may be no...
In case the DS500 has to be set into a strainless state, it needs a defined termination / storage of the recorded data by a proper shutdown Main menu Shutdown This process must always be confirmed by entering the password. DS 500 V1.55 Side 31 of 124...
New password repeat in red font. If you cannot remember the password, please use Master password in order to enter a new password. Remark: The master password is supplied together with the instrument’s documentation. DS 500 V1.55 Side 32 of 124...
Sensor settings/Choice of the sensor type 13.3.2 Sensor settings Important: Sensors from CS Instruments are generally pre-configured and can be connected directly to a free sensor channel! Main menu Settings Sensor settings An overview of the available channels appears after entering the password.
Page 34
There is no uniform standard for the tube inner diameter! (Please, inquire at the manufacturer or measure by your own !) DS 500 V1.55 Side 34 of 124...
Page 35
20 °C, 1000 hPa (according to ISO 1217 intake condition) 0 °C and 1013 hPa (= standard cubic meter) can also be entered as a reference. Do not enter the operation pressure or the operation temperature under reference conditions! DS 500 V1.55 Side 35 of 124...
Value Name displayed only by the DS 500 standard version with 4 channels! Short Name is used only in these two menu items, by the DS 500 versions with one or two extension boards (8 or 12 channels). DS 500 V1.55...
Attention: Before the selected measurement data are recorded, the data logger must be activated after the settings(See chapter 12.4 Logger settings (data logger)). DS 500 V1.55 Side 37 of 124...
Main menu Settings Sensor settings A1 Alarm-Button Relay-buttons It is possible to select from 5 different delays. T0 is preset to no delay. The delays (T1 to T4) are free definable but are common valid for all relays. DS 500 V1.55 Side 38 of 124...
Page 39
Same procedure for the remaining delay times T2-T4 is to apply. Main menu Settings Sensor settings A1 After the alarm activation at channel A1. The settings finished by pushing the button! DS 500 V1.55 Side 39 of 124...
Now the Type CS-Digital is selected for the VA/FA 400 series and confirmed by pressing button. The DS 500 detects, if the connected sensor is a flow or dew point sensor of CS Instruments and set the CS-Digital subtype automatically correct.
Now the Type CS-Digital is selected for the VA/FA 400 series and confirmed by pressing button. The DS 500 detects, if the connected sensor is a flow or dew point sensor of CS Instruments and set the CS-Digital subtype automatically correct.
In addition, you can push the scale manual button and set the measuring range. After confirming with OK, the settings are assumed. Remark: More-Settings only for type CS-Digital available! By pressing the button the settings are ready! DS 500 V1.55 Side 42 of 124...
Page 43
There is no uniform standard for the tube inner diameter! (Please, inquire at the manufacturer or measure by your own!) DS 500 V1.55 Side 43 of 124...
Page 44
20 °C, 1000 hPa (according to ISO 1217 intake condition) 0 °C and 1013 hPa (= standard cubic meter) can also be entered as a reference. Do not enter the operation pressure or the operation temperature under reference conditions! DS 500 V1.55 Side 44 of 124...
Main menu Settings Sensor settings A1 Name description field For input of a name, please enter the text field „Name“. It is possible to set a name with max. 24 characters. Confirmation by pressing the OK-button. DS 500 V1.55 Side 45 of 124...
The value is entered in the corresponding text field. The unit can be freely selected, selection menu is opened by pressing the corresponding unit-button. Confirm the settings by pressing the button. DS 500 V1.55 Side 46 of 124...
Main menu Settings Sensor settings A1 arrow right (2.page)Pressure Setting Textfield Ref.Pressure Reference pressure is the pressure for that the dew point in relaxation will be back-calculated. Default- Value is 1013 mbar (Atm. Pressure). Confirm the settings by pressing the button. DS 500 V1.55 Side 47 of 124...
Output according Namur ( < 4mA to 3.8 mA Measuring range under range >20mA to 20.5 mA Measuring range exceeding Confirm the settings by pressing the button. 3.33 °Ctd 23.313 25.85 °C 5.6314 g/m³ DS 500 V1.55 Side 48 of 124...
Input of a name, please enter the text field „Name“. 0.00 m³/h It is possible to enter a name with max. 24 4589 m³ 0.00 characters. 25,70 °C Confirmation by pressing the OK-button. DS 500 V1.55 Side 49 of 124...
There is no uniform standard for the tube inner diameter! (Please, inquire at the manufacturer or measure by your own !) Main menu Settings Sensor settings A1 diameter unit description field DS 500 V1.55 Side 50 of 124...
20 °C, 1000 hPa (according to ISO 1217 intake condition) 0 °C and 1013 hPa (= standard cubic meter) can also be entered as a reference. Do not enter the operation pressure or the operation temperature under reference conditions! DS 500 V1.55 Side 51 of 124...
13.3.6.1.4 Definition Unit of flow and velocity Main menu Settings Sensor settings A1 Flow description Field Main menu Settings Sensor settings A1 Velocity description Field DS 500 V1.55 Side 52 of 124...
Selection to confirm selection by pressing button. Important! When the counter reach 100000000 m³ the counter will be reset to zero. Remark: After confirmation with OK, the font is black again and the values and settings are accepted DS 500 V1.55 Side 53 of 124...
Output according Namur ( < 4mA to 3.8 mA Measuring range under range >20mA to 20.5 mA Measuring range exceeding “OK” Inputs / changes to be confirmed with button. Return “Back”. to main menu with DS 500 V1.55 Side 54 of 124...
High: Value over limit Low: Value under limit “OK” Inputs / changes to be confirmed with “Back”. button. Return to main menu with DS 500 V1.55 Side 55 of 124...
“CutOff” and insert the required 2.045 value, here 10. With the Reset” button all entries could be set back to zero. “OK” Inputs / changes to be confirmed with “Back”. button. Return to main menu with DS 500 V1.55 Side 56 of 124...
Set-Value to-(Offset) it is possible to set the measurement data to specific value. The positive or negative difference of the Offset is displayed With the Reset-button the Offset could be set back to zero. DS 500 V1.55 Side 57 of 124...
°C are chosen, alternatively the sensor types PT1000 and KTY81, as well as the Unit °F can be selected. More setting options, see chapter 13.3.7.1 Type 0 - 1/10/30 Volt and 0/4 - 20 DS 500 V1.55 Side 58 of 124...
Main menu Settings Sensor settings B3 Consumption Unit of current Consumption Type Pulse Remark: Example with the unit cubic meters. DS 500 V1.55 Side 59 of 124...
Page 60
The available Units for the Unit Counter Type Pulse counter can be set any time to any value you need. More setting options, see chapter 13.3.7.1 Type 0 - 1/10/30 Volt and 0/4 - 20 DS 500 V1.55 Side 60 of 124...
Main menu Settings Sensor settings A1-C4 Type description field No Sensor Is used to declare a not currently needed channel as No Sensor defined. If you go to Type No Sensor Back, channel A1 will appear as unused. DS 500 V1.55 Side 61 of 124...
4 additional channels (M1 –M4) Channels, are available and thus 32 sensor values could be queried. Option is only available with 4 or. 8 channel versions. Settings see chapter 13.3.9 Option Modbus extended channels DS 500 V1.55 Side 62 of 124...
Page 63
Modbus- register type will be selected. The number format and transmission order of each value needs to be defined by Data Type Byte Order. Both have to be applied in correct combination. DS 500 V1.55 Side 63 of 124...
Page 64
Holding Register – UI4(32) - Value: 29235175522 à AE41 5652 Selection Register Type Holding Register, Data Type U1(32b) und Byte Order A-B-C-D HWord LWord HByte LByte HByte LByte 29235175522 => Data Order 1.Byte 2.Byte 3.byte 4.Byte A-B-C-D D-C-B-A B-A-D-C C-D-A-B DS 500 V1.55 Side 64 of 124...
Page 65
By default or value = 0 no scaling is applied don’t scale and displayed in the field is Main menu Settings Sensor settings B3 OK By pressing the button, the inputs are confirmed and stored. DS 500 V1.55 Side 65 of 124...
Modbus 13.3.9 Option Modbus extended channels This option is only available for DS 500 in Version 4- or 8 channels. 13.3.9.1 Activation of the extended Modbus channels Main menu Settings Sensor settings B3 Modbus Settings allow Modbus Extended...
Main menu Settings Sensor settings M1 Modbus ID Nevertheless for each register to be read out individually Modbus ID could be defined. Confirmation by pressing button The other settings are carried out analogously Chapter 13.3.8.2 Modbus Settings DS 500 V1.55 Side 67 of 124...
The length of the file name is limited to 8 characters. The settings are saved as an XML File in the Folder \\DEV0001\SENSORS\PRES16b.xml In addition, a comment can be defined which will be displayed in case of a later import. DS 500 V1.55 Side 68 of 124...
Main menu Settings Sensor settings A1-C4 Type description field Custom Sensor Please select the needed storage location 16:58:35 Druck16b.XML 12.07.2014 SD-Card stick. I0_20Test.XML 10:28:53 14.07.2014 Stromzan.XML 14.07.2014 10:35:30 Select the needed file and confirm by pressing DS 500 V1.55 Side 69 of 124...
2 seconds. And if more than 25 measurement data are recorded at the same time, the smallest possible time interval of the data logger is 5 seconds. DS 500 V1.55 Side 70 of 124...
Page 71
Remark: If the start time is activated, it will automatically be set at the current time plus a minute. DS 500 V1.55 Side 71 of 124...
Page 72
Main menu Settings Logger settings timed Start button/timed Stop button Date/Time description field After pushing the date/time description field a window will appear where the yellow marked area of the time or date can always be set and changed. DS 500 V1.55 Side 72 of 124...
Page 73
The settings cannot be changed, if the data logger runs. Important: If a new recording file should be created, the force new record file button must be activated. Otherwise, the last applied recording file is used. DS 500 V1.55 Side 73 of 124...
Main menu Settings Device settings Overview of Device settings 13.5.1 Set language Main menu Settings Device settings Set language Here you can select one of 12 languages for the DS 500. Remark: Currently only German and English! 13.5.2 Date & Time Main menu ...
DHCP, to a computer. Remark: With activated DHCP (green hook), the automatic integration of the DS 500 in an existing network is possible, without a manual configuration. After pushing, for example the IP address description field, the command window...
Device settings 13.5.4 ModBus settings (Slave) Main menu Settings Device settings ModBus settings For using the DS 500 as RS485 Slave, first it is requested to enable it by activation of of Enable Modbus RTU(RS485). Else in this menu the transmission parameter...
By pressing Erase SdCard all Data on the SD-Card will be deleted. 0000 “Test Sd Card” Selection/activation of starts write- /read cycles. The testresults will be display as results, errors and last errors DS 500 V1.55 Side 77 of 124...
Device settings 13.5.7 Update System Important: Before updating the DS 500 the system settings should be secured either on a USB or the internal SD-Card! 13.5.7.1 Saving System settings Home Import / Export Export System Settings With Export system settings, all existing sensor settings can be exported to a USB stick or to the internal SD card.
Home Settings Device settings System-Update Update-Firmware The update of DS 500 for all new SW parts starts. Important: If the Reboot system button appears after the update, it must be pushed to restart the DS 500! DS 500 V1.55 Side 79 of 124...
Home Settings Device settings System-Update Update-Channels The update of DS 500 channels starts. Important: If the Reboot system button appears after the update, it must be pushed to restart the DS 500! Update Channels DS 500. 13.5.8 Factory Reset Main menu ...
Consumption report and the cost settings. Remark: Is no currency entered, the accordant fields remain empty. See also chapter 13.15.1 Consumption report (optional) 13.15.2 Cost Settings (optional). DS 500 V1.55 Side 81 of 124...
13.7.1 Option „Virtual Channels“ activation After purchasing of the option „Virtual Channels“ the functionality have to be activated first. Main menu Settings about DS 500 Please push the button Buy for „Virtual Channels“ and you will requested to insert the...
Type No Sensor appears. By pushing the button Generic the virtual channel is selected. Pushing the button No Sensor will reset the virtual channel. Confirmation of selection is done by pressing the button DS 500 V1.55 Side 83 of 124...
Page 84
Main menu Settings Sensor Settings Virtual Channels V1 Name text field By pushing the Text field Name a Sensor name could be inserted. The button Store is implemented for storing of sensor settings (custom sensor) see chapter 12.3.2.11 DS 500 V1.55 Side 84 of 124...
Main menu Settings Sensor Settings Virtual Channels V1 1stOperand A1 By pressing a button either for HW-, virtual channel or const. Value e.g. a list of all available measurement channels or measurement values will appear. DS 500 V1.55 Side 85 of 124...
Selecting and validation of the operand by pressing the respective operand. Pressing of the button not used deactivates the operation of the dedicated operand. This approach is analogous for both operations (1st Operation and 2nd Operation) DS 500 V1.55 Side 86 of 124...
Each calculation allows you the use of maximum 3 operands and 2 operations. The calculation is based on following formula: Example: V1a = (1st Operand 1st operation 2nd Operand) 2nd operation 3rd Operand V1a = (A1c – A2a) * 4.6 DS 500 V1.55 Side 87 of 124...
Before the selected measurement data are recorded, the data logger must be activated after the settings(See chapter 13.4 Logger settings (data logger)). See also chapter 13.3.2.3 Name the measurement 13.3.2.4 Recording measurement data DS 500 V1.55 Side 88 of 124...
Selection and Input of the operands and operations see chapter 13.7.4.2 chapter 13.7.4.3. m³ Result in is the sum of consumption sensor m³ see range “result”. 28856,8 m³ For this example it is 37233,4 m³ 37233,4 m³ 66090,2 m³ DS 500 V1.55 Side 89 of 124...
Page 90
0,072 KWh/m³ Due to more as 4 values used in virtual channel 991,36 € V1 the result range is splitted into 2 pages. To move between the pages please press page button DS 500 V1.55 Side 90 of 124...
13.8.1 Option „Analog Total“ activation After purchasing of the option „Analog Total“ the functionality have to be activated first. Main menu Settings about DS 500 Please push the button Buy for „Analog Total“ and you will requested to insert the key-code...
The text field „Unit-Consumption“ is only editable in case of measurement values(Units) with volume per time unit and thus also the consumption calculation. For labeling and setting of the description fields see also chapter 13.2.2 Label and set the description fields DS 500 V1.55 Side 92 of 124...
The smallest possible range is represented, depending on the time interval of the recording. Additional zooming and scrolling options in Chart Chart/Real time values: bigger period of time time later time earlier smaller period of time DS 500 V1.55 Side 93 of 124...
Page 94
The y-axis left 1. is already enabled, you can choose a Colour for it. Remark: Grid setting is already possible at this point, but later when a record is selected it is more reasonable! DS 500 V1.55 Side 94 of 124...
Page 95
Main menu Chart Setup Plots description field Now, you can choose the desired recording and colour intensity (in Colour). Main menu Chart Setup Now, the grid can be set with min, max, and step. DS 500 V1.55 Side 95 of 124...
Page 96
In the same way the remaining y-axes can be labelled! Four different grid settings with various Units and Colours. DS 500 V1.55 Side 96 of 124...
Page 97
Chart Main menu Chart DS 500 V1.55 Side 97 of 124...
At the push of a button the chart for the selected time range is displayed. Main menu Chart/Real time values Setup #1 - #12 In this menu item, up to twelve channels (depending on the version of the DS 500) can be activated at the same time and ...
Page 99
By activation of button # 1 - # 12, it is possible to change the setup of the corresponding graphic, see description above, or by a further press to switch off or back the graphic. DS 500 V1.55 Side 99 of 124...
1) or red (alarm Main menu channels A1 Each channel can be selected and the settings viewed and checked, but no changes can be made here. Remark: Please, make changes in the Settings! DS 500 V1.55 Side 100 of 124...
You can choose between 7 different layouts showing 1-10 measurements. See below. The values to be displayed could be selected in the Val.1 to Val.10 description fields. Different variants: DS 500 V1.55 Side 101 of 124...
Real time values, individual channels can be selected here, to detect which and how much the value has exceeded or below the alarm range. Remark: The alarm parameters can be set and/or modified here. DS 500 V1.55 Side 102 of 124...
50%, after that a "normal" function operation is possible. Important: If the Backlight dimming after button is not activated, then the Backlight stays permanently on, in the currently set brightness. DS 500 V1.55 Side 103 of 124...
In addition, it offers the most important network information, such as IP, host name and MAC. By the Runtime, you always know how long the DS 500 was in total in operation. DS 500 V1.55 Side 104 of 124...
About DS 500 13.14.5 About DS 500 Main menu Settings About DS 500 Brief description of the Hardware Software Version, as well as the Serial Number the DS 500. Under options, you can buy four additional, different functions, if you have not done this by ordering.
(optional)) and the consumption costs in chapter 12.15.2 Cost settings (optional). Via the optional function Webserver you can see the actual values of your DS 500 worldwide. 13.15.1 Consumption report (optional) Main menu Consumption report After opening the Consumption report weekly overview is displayed automatically.
Page 107
Remark: The channel selection in Consumption report is marked in green! DS 500 V1.55 Side 107 of 124...
Main menu Settings Sensor settings A1 Cost Settings use in Report + dual tariff button It can be entered here, for example, a day and night tariff with time. Label of the description fields, see chapter 13.3.2.2 Label and setting the description fields 14.4 Logger settings. DS 500 V1.55 Side 108 of 124...
Option „Webserver“ activation 13.16.1 After purchasing of the option „Webserver“ the functionality have to be activated first Main menu Settings about DS 500 for „Webserver“ Please push the button and you will requested to insert the key-code...
Webserver 13.16.3 Webserver start With an Internet-Explorer (IE, Firefox, Chrome) and the IP-address of your DS 500, you can access the webserver. http:// <IP-Adresse des DS500> Remark: The IP-address of the DS 500 yon can see in the chapters 13.14.4 System Status 13.5.3 Network...
After pressing the Button « Login » following screen is visible. Logion as Administrator with Username « admin » and the WebAdmin Password. Setup of the WebAdmin Passwords see chapter 13.16.1.2. After starting as Administrator all functions on the left side are activated. DS 500 V1.55 Side 111 of 124...
With this function, you are able to define the users with their corresponding accessrights. Username : min. 4 characters; max. 12 characters Password : min. 4 characters, max. 12 characters Group : see accessrights chapter 13.16.1.4 The inputs will be stored with « Submit » DS 500 V1.55 Side 112 of 124...
A verification (correctness of your settings) could be done by sending a test mail. Therefore, please press the button« Test EMail setting» Are all settings ok, a message , see left, will be displayed and a mail should be received by the defined recipients. DS 500 V1.55 Side 113 of 124...
In addition, a short comment could be added. With the button Submit the settings are stored. Alarm Email Content: DS 500 ALARM Event: 15.01.2015 13:49:20 IP: 192.168.172.39 Hostname: DE-0529 Alarm for Relais_1 Level_1 Comment: Test1 Channel (A2) "Ch-A2" Value "Temp."...
With show Minimum show Maximum the min and max values will be displayed too. With activation of show as curve the min and max values will be displayed as curve. DS 500 V1.55 Page 115 of 124...
Any selection change done through the webserver is transferred to the DS 500 too. With simultaneous access to the DS 500 by webserver and an operator direct at the DS500 the operator has priority. By simultaneous web access priority is according to accessrights.
Remark: In case the logger is stopped, only user with access rights of administrator or operator are able to start the logger. To stop the logger it is only possible at the DS 500 direct. DS 500 V1.55 Page 117 of 124...
Main menu Import / Export Export Logger data Change The selected date is always green, and the date numbers of the Sundays are red, like in the calendar. On days, where measurement data were recorded, the date numbers are optical highlighted. DS 500 V1.55 Page 118 of 124...
USB stick. Main menu Import / Export Export Screenshots Use the Change buttons to adjust a period between start and end. Stored bitmaps data in this period are exported. DS 500 V1.55 Page 119 of 124...
USB stick. 13.17.4 Export Report Main Import / Export Export Report By using Export Report, all existing reports can be exported in CSV-format to a USB stick. DS 500 V1.55 Page 120 of 124...
System Settings are loaded and a reboot is required. To definitively take over the new settings it is mandatory under Main menu Device settings Sensor settings to confirm each used channel A1-C4 again. DS 500 V1.55 Page 121 of 124...
Screenshots are stored in directories, defined per day and here numbered consecutively. Directory naming; DYYMMTT D=fix(for Date) YY = Year MM= Month TT= Day Path: DEV0001/Hostname/Bitmap For Hostname see Main menu SettingsSystem Status Example: first Screenshot 26. Februar 2014 \\DEV0001/DE-5001/Bitmap/D140226/B00000.bmp DS 500 V1.55 Page 122 of 124...
Chapter 12.14.3 for further information. Cleaning of the DS 500 must be undertaken using a slightly damp (not wet) cotton cloth or one-way wipe, and mild, commercially available cleaner/soap. For decontamination, spray the cleaner on an unused cotton cloth or one-way wipe, and wipe the component comprehensively.