Warnings are non-critical alarm conditions and do
not affect the operation of the generator system.
They serve to draw the operator's attention to an
undesirable condition. By default, warning alarms
are self-resetting when the fault condition is
removed.
Electrical trips stop the generator in a controlled
manner. On initiation of the electrical trip condition,
the controller de-energizes all the outputs, includ-
ing the lights, to remove the load from the genera-
tor. Once this has occurred, the controller starts the
cooling timer and allows the engine to cool off-load
before shutting down the engine.
Shutdown alarms stop the generator immediately.
On initiation of the shutdown condition, the control-
ler de-energizes all the outputs, including the lights,
to remove the load from the generator. Once this
has occurred, the controller shuts the generator set
down immediately to prevent further damage.
DTC faults are displayed by the controller.
Table 2-1. Possible DTC Faults
Fault
DTC Description
Check Engine
A fault not recognized by the controller
Fault
has been detected. Contact the engine
manufacturer for support.
Low Oil Pressure
Engine oil pressure has fallen below
its configured low oil pressure alarm
level.
Underspeed
Engine speed has fallen below its
configured underspeed alarm level.
Overspeed
Engine speed has risen above its
configured overspeed alarm level.
Low Fuel Level
Engine's fuel level has fallen below its
configured low fuel level alarm.
Battery Under/
Engine's DC supply has fallen below
Over Voltage
or risen above its configured alarm
level.
To view the active alarms, repeatedly press the ↑ and ↓
buttons until the LCD window displays the alarm.
Continue to press the ↑ and ↓ buttons to cycle through
the alarms.
To exit the alarm screen, press the ↑ and ↓ buttons
simultaneously to enter the navigation menu. Once
entered, cycle to the desired operator screen.
NOTE: The alarm condition must be corrected before a
reset will take place. If the alarm condition remains, it is
not possible to reset the unit. The exception to this is the
Low Oil Pressure alarm and similar 'active from safety on'
alarms, as the oil pressure is low with the engine at rest.
Owner's Manual for MLT6SMDS - MLT6SKDS Light Tower
To clear alarms that stop the generator, refer to
Resetting the Maintenance Alarms (If
NOTE: The LCD backlight is on if the unit has sufficient
voltage while the unit is turned on, unless the unit is
cranking. In this case, the backlight is turned off.
If the controller is left in STOP mode for a period of
inactivity, the controller enters POWER SAVE mode. To
'wake' the controller, press the Stop (O) button.
Maintenance Screen
See
Figure
2-26. The Maintenance screen (
the maintenance alarms configured into the controller.
The three alarms are for servicing the fuel filter, oil filter,
and air filter.
Figure 2-26. Maintenance Screen
Event Log Screen
See
Figure
2-27. The controller's event log (
a list of the last 15 recorded electrical trips or shutdown
events and the engine hours at which they occurred.
Once the log is full, any subsequent electrical trip or
shutdown alarm overwrites the oldest entry in the log.
The log always contains the most recent shutdown
alarms.
Figure 2-27. Event Log Screen
Proceed as follows to view the event log:
1. Press both ↑ and ↓ buttons simultaneously to
display the navigation menu.
2. Cycle to the event log section and press the Auto
button to enter.
General Information
Equipped).
) displays
003781
) displays
003782
23