Salda VEGA 350 E Installation And Maintenance Manual page 20

Air supply units
Hide thumbs Also See for VEGA 350 E:
Table of Contents

Advertisement

VEGA 350E/700E/1100E/1100W
Name
ModBus function R/W
Fire alarm
Coils
Filter
Coils
Fan overheat Coils
LowPower
Coils
T limit
Coils
Reset
Coils
Overheat
Coils
Tsupplay
Discrete
Twater
Discrete
Toutdoor
Discrete
Fire alarm
Discrete
Coldspell (ex-
Discrete
changer)
Fan overheat Discrete
Sensors
Discrete
Water
Discrete
LowPower
Discrete
Overheat
Discrete
Filter
Discrete
Supply
Discrete
Fan speed 1 Discrete
Fan speed 2 Discrete
Fan speed 3 Discrete
Water pump
Discrete
Overheat
Discrete
Alarm
Discrete
T supplay
Input
Speed
Input
T set
Input
Heater output Input
Speed
Holding_Register
T set
Holding_Register
time off
Holding_Register
SAF Low
Holding_Register
SAF Midd
Holding_Register
SAF High
Holding_Register
MB addres
Holding_Register
HeatPI:Kp
Holding_Register
HeatPI:Ki
Holding_Register
* - default value
EKR-KRE:150202 added Holding register „time off"
20
Data
Data
address
address
(dec)
(hex)
0x....)
Coils Read - 01h, Write – 05h, 0Fh
R
1
0x01
R
2
0x02
R
3
0x03
R
5
0x05
R
8
0x08
W
18
0x12
R
44
0x2C
(1x....) Discrete Read – 02h ( Present value, Unsigned Word )
R
2
0x02
R
4
0x04
R
5
0x05
R
9
0x09
R
10
0x0A
R
12
0x0C
R
13
0x0D
R
18
0x12
R
19
0x13
R
22
0x16
R
23
0x17
R
24
0x18
R
25
0x19
R
26
0x1A
R
27
0x1B
R
28
0x1C
R
30
0x1E
R
31
0x1F
(3x....) Input Read - 04h ( Present value, Signed Word )
R
0
0x00
R
1
0x01
R
2
0x02
R
4
0x04
(4x....) Holdings Read – 03h, Write – 06h, 10h ( Present value, Unsigned Word )
R/W
0
0x00
R/W
1
0x01
8
0x08
R/W
280
0x118
R/W
281
0x119
R/W
282
0x11A
R/W
301
0x12D
R/W
310
0x136
R/W
311
0x137
Report SlaveID – 11h ( Present value, Unsigned Char )
R
Description
( Present value, Unsigned Word )
Alarm from A1 input (A1)
Info from Filter input
Alarm from A4 input (A4)
Low voltage alarm (A7)
Supply air temperature sensor alarm
System restart
Alarm from A6 input (A6)
Supply air temperature sensor alarm
Return water temperature sensor alarm
Outdoor air temperature sensor alarm
Alarm from A1 input (A1)
Tsupplytemp.lessthan(Tset-10'C)alarm (A2)
Alarm from A4 input (A4)
Any sensor fail alarm
Critical return water temper. alarm (A5)
Low voltage alarm (A7)
Alarm from A6 input (A6)
Info from Filter input
Air supply valve output active
Fan 1 speed output active
Fan 2 speed output active
Fan 3 speed output active
Water pump output active
Tsupply temp. higher than 40 'C alarm (A6)
Any alarms alarm
Supply air temperature sensor value
Actual fan speed
Actual temperature setting
Heater output
Fan speed setting
Supply air temperature set
Time to stop ventilator
Analog output 0-10V = ( 1speed /10)V
Analog output 0-10V = ( 2speed /10)V
Analog output 0-10V = ( 3speed /10)V
Active ModBus addres on plate
Heating proportional coef.
Heating integral coef.
KE-AE/002/Ver.1.6(ACmotor)
(EC motor)
Value
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
Read =0
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
1-active, 0-passive
Real =(value*10)
0,1,2,3
0-30'C
0-100%
0,1,2,3 (0*)
0-30'C (18*)
30-120min.(50*)
20-SAF Midd (30*)
SAF Low – SAF High (60*)
SAF Midd -100 (100*)
0-247 (1*)
1-100 (30*) (Kp=X/10)
1-200 (6*) (Ki=X/100)
KE-EE/002/Ver.1.6
KE-AE:150318 KE-EE:150318
www.salda.lt