- Installing should only be performed by qualified and trained staff.
It is recommended to fix the air supply unit using supplementary brackets.
- Mount the unit on safe and firm base.
- Connecting the duct system refer to air flow labels.
Standard package includes (without optional accessories):
1.
Amortization pads with hanging bracket - 4 pcs. (VEGA 350E/700E), 6 pcs. (VEGA 1100 E/W);
2.
Screws M5x16 DIN 7985, spring washers 5 DIN 127, washers 5 DIN 440R - 8 sets (VEGA 350E/700E), 12 sets (VEGA 1100 E/W);
3.
Supply air sensor TJ - 1 pcs.
4.
Outdoor air sensor TL - 1 pcs. (VEGA 1100W)
Mounting positions
•
Operation start-up of the unit shall be performed only by trained and qualified personnel.
•
The assembly is ready for work after the voltage, remote controller, selected accessories are connected and the ventilation unit is connected to
the air duct system.
•
Before start-up, make sure that power supply circuit corresponds to the specification indicated in the label.
•
Before start-up, make sure that the unit is connected to the mains in accordance with the wiring diagram shown in this document and under the
connection cover of automatic control board.
•
Before start-up of the fan, make sure that the above instructions of safety and installation are applied.
•
Upon start-up of the unit, make sure that the motor rotates evenly, without vibration and outside noise.
•
Upon start-up of the unit, make sure that the air flow generated by the unit matches the direction of air indicated on the casing.
•
MAKE SURE that the air intake damper opens and closes correctly.
•
The current used by the unit shall be tested for compliance with the maximum allowed current indicated in this document.
•
Using the remote controller select the necessary fan rotation speed and supply air temperature.
www.salda.lt
o
180
VEGA 350E/700E/1100E/1100W
13