Description and function

6.1 Operating panel

The operating panel consists of a pushbutton, a red/green LED
and 4 yellow LEDs.
Pushbutton

6.1.1 Display mode

Either the operating status or the alarm status is shown in display
mode.
Operating status
If the pump is in operation, LED1 lights up green. The other four
LEDs show the current power consumption (P1) according to the
following table. When the pump is running, the active LEDs light
up permanently in display mode. This differentiates the display
mode from the settings mode. In settings mode, the active LEDs
flash. If the pump is switched off via the external PWM signal, the
LEDs do not light up.
green LED1 flashes. The
Display
Green LED
Standby (only externally triggered)
(flashes)
Green LED and
1 yellow LED
Green LED and
Low medium output
2 yellow LEDs
Green LED and
High medium output
3 yellow LEDs
Green LED and
High output
4 yellow LEDs

6.1.2 Settings view

The display switches from operating view to settings view at the
touch of a button. In the settings view, the LEDs show the current
active control curve and the current control type. No settings can
be made on this level, however. After 2 seconds, the display
switches back to operating view.
If LED 1 lights up green, the pump is either running or being con-
trolled internally. If LED 1 lights up red, the pump is being con-
trolled externally. LEDs 2 and 3 show the different control types
and LEDs 4 and 5 show the different
LED s
Power in %
Meaning
based on
P1,MAX
Low output
0-25
25-50
50-75
75-100
control curves.
452115.66.53 · FD 9712
Fig. 6.1:Operating panel with pushbutton and five LEDs
The following is shown on the operating panel:
Display mode (during operation)
- Operating status
- Alarm status
Settings mode (after pressing the button).
During operation, the display is in display mode. When the key is
pressed, the view (operating status or alarm status) is changed
or switched to settings mode.
Alarm status
If one or more faults occur, the LED1 lights up red. If an alarm is
active, the yellow LEDs show the cause of the fault according to
the following table. If multiple faults are active at the same time,
the LEDs indicate the fault with the highest priority. The priority is
shown in the following table.
If an alarm is no longer active, the display switches back to the
operating status.
Display
Red LED and
1 yellow LED
(LED 5)
Red LED and
0
1 yellow LED
(LED 4)
Red LED and
1 yellow LED
(LED 3)
Meaning
Operating mode Countermeasure
The pump
attempts to restart
Rotor blocked
every 1.33 s sec-
onds.
The pump was
Supply voltage too
switched off due to
low
an inadequate
supply voltage.
The pump was
Fault in the elec-
switched off due to
trics
a serious fault.
English
Wait or unblock
the pump.
Check the power
supply
Check the power
supply / replace
the pump.
EN-5