the set screw. Insert the bare end of the wire into the barrel portion of the Wire End Terminal &
crimp barrel portion using suitable crimping tool (Fig 3.11). Use #12 AWG terminals for AWG
#12 wiring for AC input and AWG #14 terminals for AWG #14 wiring for AC output. Insert
the terminated end of the wire fully into the terminal slot till it stops. Tighten the screw firmly.
Tightening torque for the screws – 7 to 12 Kgf*cm / 0.5 to 0.9 lbf*ft.
3.8 SIZING OF WIRING AND BREAKERS - AC INPUT SIDE
WARNING!
For EVO-1212F-HW / 1224F-HW, AC Breaker for the AC input circuits has NOT been
provided internally. This has to be provided externally by the installer / user based on
guidelines given below. Please note that guidelines given below on wire sizing and over-
current protection will be superseded by the applicable National / Local Electrical Codes.
MISE EN GARDE!
Pour EVO-1212F-HW / 1224F-HW, Breaker AC pour les circuits d'entrée AC ont pas été fournis en interne.
Cela doit être fournie en externe par l'installateur / l'utilisateur en fonction des directives données ci-dessous.
Se il vous plaît noter que les directives ci-dessous sur dimensionnement des câbles et protection contre les
surintensités seront remplacées par les nationaux / codes électriques locaux applicables.
3.8.1 Tables for Wire and Breaker Sizing - AC Input Side
Table 3.2 provides details of wire and breaker sizing for the AC input side.
AC input side wiring and breaker sizes depend upon the maximum continuous AC input cur-
rent under various operating conditions described in the succeeding paragraphs.
– When Grid input is available and the unit is operating in Charging / Pass Through Mode,
the AC Input Current will be determined as follows:
– AC Input Current will be equal to the sum of the AC Side Battery Charging Current
and the Pass Through current.
The AC Input current in Charging / Pass Through Mode will be restricted by the breaker
in the AC Input Branch Circuit that is feeding the unit. The AC Input Current drawn by
the unit can be programmed to the desired "GRID MAX CURRENT" to match the Amp
rating of breaker in the AC Input Branch Circuit. Optional Remote Control EVO-RC-PLUS
is required to change this limit [See EVO-RC-PLUS Manual: (i) Fig 4.3, Screen 2 (ii) Table 4.4
Screen 2 and (ii) Section 4.5.2.2]. The "GRID MAX CURRENT" set at 20A (Default Setting).
48 | SAMLEX AMERICA INC.
Installation
Stripped Wire End
Fig 3.11 Stripped Wire End Terminal on AC Wiring
Crimp Barrel Portion
Wire End Terminal