4. Diagnostic code

YHUJYH024BARXA-X
Flash times of
LED on
mainboard
1
Eeprom failure
2
IPM failure
Communication error between main
4
board and spdu module SPDU
Communicition error
5
High pressure protection
Module over-voltage protection(only for
Spdu)
6
Module lack-voltage protection(only for
Spdu)
Compressor discharging temperature
8
protection
9
Abnomal of DC motor
10
Abnomal of pipe sensor
12
Abnomal of outdoor ambient senso
Abnormal of compressor dischage
13
sensor
Communication error between indoor
15
and outdoor unit
16
Lack of refrigerant
17
4-way valve reverse failure
18
Compressor jam (ony for spdu )
19
Module EEV select circuit error
25
Compressor U-phase over-current
25
Compressor V-phase over-current
25
Compressor W-phase over-current
45
Low pressure protection
Trouble description
Analyze and diagnose
Outdoor main board eeprom fail
IPM failure
Communication fail over 4 min
System high pressure over 4.15 Mpa
Send from Spdu module
Compressor discharging temperature over 110
centigrade
jam of DC motor or motor failure
Piping sensor short-circuit or open-circuit
Outdoor ambient sensor
short-circuit or open-circuit
Compressor discharging sensor short-circuit or
open-circuit
Communication fail over 4 min
check if there is leakage in the unit
Alarm and stop if detect Td-Tci<=15 last for 1min
after compressor has started for 10min in heating
mode, confirm the failure if it appears 3 times in
one hour.
Inner compressor is abnormal jamed
Module EEV select wrong circuit
The current of compressor U-phase is too high
The current of compressor V-phase is too high
The current of compressor W-phase is too high
System over pressure under 0.05Mpa
241