4. After all bases are installed, check loop continuity. Refer to System manual
for the loop continuity checkout procedure. For ADB-11 loop continuity
check, use the jumper furnished in every base (between terminals 1a and
1b) to complete the loop (Refer to Figure 3). An open circuit condition exists
until the jumper or detector is installed in the base.
5. If loop continuity is acceptable, remove the jumper at each base and
proceed with detector head installation.
ALARM LED
LOCATION WITH
DETECTOR
INSTALLED
IN BASE
COMPATIBLE CONTROL EQUIPMENT FOR ADB-11
Compatibility Identifier
CP-2ER
CP-2HR
CP-35 (System 3)
CZM-4 (MXL, MXL-IQ)
PXL
SXL-EX
SZE-4X (SXL-EX)
SZE-8AX (SXL-EX)
ZU-35 (System 3)
The detector model number is the compatibility identifier.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-096162-8
Positioning the Alarm LED
Equipment
Figure 3
Installation/Wiring
Instructions
P/N 575-293737-7
P/N 575-287232-9
P/N 315-084902-22
P/N 315-090726-9
P/N 315-094131-5
P/N 315-095997-6
P/N 315-096018-5
P/N 315-096022-5
P/N 315-083222-15
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada
FACTORY
INSTALLED
JUMPER
BASE
MOUNTING
HOLES