Table 1- 1
S7-200 SMART CPUs
Compact serial, non-
expandable
Standard, expandable
Relay output
Transistor output (DC)
I/O points (built-in)
Table 1- 2
Compact serial, non-expandable CPUs
Features
Dimensions: W x H x D (mm) 90 x 100 x 81
User memory
Program
User data
Retentive
On-board digi-
Inputs
tal I/O
Outputs
Expansion modules
Signal board
High-speed
Single
counters (4
phase
total)
A/B phase
PID loops
Real-time clock with 7-day
back-up
You can configure areas of V memory, M memory, C memory (current values), and portions of T memory (current val-
1
ues on retentive timers) to be retentive, up to the specified maximum amount.
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
SR20 ST20
CR20s SR30 ST30
X
X
X
X
X
X
X
X
20
20
20
30
CPU CR20s
12 Kbytes
8 Kbytes
2 Kbytes max.
1
12 DI
8 DQ Relay
None
None
4 at 100 kHz
2 at 50 kHz
8
No
CR30s SR40 ST40
X
X
X
X
X
X
30
30
40
CPU CR30s
CPU CR40s
110 x 100 x 81
125 x 100 x 81
12 Kbytes
12 Kbytes
8 Kbytes
8 Kbytes
2 Kbytes max.
2 Kbytes max.
1
18 DI
12 DQ Relay
None
None
None
None
4 at 100 kHz
4 at 100 kHz
2 at 50 kHz
2 at 50 kHz
8
8
No
No
Product overview
1.1 S7-200 SMART CPU
CR40s SR60 ST60
X
X
X
X
X
X
X
X
40
40
60
60
CPU CR60s
175 x 100 x 81
12 Kbytes
8 Kbytes
2 Kbytes max.
1
36 DI
24 DI
24 DQ Relay
16 DQ Relay
None
None
4 at 100 kHz
2 at 50 kHz
8
No
CR60s
X
X
60
1
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-200 smart

Table of Contents