Configuring The Retentive Ranges - Siemens SIMATIC S7 System Manual

Hide thumbs Also See for SIMATIC S7:
Table of Contents

Advertisement

You can set digital output points to a specific value when the CPU is in STOP mode, or
preserve the output states that existed before the transition to STOP mode.
You have two ways to set the digital output behavior in STOP mode:
● Freeze Outputs in last state: Click this checkbox to have all digital outputs frozen in their
last states at the time of a RUN-to-STOP transition.
● Substitute value: If the Freeze Outputs in last state checkbox is not checked, this table
allows you to select the desired state of each output whenever the CPU is in STOP
mode. Click the checkbox for each output you want set to ON (1). The default substitute
value for digital outputs is OFF (0).
6.1.5

Configuring the retentive ranges

Click the Retentive Ranges node of the system block (Page 133) dialog to configure ranges
of memory that will be retained following a power cycle.
Configure the areas of memory you want to retain through power cycles. Enter new values
for V, M, T, or C memory.
You can define ranges of addresses in the following memory areas to be retentive: V, M, T,
and C. For timers, only the retentive timers (TONR) can be retained, and, for both timers and
counters, only the current value can be retained (timer and counter bits are cleared on each
power-up).
S7-200 SMART
System Manual, V2.3, 07/2017, A5E03822230-AF
6.1 Configuring the operation of the PLC system
PLC device configuration
141