Connections and Applications

W7220 Economizer Module Wiring —
Use Fig. 45 and Tables 6 and 7 to locate the wiring
terminals for the Economizer module.
Left Terminal
Block Label
Table 6 – Economizer Module - -
Left Hand Terminal Blocks
Label
Type
Top Left Terminal Block
MAT
20k NTC
Supply Air Temperature Sensor
MAT
and
(polarity insensitive connection)
COM
OAT
20k NTC
Outdoor Air Temperature Sensor
OAT
and
(polarity insensitive connection)
COM
S--- BUS
S--- Bus
Enthalpy Control Sensor
S--- BUS
(Sylk Bus)
(polarity insensitive connection)
Bottom Left Terminal Block
IAQ 2--- 10
2--- 10 Vdc
Air Quality Sensor Input
(e.g. CO
IAQ COM
COM
Air Quality Sensor Common
IAQ 24V
24 Vac
Air Quality Sensor 24 Vac Source
ACT 2--- 10
2--- 10 Vdc
Damper Actuator Output (2--- 10 Vdc)
ACT COM
COM
Damper Actuator Output Common
ACT 24V
24 Vac
Damper Actuator 24 Vac Source
W7220 Controller
NOTE: The bottom 4 Pin actuator header is not used
Fig. 45 - - W7220 Economizer Module Terminal Connection Labels
Description
sensor)
2
Right Terminal
Block Label
Table 7 – Economizer Module - -
Right Hand Terminal Blocks
Label
Type
Top Right Terminal Block
N/A
n/a
AUX2--- I
24 Vac IN
OCC
24 Vac IN
E--- GND
E--- GND
EXH1
24 Vac OUT Exhaust Fan 1 Output
AUX1--- O
24 Vac OUT Programmable:
Bottom Right Terminal Block
Y2--- I
24 Vac IN
Y2--- O
24 Vac OUT Y2 out --- Cooling Stage 2 Output to
Y1--- I
24 Vac IN
Y1--- O
24 Vac OUT Y1 out --- Cooling Stage 2 Output to
C
COM
R
24 Vac
Refer to Fig. 46 and 47 for sensor and controls connections.
34
Description
The first terminal is not used
Input from Thermostat W1 indicating
base unit is in Heat mode, damper
controls to High Fan Speed
setpoints
Occupied / Unoccupied Input
Earth Ground --- System Required
Exhaust fan 2 output
or
ERV
or
System Alarm output
Y2 in --- Cooling Stage 2 Input from
space thermostat
stage 2 mechanical cooling
Y1 in --- Cooling Stage 2 Input from
space thermostat
stage 2 mechanical cooling
24 Vac Common
24 Vac Power (Hot)
C14156