SE-330HV MANUAL
NEUTRAL-GROUNDING-RESISTOR MONITOR
REVISION 5-M-101817
Copyright Ó 2017 Littelfuse Startco.
All rights reserved.
Document Number: PM-1215-EN
Printed in Canada.

Advertisement

Table of Contents
loading

Summary of Contents for Littelfuse Startco SE-330HV

  • Page 1 Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/SE-330HV SE-330HV MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR REVISION 5-M-101817 Copyright Ó 2017 Littelfuse Startco. All rights reserved. Document Number: PM-1215-EN Printed in Canada.
  • Page 2: Se-330Hv Neutral-Grounding-Resistor Monitor Rev. 5-M

    Page i SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 This page intentionally left blank.
  • Page 3: Table Of Contents

    Analog-Output Connections ........5 1.2 SE-330HV NGR Monitoring ......... 1 SE-330HV Connection Diagram ......7 Operation .............. 3 SE-330HV Outline and Panel-Mounting Details ..8 2.1 Settings ..............3 SE-330HV Outline and Surface-Mounting Details .. 9 2.1.1 GF Trip Time ..........3 SE-IP65CVR-G Weatherproof Cover Outline ..
  • Page 4 Page iii SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 This page intentionally left blank.
  • Page 5: General

    NGR current will flow if the NGR is healthy. systems, the magnitude of charging current can be The SE-330HV will trip on ground fault if fault current conservatively estimated as ½ A per 1,000 kVA on low- exceeds the GF TRIP LEVEL setting for an interval voltage systems and 1 A per 1,000 kVA on medium- equal to the GF TRIP TIME setting.
  • Page 6: Typical Values For Tripping Systems

    The SE-330HV provides the following additional features: • When the trip level is set to MEM, the ground-fault trip setting is defined by an internal non-volatile memory variable. Range is 2 to 100% in 1% increments of the CT-primary rating.
  • Page 7: Operation

    Contacts open if there is a trip, a Set-Point Assistant is included with the SE-MON330 loss of supply voltage, or a processor failure. In the fail-safe software. mode, SE-330HV trips are not reset when supply voltage is 2.1.3 V cycled. EVEL...
  • Page 8: Frequency (S6)

    When supply voltage is applied with switch S2 set to NON-FAIL-SAFE, SE-330HV trips : If the SE-330HV is not calibrated and is supplied are reset. When a local, remote, or network reset is issued, from the load side of the breaker (non-fail-safe mode), both trip LED's will flash if they are off.
  • Page 9: Relay K1 Led

    Non-critical diagnostic codes include SD Card status and USB Error status. All other diagnostic codes are considered critical. Starting with SE-330HV firmware version 2.60 and SE- MON330 software version 3.8, the SE-330HV can be configured to show only critical diagnostic codes. In this configuration, non-critical diagnostic codes will not be indicated with the DIAGNOSTIC LED.
  • Page 10: Installation

    Outline and panel-cutout dimensions for the SE-330HV NGR. See the simplified diagram in Fig. 14. are shown in Fig. 4. To panel mount the SE-330HV, : Voltage at terminal N rises to line-to-neutral voltage insert it through the panel cutout and secure it with the when a ground fault occurs.
  • Page 11: Se-330Hv Connection Diagram

    Page 7 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 3. SE-330HV Connection Diagram.
  • Page 12: Se-330Hv Outline And Panel-Mounting Details

    Page 8 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 4. SE-330HV Outline and Panel-Mounting Details.
  • Page 13: Se-330Hv Outline And Surface-Mounting Details

    Page 9 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 5. SE-330HV Outline and Surface-Mounting Details.
  • Page 14: Se-Ip65Cvr-G Weatherproof Cover Outline

    Page 10 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 6. SE-IP65CVR-G Weatherproof Cover Outline.
  • Page 15 Page 11 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 7. SE-IP65CVR-G Weatherproof Cover Installation.
  • Page 16: Se-Ip65Cvr-G Weatherproof Cover Installation . 11 8 Er-15Kv Sensing Resistor

    Page 12 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 8. ER-15KV Sensing Resistor.
  • Page 17: Er-25Kv Sensing Resistor

    Page 13 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 9. ER-25KV Sensing Resistor.
  • Page 18: Er-35Kv Sensing Resistor

    Page 14 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 10. ER-35KV Sensing Resistor.
  • Page 19: Er-72Kv Sensing Resistor Outline

    Page 15 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 11. ER-72KV Sensing Resistor Outline.
  • Page 20: Er-72Kv Sensing Resistor Mounting Details

    Page 16 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 12. ER-72KV Sensing Resistor Mounting Details.
  • Page 21: Er-1000Hv Sensing Resistor

    Page 17 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 13. ER-1000HV Sensing Resistor.
  • Page 22: Ground-Fault Ct

    The accuracy of a typical current sensor decreases below 5% of its current rating. CT-primary current- injection testing is recommended to verify trip levels below CT-primary rating. Section 9.4. Littelfuse Startco current sensors are designed for use at low levels and respond linearly to 2% current rating.
  • Page 23: Efct-1 Ground-Fault Current Sensor

    Page 19 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 15. EFCT-1 Ground-Fault Current Sensor.
  • Page 24: Se-Cs30-70 Ground-Fault Current Sensor

    Page 20 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 16. SE-CS30-70 Ground-Fault Current Sensor.
  • Page 25: Efct-26 And Se-Cs30-26 Ground-Fault Current Sensors

    Page 21 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 17. EFCT-26 and SE-CS30-26 Ground-Fault Current Sensors.
  • Page 26: Rk-332 Remote Indication And Reset

    Page 22 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 FIGURE 18. RK-332 Remote Indication and Reset. FIGURE 19. PGA-0520 Analog Percent Current Meter.
  • Page 27: Isolated Ground Connection

    If the G terminals on the sensing resistor and the SE-330HV are connected to an isolated ground, the SE-330HV will be exposed to the GPR. If the GPR is greater than the terminal-block rating, the SE-330HV must be isolated from station ground and precautions must be taken with the power supply and the trip contacts.
  • Page 28: Data Interfaces

    : The maximum microSD™ card storage capacity is data logging of measured values and for firmware upgrades. 32 GB for SE-330HV hardware revision 16 and higher. The maximum microSD™ card storage capacity is 4 GB for : SD card performance may vary by manufacturer, SE-330HV hardware revision 15 and lower.
  • Page 29: Troubleshooting

    1 L - 8 S - 1 L An error was detected in the Non-Volatile Memory. Press RESET DIAGNOSTIC LED flash code to clear the trip. If the problem persists, consult Littelfuse Startco. Critical diagnostic code. GF LED : ON, RF LED...
  • Page 30 : No Change, RF LED : No Change, K1:No Change DIAGNOSTIC LED = Solid Red SE-330HV processor failed to start. Cycle supply. If problem persists, consult Littelfuse Startco. K1: De-energized. Pressing RESET does not clear trips. Trip condition is still present. Locate and correct.
  • Page 31: Technical Specifications

    Page 27 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 6. T ECHNICAL PECIFICATIONS Trip-Time Accuracy ....10% of Setting, 20 ms minimum 6.1 SE-330HV 3 dB Frequency Response: Supply: S6 = 50 Hz ......25 to 85 Hz Option 0 ........ 30 VA, 120 to 240 Vac (+10, - S6 = 60 Hz ......
  • Page 32 Page 28 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 Dimensions: Subject to maximums of 8 A at 250 Vac, 8 A resistive Height ........213 mm (8.4”) at 30 Vdc, and 0.4 A resistive at 150 Vdc. Width ........99 mm (3.9”) Depth ........
  • Page 33: Sensing Resistors

    Page 29 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 Accuracy included for EFCT-x and SE-CS30-x current sensors only. Magnetic Field microSD™ and microSDHC™ are trademarks of Immunity ......IEC 61000-4-8 SD-3C, LLC. 50 Hz and 60 Hz Remote-reset wiring is limited to 10 m (32’).
  • Page 34: Current Sensors

    Page 30 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 ER-72KV: EFCT-26: Current Ratio ....... 5:0.05 A Maximum Voltage ..... 44,000 Vac Insulation ......600-V Class Maximum Current ....220 mA Window Diameter ....26 mm (1.0”) Resistance ......200 kW Shipping Weight ....0.45 kg (1.0 lb) Thermal: Certifications .......
  • Page 35: Ordering Information

    Set-Point Assistant ....Setting Guide 72 kVac ER-1000HV ......For system voltages up to NOTES: 1 kVac Profibus models only available on legacy SE-330HV. Current Sensors: Includes Modbus TCP and Ethernet/IP protocols. EFCT-1 ........Current Sensor, Includes IEC 61850 and Modbus TCP protocols.
  • Page 36: Warranty

    Applying the test voltage to the R and G terminals will OTE: The SE-330HV Neutral-Grounding-Resistor Monitor is damage the SE-330HV and the ER sensing resistor. The V warranted to be free from defects in material and TRIP LEVEL is the trip voltage at terminal N, not terminal R.
  • Page 37: Ground-Fault Performance Test

    Ensure the cables pass through the ground- fault-current-sensor window. This check can be done visually with knowledge of the circuit. FIGURE 21. Ground-Fault-Test Circuit. connection of the current-sensor secondary to the SE-330HV is not polarity sensitive. TABLE 3. G ROUND AULT ECORD...
  • Page 38: Appendix Ase-330Hv Revision History

    Page 34 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 APPENDIX A SE-330HV REVISION HISTORY HARDWARE REVISION MANUAL MANUAL (REVISION NUMBER FIRMWARE REVISION RELEASE DATE REVISION ON PRODUCT LABEL) October 18, 2017 5-M-101817 2.60 December 7, 2016 5-L-120716 2.55 2.54 September 21, 2016 5-K-092116 2.53...
  • Page 39 Page 35 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 ECTION SD card diagnostic troubleshooting updated. 5-H-062215 EVISION ECTION Section 2.1.6 added. ECTION SD Card approximate yearly data logging usage updated. SE-MON330 software version updated. ECTION Resistor-fault trip level ranges added. 5-G-052015 EVISION ECTION SD Card storage capacity updated.
  • Page 40 Reduced ESD sensitivity of USB and SD card connectors. ARDWARE EVISION Updated SE-330HV platform to include USB and microSD™ interfaces, programmable trip level (MEM) feature, and ability to add future options. Real-time clock added. Added dual cable and fiber Ethernet ports.
  • Page 41 Page 37 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 IEC 61850 GOOSE network input support now always enabled. Improved compatibility for Modbus TCP. Web page disabled for Ethernet options. This will be enabled in a future firmware release. IP setting changes for Ethernet options now require power cycle to take effect.
  • Page 42 Page 38 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 This page intentionally left blank.
  • Page 43 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: Littelfuse 5SHT-101-E 7SHT-401-E ER-1000HV 5SHT-500-E 7SHT-601-E 5SHT-151-E 7SHT-301-E 8SHT-151-E 8SHT- 601-E 5SHT-102-E...