NGR current will flow if the NGR is healthy. systems, the magnitude of charging current can be The SE-330HV will trip on ground fault if fault current conservatively estimated as ½ A per 1,000 kVA on low- exceeds the GF TRIP LEVEL setting for an interval voltage systems and 1 A per 1,000 kVA on medium- equal to the GF TRIP TIME setting.
The SE-330HV provides the following additional features: • When the trip level is set to MEM, the ground-fault trip setting is defined by an internal non-volatile memory variable. Range is 2 to 100% in 1% increments of the CT-primary rating.
Contacts open if there is a trip, a Set-Point Assistant is included with the SE-MON330 loss of supply voltage, or a processor failure. In the fail-safe software. mode, SE-330HV trips are not reset when supply voltage is 2.1.3 V cycled. EVEL...
When supply voltage is applied with switch S2 set to NON-FAIL-SAFE, SE-330HV trips : If the SE-330HV is not calibrated and is supplied are reset. When a local, remote, or network reset is issued, from the load side of the breaker (non-fail-safe mode), both trip LED's will flash if they are off.
Non-critical diagnostic codes include SD Card status and USB Error status. All other diagnostic codes are considered critical. Starting with SE-330HV firmware version 2.60 and SE- MON330 software version 3.8, the SE-330HV can be configured to show only critical diagnostic codes. In this configuration, non-critical diagnostic codes will not be indicated with the DIAGNOSTIC LED.
Outline and panel-cutout dimensions for the SE-330HV NGR. See the simplified diagram in Fig. 14. are shown in Fig. 4. To panel mount the SE-330HV, : Voltage at terminal N rises to line-to-neutral voltage insert it through the panel cutout and secure it with the when a ground fault occurs.
The accuracy of a typical current sensor decreases below 5% of its current rating. CT-primary current- injection testing is recommended to verify trip levels below CT-primary rating. Section 9.4. Littelfuse Startco current sensors are designed for use at low levels and respond linearly to 2% current rating.
If the G terminals on the sensing resistor and the SE-330HV are connected to an isolated ground, the SE-330HV will be exposed to the GPR. If the GPR is greater than the terminal-block rating, the SE-330HV must be isolated from station ground and precautions must be taken with the power supply and the trip contacts.
: The maximum microSD™ card storage capacity is data logging of measured values and for firmware upgrades. 32 GB for SE-330HV hardware revision 16 and higher. The maximum microSD™ card storage capacity is 4 GB for : SD card performance may vary by manufacturer, SE-330HV hardware revision 15 and lower.
1 L - 8 S - 1 L An error was detected in the Non-Volatile Memory. Press RESET DIAGNOSTIC LED flash code to clear the trip. If the problem persists, consult Littelfuse Startco. Critical diagnostic code. GF LED : ON, RF LED...
Page 30
: No Change, RF LED : No Change, K1:No Change DIAGNOSTIC LED = Solid Red SE-330HV processor failed to start. Cycle supply. If problem persists, consult Littelfuse Startco. K1: De-energized. Pressing RESET does not clear trips. Trip condition is still present. Locate and correct.
Page 27 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 6. T ECHNICAL PECIFICATIONS Trip-Time Accuracy ....10% of Setting, 20 ms minimum 6.1 SE-330HV 3 dB Frequency Response: Supply: S6 = 50 Hz ......25 to 85 Hz Option 0 ........ 30 VA, 120 to 240 Vac (+10, - S6 = 60 Hz ......
Page 32
Page 28 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 Dimensions: Subject to maximums of 8 A at 250 Vac, 8 A resistive Height ........213 mm (8.4”) at 30 Vdc, and 0.4 A resistive at 150 Vdc. Width ........99 mm (3.9”) Depth ........
Page 29 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 Accuracy included for EFCT-x and SE-CS30-x current sensors only. Magnetic Field microSD™ and microSDHC™ are trademarks of Immunity ......IEC 61000-4-8 SD-3C, LLC. 50 Hz and 60 Hz Remote-reset wiring is limited to 10 m (32’).
Page 30 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 ER-72KV: EFCT-26: Current Ratio ....... 5:0.05 A Maximum Voltage ..... 44,000 Vac Insulation ......600-V Class Maximum Current ....220 mA Window Diameter ....26 mm (1.0”) Resistance ......200 kW Shipping Weight ....0.45 kg (1.0 lb) Thermal: Certifications .......
Set-Point Assistant ....Setting Guide 72 kVac ER-1000HV ......For system voltages up to NOTES: 1 kVac Profibus models only available on legacy SE-330HV. Current Sensors: Includes Modbus TCP and Ethernet/IP protocols. EFCT-1 ........Current Sensor, Includes IEC 61850 and Modbus TCP protocols.
Applying the test voltage to the R and G terminals will OTE: The SE-330HV Neutral-Grounding-Resistor Monitor is damage the SE-330HV and the ER sensing resistor. The V warranted to be free from defects in material and TRIP LEVEL is the trip voltage at terminal N, not terminal R.
Ensure the cables pass through the ground- fault-current-sensor window. This check can be done visually with knowledge of the circuit. FIGURE 21. Ground-Fault-Test Circuit. connection of the current-sensor secondary to the SE-330HV is not polarity sensitive. TABLE 3. G ROUND AULT ECORD...
Page 40
Reduced ESD sensitivity of USB and SD card connectors. ARDWARE EVISION Updated SE-330HV platform to include USB and microSD™ interfaces, programmable trip level (MEM) feature, and ability to add future options. Real-time clock added. Added dual cable and fiber Ethernet ports.
Page 41
Page 37 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 IEC 61850 GOOSE network input support now always enabled. Improved compatibility for Modbus TCP. Web page disabled for Ethernet options. This will be enabled in a future firmware release. IP setting changes for Ethernet options now require power cycle to take effect.
Page 42
Page 38 SE-330HV Neutral-Grounding-Resistor Monitor Rev. 5-M-101817 This page intentionally left blank.