Page 1
SE-325 MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR MAY 6, 2008 REVISION 10 C T 1 C T 2 A G R O U N D R E S E T R E S I S TO R F A U L T F A U L T 2 0 0 1 .
IGURES IGURE Table of Contents ..............i Typical Application ............3 List of Figures................i SE-325 Outline and Mounting Details......4 List of Tables ................i Current Transformers............ 5 ER-600VC Sensing Resistor ........6 General ................. 1 ER-5KV Sensing Resistor ..........7 1.1 Modern Resistance-Grounded Systems .......
1.2 SE-325 NGR M ONITORING exists in low-resistance- or solidly grounded systems and The SE-325 is a neutral-grounding-resistor monitor for a ground-fault can result in substantial point-of-fault resistance-grounded systems up to 25 kVac. It measures damage.
Red LED's indicate ground-fault and resistor- occurs. The shunt-trip mode is not fail-safe because shunt- fault trips. When a trip occurs, the SE-325 remains latched trip devices do not operate if supply voltage fails. until the reset switch is pressed or supply voltage is cycled.
NSTALLATION 3.1 SE-325 Face-plate LED's are driven in series with remote- SE-325 outline and mounting details are shown in indication LED's. When remote-indication LED’s are not Fig. 2. Typical connections are shown in Fig. 1. Connect used, terminals GI, +, and RI must be connected for the supply voltage to L1 and L2.
4 . 8 ( 0 . 1 9 ) D I A TERMINAL-BLOCK SCREWS: 6-32 x 0.25. MOUNTING SCREWS: M4 OR 8-32. SHOWN WITH TERMINAL-BLOCK COVER REMOVED. MINIMUM CLEARANCE FOR FUSE REMOVAL. FIGURE 2. SE-325 Outline and Mounting Details. Pub. SE-325-M, May 6, 2008.
Outline and mounting details for CT200 and CT200L Connect the secondary of the ground-fault CT to SE-325 current transformers are shown in Fig. 3. Ground-fault-CT terminals CT1 and CT2. The CT connection to the SE-325 connections and the typical ground-fault-CT location are is not polarity sensitive.
THIS CONNECTION MAY BE REMOVED FOR DIELECTRIC STRENGTH TESTING. ENSURE THAT THE JUMPER IS INSTALLED AFTER TESTING. ON REVISION 1 UNITS, SCREW IS NOT PRESENT AND ENCLOSURE IS ELECTRICALLY CONNECTED TO TERMINAL G. FIGURE 4. ER-600VC Sensing Resistor. Pub. SE-325-M, May 6, 2008.
STRENGTH TESTING. ENSURE THAT THE JUMPER IS INSTALLED (18.00) AFTER TESTING. ON REV 0 & 1 UNITS SCREW IS NOT MOUNTING DETAIL PRESENT AND BASE IS ELECTRICALLY CONNECTED TO TERMINAL G. FIGURE 5. ER-5KV Sensing Resistor. Pub. SE-325-M, May 6, 2008.
Option H required, use an RK-13 Relay Interface Module. Trip Time......0.1 to 2.0 s, RK-13 mounts on the SE-325 lower terminal block and it is 0.1 to 5.0 s with compatible with the RK-302, RK-325 and RK-325I. See Option T Figs.
N Non-latching Operation D 120-Vac/dc Supply SE-325 that is determined by Startco to be defective if it T Extended G-F Trip Time is returned to the Startco factory, freight prepaid, within the warranty period.
0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Set the test current to 0.6, 2.3, or 4.6 A for SE-325 units set at 0.5, 2.0, or 4.0 A FIGURE 12. Ground-Fault-Test Circuits respectively. Fig. 12b shows a test circuit using a Startco SE-100T Ground-Fault-Relay Tester.
Test Equipment: 0 to 120 Vac voltage source and multimeter. Applying the test voltage to the R and G terminals will OTE: damage the SE-325 and the ER sensing resistor. The RES TRIP LEVEL is the trip voltage at terminal N, not terminal R. Procedure: •...