Panasonic KW9M Eco-Power Meter Installation Instructions page 2

Advanced type
Hide thumbs Also See for KW9M Eco-Power Meter:

Advertisement

10. Setting Flow
Measuring value display
Enter password
【Power
【Demand】
measurement】
Phase/Wire
Power demand type
Power demand
CT type
interval *1
Primary side
Power demand
current of CT
interval 2 *1
Calcuration method
Rated voltage
for 30-min demand *2
VT ratio
Power input type *2
Over voltage
Pulse type *2
Pulse rate (elecric power
Under voltage
convertion)
*2
Over current
Pulse constant value *2
Under current
Current demand interval
Rate(P)
Total, T1-4
Rate(-P)
Total, T1-4
11. How to Set the Parameters related to
Power Measurement
Set before measuring.
Select setting item with
and press
and the value will be blinking.
Set with
and
When you select [YES] with the confirmation window
and press
, the setting values are decided.
◆Phase / Wire
Select measured phase and wire system.
Single-phase 2-wire (initial)
Single-phase 3-wire
Three-phase 4-wire
Three-phase 3-wire
When the system is not matched with the measure system,
it doesn't measure correctly
◆CT type
Select using CT type (secondary side current).
To use CT with secondary side current 5A: [5] (initial)
To use CT with secondary side current 1A: [1]
◆Primary side current of CT
Set the primary side current of using CT.
Enter the primary side current of CT that is set at CT type
setting.
Increase
Decrease
[Set range] 1 to 65535 (initial: 5)
Primary side current of using CT is 400A: [400]
Setting Mode
【Communication】
【Pulse】
【Optional function】
Pulse input 1
Auto-off
Protocol
Clock
Luminance
Device number
synchronize *3
Transmission
Pulse input 2
Alarm blinking
speed
Transmission
Update cycle
Prescale 1 *4
format
Stop bit
Prescale 2
Auto-display
Display cycle
Pulse output 1
Response time
Temperature
Pulse output 2
correction
Reset all
integral value
Press
during each item is displayed to change the setting value.
Press
to display the confirmation window.
Select [YES] and press
to decide the setting value.
However no value is changed, the confirmation window is skipped and
it displays the measuring value display.
Confirmation Mode
Setting confirmation
NO
◆Rated voltage
Set the rated voltage of measured voltage.
Increase
Decrease
[Set range] 100 to 500 (initial:100)
◆VT ratio
Select the voltage input method, input voltage directly
or uses a voltage transformer (VT: secondary side rating
110V) and set VT ratio.
Increase
Decrease
[Set range] 1.00 to 600.00 (initial:1.00)
Input directly without VT: [1.00]
Use VT
: [1.01 to 600.00]
◆Over Voltage/ Over Voltage 2
Set the ratio for the rated voltage to judge to be over voltage
at [over volt] window.
Increase
Decrease
[Set range] 100.0 to 120.0 %
(initial:105.0)
Press
, and [over volt 2] is displayed.
At this window, set a ratio of voltage to clear overt voltage.
Increase
Decrease
[Set range] 100.0 to 120.0 %
(initial:105.0)
◆Under Voltage / Under Voltage 2
Set the ratio for the rated voltage to judge to be under
voltage at [under volt] window.
Increase
Decrease
[Set range] 5.0 to 100.0 %
(initial: 95.0)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
【Time program】
【Calendar timer】
Program 1
Reset integral
Program 2
value 1
*6
*7
Reset integral
Program 3
*7
value 2
*6
Reset integral
Program 4
*7
value 3
*6
Reset count
Program 5
value 1
*6
*7
Reset count
Program 6
*7
*5
value 2
*6
Reset logging
*1 It skips when [Peak] or [30min] is set at
data
*6
power demand type.
*2 It skips when except [30min] is set at
power demand type.
Version
*3 It skips when [30] is set at pulse input 1.
*4 It skips when [Clock] is selected at
pulse input 1.
*5 It skips when [0] is set at auto-display
setting.
*6 It skips when [YES] is selected at reset
all integral value.
*7 It skips when [OFF] is selected at
the previous program.
Setting confirmation
Measuring value display
YES
Press
, and [under volt 2] is displayed.
At this window, set a ratio of voltage to clear under voltage.
◆Over Current /Over Current 2
Set the ratio for the rated voltage to judge to be over
current at [over curr] window.
Press
, and [under curr 2] is displayed.
At this window, set a ratio of voltage to clear under voltage.
◆Under Current /Under Current 2
Set the ratio for the rated current to judge to be under current
at [under curr] window.
[Set range] 0.0 to 100.0 %
Press
, and [under curr 2] is displayed.
At this window, set a ratio of current to clear under current.
[Set range] 0.0 to 100.0 %
◆How to Enter Password
It is necessary to enter password to shift to setting
mode. Enter [0000] and shift to password setting
mode when you set password at the first time.
*When setting password, be careful for handling and note it.
Measuring value display
Password
entry window
【Password】
Calendar
Password
timer
setting
Setting
mode of
power
measurement
Program 7
*7
Program 8
*7
Program 9
◆How to Initialize Password
*7
When you forget the password, initialize it in the
following procedures. (Initial: [0000])
It is impossible to decode the set password.
Program 10
Measuring value display
*7
Password
entry window
Initialize[YES]
◆Conversion rate (P)
Set the conversion rate per integral active power 1 kWh.
You can set 5 kinds of rate for each time zone, all-time,
time zone 1, time zone 2, time zone 3 and time zone 4.
Rate for all-time is used when time program is not set.
Increase
When you set one or more time programs, the rates for
time zone 1, 2, 3 and 4 are used. Rate for all-time is not used.
Decrease
[Set range] 5.0 to 100.0 %
(initial: 95.0)
Increase
Decrease
[Set range] 0.1 to 120.0 %
(initial: 100.0)
◆Conversion rate (-P)
Set the conversion rate per integral export power (-P) 1 kWh.
Increase
Decrease
[Set range] 0.1 to 120.0 %
(initial: 100.0)
Increase
◆Calender timer
Decrease
Set the date and time.
(initial:0.0)
Increase
In order to use the logging function, set the date and time.
Decrease
・Refer to User's manual for the other settings.
(initial:0.0)
Enter password
from left to right
Increase
Shift entered digit to the right
If the password is wrong,
[FAIL] is displayed and it returns
to the password entry window.
*If you make wrong password
5 times, you can't set 1-hour after.
Password
initialize window
+
30 sec.
Not initialize[NO]
Return to the measuring value display
Increase
Decrease
[Set range] 0.00 to 99.99 /1kWh
(initial:10.00)
Time zone
None: all-time
T1: time zone 1 T2: time zone 2
T3: time zone 3 T4: time zone 4
Increase
Decrease
[Set range] 0.00 to 99.99 /1kWh
(initial:10.00)
Time zone
None: all-time
T1: time zone 1 T2: time zone 2
T3: time zone 3 T4: time zone 4
Increase
Decrease
[Set range]
Jan. 1st, 2000 00:00: to
Dec. 31st, 2099 23:59