INSTALLATION OF INDOOR, OUTDOOR UNIT
10

INSTALLATION OF OUTDOOR UNIT

You need to select adequate installation location considering the following conditions, and make
sure to acquire the consent of the user.
Installation Places
- If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat
radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows
around front, back and side of the unit are
respected.
- Do not place animals and plants in the path of the
warm air.
- Take the air conditioner weight into account and
select a place where noise and vibration are mini-
mum.
- Select a place so that the warm air and noise from
the air conditioner do not disturb neighbors.
- Select a place that can sufficiently endure the weight and vibration of the outdoor unit and
where even installation is possible.
- Select a place that has no direct impact of snow or rain
- Select a place with no danger of snowfall or icicle drop
- Select a place without weak floor or base such as decrepit part of the building or with a lot of
snow accumulation
- Install at a place with fluent water draining to prevent damage from localized heavy rain and
avoid frequent flooded area.
Piping length and the elevation
• Single Operation
Pipe Size mm(inch)
Model
Gas
UU18WE
Ø12.7 (1/2)
UU18W
Ø12.7 (1/2)
UU24WE
Ø15.88 (5/8)
UU24W
Ø15.88 (5/8)
UU30W
Ø15.88 (5/8)
If installed tube is shorter than 7.5 m,
additional charging is not necessary.
Additional Refrigerant
= [A-7.5 (m)] x Additional refrigerant (g/m)
Length A(m)
Liquid
Standard
Ø6.35 (1/4)
7.5
Ø6.35 (1/4)
7.5
Ø9.52 (3/8)
7.5
Ø9.52 (3/8)
7.5
Ø9.52 (3/8)
7.5
Indoor unit
More than
300mm
F e
n c e
o b
o r
s t a
c l e
s
More than 700mm
Elevation B(m)
Max.
Standard
25
5
30
5
30
5
50
5
50
5
A
B
Outdoor unit
More than
More than
More than
300mm
300mm
300mm
More than 600mm
Additional
refrigerant
Max.
(g/m)
15
20
30
20
15
40
30
40
30
40
Outdoor unit
A
Indoor unit
B

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uu18wUu30wUu24wUu24we