Installation Places for
Outdoor Unit
You need to select adequate installation
location considering the following conditions,
and make sure to acquire the consent of the
user.
- If an awning is built over the unit to prevent
direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not
restricted.
- Ensure that the spaces indicated by arrows
around front, back and side of the unit are
respected.
- Do not place animals and plants in the path of
the warm air.
- Take the air conditioner weight into account and
select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise
from the air conditioner do not disturb
neighbors.
- Select a place that can sufficiently endure
the weight and vibration of the outdoor unit
and where even installation is possible.
- Select a place that has no direct impact of
snow or rain
- Select a place with no danger of snowfall or
icicle drop
- Select a place without weak floor or base
such as decrepit part of the building or with a
lot of snow accumulation
- Install at a place with fluent water draining to
prevent damage from localized heavy rain
and avoid frequent flooded area.
More than
300 mm
F e
n c e
o b
o r
s t a
c l e
s
More than
More than
More than
300 mm
300 mm
300 mm
More than 600 mm
More than 700 mm
INSTALLATION PLACES
CAUTION
!
Be very careful while carrying the
product.
• Do not have only one person carry
product if it is more than 20 kg (44 lbs).
• PP bands are used to pack some
products. Do not use them as a mean
for transportation because they are
dangerous.
• Do not touch heat exchanger fins with
your bare hands. Otherwise you may
get a cut in your hands.
• Tear plastic packaging bag and scrap it
so that children cannot play with it.
Otherwise plastic packaging bag may
suffocate children to death.
• When carrying in Outdoor Unit, be sure
to support it at four points. Carrying in
and lifting with 3-point support may
make Outdoor Unit unstable, resulting
in a fall.
• Use 2 belts of at least 8 m (26.2 ft)
long.
• Place extra cloth or boards in the
locations where the casing comes in
contact with the sling to prevent
damage.
• Hoist the unit making sure it is being
lifted at its center of gravity.
13
A > 200 mm