Optional Water Wizard - Greenheck DG Installation, Operation And Maintenance Manual

Direct spark ignition make-up air
Table of Contents

Advertisement

Troubleshooting
Water Wizard™ — Improper Water Supply
NOTE
If the water supply is too low, the media will
continuously appear dry.
NOTE
If the water supply is too high, the media will be
saturated and excessive water will be draining from
the sump tank.
NOTE
Some water drainage is desired to keep the media
flushed, but it should be minimized to utilize the Water
Wizard.
1. Adjust the Manual Supply Valve
Adjust the manual supply valve (refer to Start-Up, Water
Wizard™). If the recommended water pressure does not
provide enough water, increase the pressure until the
desired water supply is achieved. If the recommended
water pressure provides too much water, decrease
the water pressure until the desired water supply is
achieved.
CAUTION
Only proceed to Steps 2 and 3 if Step 1 does not
correct the problem.
2. Enter Program Mode
Press and hold the Enter
key for three seconds
to enter Program Mode. The
display will read "Pro" when
Program Mode is active.
3. Adjust the On Time Factor
While in the Program
Menu, use the Up and
Down keys to navigate
through the menu
options until "ont" is
displayed.
With "ont" displayed, press the Enter key to access the
setting.
With the setting displayed, use the Up and Down keys
to adjust the setting as needed.
Increase the factor to increase the water supply or
decrease the factor to decrease the water supply.
Press the Enter key to save the new On Time Factor and
return to the Program Menu.
NOTE
Changing the On Time Factor by (1) will change the
water supply by approximately 3%.
IMPORTANT
The Enter key must be pressed to save the new On
Time Factor.
32