Mitsubishi Electric Mr. SLIM PEAD-RP60JA Technical Manual page 22

Air volume control
Hide thumbs Also See for Mr. SLIM PEAD-RP60JA:

Advertisement

6-2. Changing the power voltage setting
■PEAD-RP60,71,100,125,140JA(L)
Change power voltage setting by function selection via
the remote controller
Settings
Mode no.
240V
04
220,230V
6-3. Selecting the external static pressure
■PEAD-RP60,71,100,125,140JA(L)
Change external static pressure setting by function
selection via the remote controller
Setting no. of
External static
mode no.08
pressure
35Pa
2
50Pa
3
70Pa
1
100Pa
2
150Pa
3
PRECAUTION:
External static pressure must be at the rated air volume when all the damper is full open.
Set a bypass damper to secure minimum air volume with a minimum damper opening.
(Refer to 3.Fan characteristic curves)
Setting no. Initial setting
1
Ο
2
Setting no. of
Initial setting
mode no.10
1
Ο
1
2
2
2
■PEFY-P63,71,80,100,125,140VMA(L)-E
Change power voltage setting by dip switch
Settings
220, 230V
220V
240V
240V
■PEFY-P63,71,80,100,125,140VMA(L)-E
Change external static pressure setting by dip switch
Extemal static pressure
35 Pa
50 Pa
70 Pa
100 Pa
150 Pa
21
SW5
Initial setting
ON
Ο
OFF
Switch operation
3
1
2
2
1
SWA
SWC
3
1
2
2
1
SWA
SWC
3
1
2
2
1
SWA
SWC
3
1
2
2
1
SWA
SWC
3
1
2
2
1
SWA
SWC