Mitsubishi Electric Mr. SLIM PEAD-RP60JA Technical Manual page 7

Air volume control
Hide thumbs Also See for Mr. SLIM PEAD-RP60JA:

Advertisement

2-2. Example of air volume control by contact input and analog input
←(2) Analog input
CN2A
(1) Contact input
CN105
MAC-397IF-E *
Outdoor unit
Indoor unit
Air inlet
MA Remote
controller
MAC-397IF-E input
Indoor unit
MAC-397IF-E
CN105
CN560
Lead wires
■Dip switch (SW500) setting
ON
1
2
3
4
5
6
7
Refer to the MAC-397IF-E manual for DIP-SW setting and wiring.
2-3. Example of air volume control with fixed static pressure
This example shows how to keep duct static pressure at a constant level with analog input.
CN2A
Analog input
Contact input
CN105
MAC-397IF-E *
Indoor unit
Air inlet
Check air volume at each air outlet when R1-R4 is full open and set static pressure as target value. Then, analog
input to keep the static pressure at this target value even when either of the damper closes.
With MAC-397IF-E as in section 2-2, it is also possible to stop the indoor unit when all duct damper closes.
*Refer to the 1-3 for air volume differentials to prevent hunting.
1. Contact input
Damper System
2. Analog input
Controller
Bypass damper
Damper
Damper System Remote controller
Supply connecters to CN2A and CN105 on site. (Refer to 5).
* MAC-397IF-E:MA & Contact terminal interface (optional)
Field supply
Damper System Controller
CN591
Contact point a
1 2 3
4
5 6
(about 10mA)
8
Damper System
Controller
Bypass damper
R4
R3
R2
17m
/min 7m
/min
5m
/min 5m
3
3
3
Damper System Remote controller
Field supply
When either of the damper open/close with damper system controller,
ON/OFF signal via MAC-397IF-E.
Air volume controllable with analog input to CN2A, controlling open/close
of duct damper.
* It is possible to directly command CN105 without MAC-397IF-E with
serial communication. For further details, contact your nearest distributor.
air outlet
R1
Damper
/min
3
6