• If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm
from the drain hose port. If it is raised higher than 550
mm, there may be water leaks.
Drain hose
Band joint
• Do not give the hose an upward gradient beyond the
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
Under gradient
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
Support pieces
• Install horizontally.
Hanger
Main drainpipe
20 mm or more
1/100 or more
550 mm or
300 mm or
less
less
Ceiling
Ceiling
1 to 1.5 m
1/100 or more
Ceiling
Individual
air vent
Be horizontal
Indoor unit
• Max. allowable axis gap.
Indoor unit
• Max. allowable bending angle.
Indoor unit
NOTE
• If a concentrated drain pipe is installed, refer to the
figure below.
1~1.5m
Centralized horizontal drainpipe
(more than 1/100 slope)
Flexible hose
Max. 20 mm
Max. 30˚
Main air vent
550mm or less