2. Installation and wiring
INSTALLATION PRECAUTIONS
Use the module in the environment described in the USER'S MANUAL General Specification.
Do not use the PLC in places with dust, soot, conductive dust, corrosive gas or combustible
gas, places exposed to high temperature, condensation, wind or rain or places that experience
vibration or impact.
Using the module outside the range of the general specification may result in electrical shock,
fire, malfunctions, or damage to the PLC.
When drilling screw holes or performing wiring, make sure that cutting and wiring debris or
other foreign matter do not enter the ventilation slits of the module.
Such matter may cause fire, failure or malfunction.
When the installation work is completed, remove the dust protection sheet from the ventilation
slits of the PLC.
If the sheet remains attached, it may cause fire, failure or malfunction.
Securely connect extension cables to their specified connectors.
Poor contact may cause malfunction.
WIRING PRECAUTIONS
Before beginning any installation or wiring work, make sure all phases of the power supply
have been shut off.
Failing to shut off the power supply may cause electrical shock or damage to the module.
Following installation or wiring work, when turning on the power supply and operating the PLC,
make sure that the terminal cover provided as an accessory has been attached to the module.
Failing to attach the cover may cause electrical shock.
For the CC-Link system, use dedicated cables specified by the manufacturer.
The performance of the CC-Link system cannot be guaranteed with any cable other than
dedicated ones specified by the manufacturer.
For the maximum total extension length and the cable length between stations, observe the
specifications described in USER'S MANUAL.
With wiring outside the specification range, normal data transfer cannot be guaranteed.
Make sure to fix communication cables and power cables connected to the module by placing
them in a duct or clamping them.
Cables not placed in a duct or left unclamped may hang or shift, allowing them to be pulled
accidentally, which may result in malfunction or damage to the module and the cables.
When disconnecting a communication/power cable connected to the module, do not hold the
cable area.
For a cable with a connector, hold the connector attached to the cable.
For a cable connected to a terminal block, loosen screws of the terminal block before
disconnecting the cable.
If a cable is pulled while it is connected to a module, the module may malfunction or the
module and the cable may be damaged.
WIRING PRECAUTIONS
Use a grounding resistor of 100Ω or less with a wire of 2 mm
terminal in the PLC main units. However, never perform common grounding with a high voltage
system.
Other
Other
PLC
PLC
equipment
equipment
Dedicated grounding
Common grounding
(best)
(allowed)
Do not bundle control cables and communication cables with the main circuit and power
cables. Keep control cables and communication cables at least 100 mm away from the main
circuit and power cables.
Otherwise, electric noise may cause a malfunction.
2.1 Installation
Install the FX
-16CCL-M on the right side of the FX
/FX
2N
1N
2N
extension unit or another extension block. (For the FX
Series, the FX
2NC
FX
Series, the FX
-CNV-IF or FX
-1PS-5V is required.)
3UC
2NC
3UC
The FX
-16CCL-M can be installed using a DIN rail (DIN 46277, width: 35 mm (1.38 in.)) or directly with
2N
M4 (0.16 in.) screws.
In the case of direct installation, provide a space of 1 to 2 mm (0.04 to 0.08 in.) between the units.
2.2 Dedicated CC-Link Cables
Use dedicated CC-Link cables in the CC-Link system.
If any other cable is used, the performance of the CC-Link system cannot be guaranteed.
2.3 Module Wiring with Dedicated CC-Link Cables
This section describes the connection method of dedicated CC-Link cables.
The cables can be connected regardless of the station number.
Make sure to connect a terminal resistor (offered as an accessory to the module) between the
terminals DA and DB in the modules at both ends of the CC-Link system.
In the CC-Link system, the terminal resistor required varies depending on the cable used.
When a dedicated CC-Link cable is used: 110 Ω, 1/2 W (brown, brown and brown)
-
When a dedicated high-performance CC-Link cable is used: 130 Ω, 1/2 W (brown, orange and
-
brown)
The master module can be connected at either and of the system.
Star configuration is not allowed.
The figure below shows the connection method.
Important
Make sure to use only one type of cable (dedicated CC-Link cables OR dedicated CC-Link high-
performance cables).
If both types of cables are used together, normal data transmission cannot be guaranteed.
Point
The shielded dedicated CC-Link cable should go through the terminals SLD and FG in each
module, and both ends should be grounded (Class D = solid grounding).
The terminals SLD and FG are connected to each other inside the module.
Master module
DA
Terminal
resistor
DB
DG
SLD
FG
3. SPECIFICATION
3.1 Power Supply Specification
Item
24V DC external power
supply
5V DC internal power
supply
3.2 General Specification
Dielectric strength: 500V AC for 1 minute (between the case and the PLC ground)
Other specification is equivalent to that of the PLC main unit.
3.3 Performance Specification
Item
2
or more to ground the grounding
Applicable function
CC-Link version
Other
PLC
equipment
Transmission speed
Station number
Maximum total cable
Common grounding
length (maximum
(not allowed)
transmission distance)
Maximum number of
/FX
/FX
/FX
Series main unit,
connected modules
2NC
3U
3UC
-CNV-IF is required. For the
2NC
Maximum number of I/O
points per system
Remote module
Remote module
DA
DA
DB
DB
DG
DG
SLD
SLD
Dedicated CC-Link cable
Dedicated CC-Link cable
FG
FG
Specification
Supplied from a 24V DC (150 mA) external terminal block.
5V DC of PLC is not used.
(5V DC is converted from 24V DC external power supply.)
Specification
Master station function (The local station and standby master station functions
are not provided.)
Ver.1.10
Selectable (by rotary switch): 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps or
10 Mbps
0 (set by rotary switch)
1,200 m maximum
Varies depending on the transmission speed. (Refer to USER'S MANUAL.)
Remote I/O stations: 7 maximum (Each station occupies 32 I/O points of
the PLC.)
Remote device stations: 8 maximum (The following condition must be
satisfied.)
{(1×a)+(2×b)+(3×c)+(4×d)} ≤ 8
a: Number of remote device stations occupying 1 station
b: Number of remote device stations occupying 2 stations
c: Number of remote device stations occupying 3 stations
d: Number of remote device stations occupying 4 stations
Number of remote I/O stations + Number of remote device stations ≤ 15
"Maximum number of I/O points per system" below shall be satisfied.
For the system configuration calculation, refer to the USER'S MANUAL.
When using an FX
/FX
(V 2.20 or later) PLC:
3U
3UC
1) (Actual number of PLC I/O points) + (Number of points occupied by
special function blocks) + (Number of points occupied by
-16CCL-M: 8) ≤ 256 (FX
FX
/FX
(V 2.20 or later) Series PLC)
2N
3U
3UC
2) (32 × Number of remote I/O modules) ≤ 224 (FX
3U
/FX
3UC
later) Series PLC)
3) Total number of points (1)+2)) ≤ 384
Item
When using an FX
Connection is allowed as far as the following condition is satisfied:
(Actual number of PLC I/O points) + (Number of points occupied by
special function blocks) + (Number of points occupied by
Maximum number of I/O
-16CCL-M: 8) + (32 × Number of remote I/O modules) ≤ 256
FX
2N
points per system
(FX
/FX
/FX
2N
2NC
PLC)
For the system configuration calculation, refer to the USER'S MANUAL.
Remote I/O station
Remote device station : Remote I/O = 32/32 (RX/RY) points
Number of link points
per station
Communication method
Polling method
Synchronous method
Frame synchronous method
Encoding method
NRZI method
Transmission path type
Bus (RS-485)
Transmission format
In conformance to HDLC Standard
16
12
5
Error control method
CRC(X
+X
+X
+1)
Terminal
Connection cable
Dedicated CC-Link cable/Dedicated high-performance CC-Link cable
resistor
Automatic return function
RAS function
Slave station cutoff function
Error detection by link special relay/register
Number of times of
parameter registration
Approximately 10,000 times
to EEPROM
FX
, FX
(V 2.20 or later), FX
1N
2N
Connectable PLC
PLC
8 I/O points of FX Series PLC (8 points in total. The ratio between inputs
Number of occupied
and outputs is arbitrary.)
I/O points
When remote I/O station is connected, 32 points per station are occupied.
Communication with PLC By FROM/TO instructions via the buffer memory
Scan method: Asynchronous mode
Automatic refresh: Not provided
Local station function: Not provided
Note
Standby master station function: Not provided
Intelligent device station connection function: Not provided
FX
-32ASI-M AS-i master block: Cannot be connected concurrently.
2N
POWER : Lit while 24V DC is supplied from outside.
L RUN
: Lit while communication is normal.
Operation indication
L ERR
: Lit when communication error has occurred.
SD
: Lit while data is being transmitted.
RD
: Lit while data is being received.
Terminal resistor
For standard cable:
110 Ω, 1/2 W (color cable: brown, brown and brown), 2 cables
Accessories
For high performance cable:
130 Ω, 1/2 W (color cable: brown, orange and brown), 2 cables
Special block number label
MASS (Weight)
0.4 kg (0.88 lbs)
*1 Dedicated CC-Link cables and dedicated high-performance CC-Link cables cannot be used at the
same time.
Attach a terminal resistor in accordance with the cable type.
*2 When an FX
Series PLC is connected, the interface FX
2NC
*3 When an FX
Series PLC is connected, the interface FX
3UC
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any
patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving
industrial property rights which may occur as a result of using the contents noted in this manual.
Manual number : JY992D93201
Manual revision : C
Date
(V 2.20 or
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN
JY992D93201C
Specification
, FX
, FX
or a FX
(V 2.20 or less) PLC:
1N
2N
2NC
3UC
(V 2.20 or less) Series PLC) or 128 (FX
Series
3UC
1N
: Remote I/O = 32/32 (RX/RY) points
Remote register = 4 (RWw) points
(master station → remote device station)
Remote register = 4 (RWr) points
(remote device station → master station)
*1
*2
*3
, FX
(V 2.20 or later)
, FX
Series
3U
2NC
3UC
-CNV-IF is required.
2NC
-CNV-IF or FX
-1PS-5V is required.
2NC
3UC
: SEP . 2007
Effective SEP . 2007
Specifications are subject to
change without notice