Mitsubishi Electric MELSEC FX2N-16CCL-M Hardware Manual page 7

Cc-link system master block
Hide thumbs Also See for MELSEC FX2N-16CCL-M:
Table of Contents

Advertisement

FX
-16CCL-M CC-Link SYSTEM MASTER BLOCK
2N
HARDWARE MANUAL
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX
-16CCL-M CC-Link SYSTEM MASTER BLOCK. It should be read and
2N
understood before attempting to install or use the unit. Further information can be found in the FX series
PLC hardware manuals.
Guidelines for the safety of the user and protection of the FX
SYSTEM MASTER BLOCK
If in doubt at any stage during the installation of the FX
-16CCL-M CC-Link SYSTEM MASTER
2N
BLOCK always consult a professional electrical engineer who is qualified and trained to the local
and national standards. If in doubt about the operation or use of the FX
SYSTEM MASTER BLOCK please consult the nearest Mitsubishi Electric distributor.
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to
understanding the text, not to guarantee operation. Mitsubishi Electric will accept no
responsibility for actual use of the product based on these illustrative examples.
Owing to the very great variety in possible application of this equipment, you must satisfy
yourself as to its suitability for your specific application.
Note's on the symbology used in this manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the user's personal safety and protect the integrity of the equipment.
Whenever any of the following symbols are encountered, its associated note must be read and
understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware warnings
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage.
1. INTRODUCTION
1.1 Associated Manuals
Manual name
Manual number
★FX
-16CCL-M
JY992D93101
Describes programming and handling of the CC-
2N
User's Manual
(sent separately)
Link master block FX
★FX
/FX
/FX
/FX
JY992D88101
Explains the instructions available to the FX
1S
1N
2N
2NC
Programming Manual II
(sent separately)
FX
/FX
1N
2N
★FX
/FX
JY997D16601
Explains the instructions available to the FX
3U
3UC
Programming Manual
(sent separately)
FX
Series PLC.
3UC
JY992D89301
Describes hardware specifications, wiring and
✩FX
Hardware Manual
1N
(packed with product)
mounting of the FX
Describes the contents related to the hardware
JY992D66301
✩FX
Hardware Manual
such as specifications, wiring and mounting of the
2N
(packed with product)
FX
Series PLC.
2N
✩FX
Series User's
3U
JY997D16501
Describes the hardware specifications, wiring and
Manual
(sent separately)
mounting of the FX
- Hardware Edition
JY992D76401
Describes the hardware specifications, wiring and
✩FX
Hardware Manual
2NC
(packed with product)
mounting of the FX
✩FX
Series User's
3UC
JY997D28701
Describes the hardware specifications, wiring and
Manual
(sent separately)
mounting of the FX
- Hardware Edition
✩FX
-32CCL
JY992D71801
Describes programming and handling of the CC-
2N
User's Manual
(packed with product)
Link interface block FX
★: Indispensable manual
✩: Manual required depending on equipment used
1.2 Overview
The CC-Link master block FX
as the master station of the CC-Link system.
CC-Link Ver.1.10
1) Remote I/O stations and remote device stations can be connected to the master station (FX Series
PLC).
Master station
Remote I/O station
Remote device station
2) By using the CC-Link interface block FX
JY992D93201C
remote device stations to configure a simple distributed system.
Partner manufacturer's
product
-16CCL-M CC-Link
2N
-16CCL-M CC-Link
2N
1.3 Dimensions and Setting
Dimensions: mm (inches)
85(3.34)
75(2.95)
2-f4.5
10)
FX
-16CCL-M
2N
Description
Number
Name
-16CCL-M.
2N
1)
LED
/
1S
indicators 1
/FX
Series PLC.
2NC
/
3U
Series PLC.
1N
Series PLC.
3U
Series PLC.
2NC
Series PLC.
3UC
2)
Power indictor POWER
-32CCL.
2N
-16CCL-M is a special extension block which assigns an FX Series PLC
2N
: Station which controls the data link system
: Remote station which handles only bit information
: Remote station which handles both bit information and word information
-32CCL, two or more FX Series PLCs can be connected as
2N
CC-Link master block
FX
-16CCL-M
2N
FX
/FX
/FX
/FX
/FX
1N
2N
2NC
3 U
3 UC
Series PLC
Remote I/O station
Remote device station
Remote device station
FX
/FX
/FX
/FX
/FX
/FX
CC-Link interface block
0N
1N
2N
2NC
3U
3U C
Series PLC
FX
-32CCL
2N
MASS (Weight): 0.4 kg (0.88 lbs)
87(3.43)
RUN
ERR.
MST
9)
TEST1
TEST2
L RUN
L ERR.
POWER
8)
12)
E
SW
M/S
R
PRM
R
TIME
O
LINE
R
SD
RD
9(0.35)
Inside of top cover
Description
LED
Description
name
ON : Module is normal.
RUN
OFF: Watchdog time error has occurred.
RUN
Indicates the communication status with the
ERR.
stations set in the parameters.
MST
ON
: Communication error has
TEST 1
ERR.
TEST 2
occurred in all stations.
Flashing : Communication error has
L RUN
occurred in some stations.
L ERR
MST
ON : Set as the master station
TEST1
Test result indication
TEST2
Test result indication
ON : Data link is being executed
L RUN
(host station).
ON
: Communication error has
occurred (host station).
L ERR.
Flashing : The settings of the switches 4) to
7) were changed while the power
was ON.
ON : 24V DC is supplied from the outside.
Number
Name
3)
LED
SW
indicators 2
M/S
E
R
PRM ON : Parameter setting error has occurred.
SW
E
R
M/S
R
R
PRM
O
TIME
TIME
O
R
LINE
R
SD
LINE
RD
SD
RD
Remote I/O station
4)
Station
Sets the station number of the module. (Default setting at shipment: 00)
number setting
switch
<Setting range>
00 (because the FX
STATION NO.
× 10
If "65" or larger number is set, the "SW" and "L ERR." LED indicators turn ON.
× 1
5)
Mode setting
Sets the operation status of the module. (Default setting at shipment: 0)
switch
Number
0
1
MODE
2
3
4
5
6
7
8 to A
B to F
6)
Transmission
Sets the transmission speed of the module. (Default setting at shipment: 0)
speed setting
Number
switch
0
B RATE
1
RUN
FX
2N
-16CCL-M
0
156K
ERR.
1)
2
MST
1
625K
TEST1
TEST2
2
2.5M
STATION
L RUN
3
NO.
L ERR.
4)
´10
3
5M
2)
POWER
4
10M
4
´
1
5)
4
5 to 9
MODE
11)
B RATE
6)
0
156K
7)
Condition
Sets the operation condition. (Default setting at shipment: All OFF)
1
625K
2
2.5M
3
5M
7)
ON
4
10M
setting switch
SW
OFF
ON
1
-
-
2
-
-
SW
E
3
-
-
4
CLR
HLD
M/S
R
Number
3)
5
-
-
PRM
R
6
-
-
TIME
O
7
-
-
LINE
R
8
-
-
ON
SD
SW
OFF
ON
RD
1
SW1 to
2
3
SW3
4
CLR
HLD
5
6
SW4
7
8
SW5 to
SW8
LED status
8)
Terminal block Connects dedicated CC-Link cables to enable data link. For the connection
Normal
Error
method, refer to Section 2.3.
ON
OFF
The terminals SLD and FG are connected inside.
M3.5 Screw
ON or
OFF
flashing
ON
OFF
9)
Terminal block Connects the power supply to operate the master block.
OFF except during
test
M3 Screw
ON
OFF
10)
Extension
ON or
Connects the PLC.
OFF
cable
flashing
11)
Next step
extension
Connects extension equipment.
ON
OFF
connector
12)
DIN rail
mounting
DIN46277: DIN rail mounting groove of 35 mm (1.38") in width
groove
Description
ON : Switch setting error has occurred.
OFF
ON
ON : The master station is already present
OFF
ON
in the same line.
OFF
ON
ON : Data link watchdog timer errors has
OFF
ON
occurred (error in all stations).
ON : The cable is broken or the
transmission route has been affected
OFF
ON
by noise, etc.
ON : Data is being transmitted.
ON
OFF
ON : Data is being received.
ON
OFF
-16CCL-M is dedicated to the master station)
2N
Name
Description
Online
Sets connection to data link.
(Unusable)
Offline
Sets disconnection from data link.
Line test 1
Refer to USER'S MANUAL.
Line test 2
Refer to USER'S MANUAL.
Parameter
Refer to USER'S MANUAL.
verification test
Hardware test
Refer to USER'S MANUAL.
(Unusable)
Setting error (The SW LED indicator turns ON.)
(Unusable)
Cannot be set because it is already used inside.
(Unusable)
Setting error (The SW LED indicator turns ON.)
Setting contents
156 kbps
625 kbps
2.5 Mbps
5 Mbps
10 Mbps
Setting error (The SW and L ERR. LED indicators turn ON.)
Switch status
Setting description
ON
OFF
(Unusable)
Always OFF
Keep
Clear
Input data status in data link faulty station
(HLD)
(CLR)
(Unusable)
Always OFF