This Manual covers both the Wide angle and the Narrow long range occupancy sensor. Dialight Part Numbers described here-in are: WOSU22BG2 Wide angle WOSU12BG2 Long Range Wide optic version Long Range Version 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
How to Mount ..................................... 12 Long Range Sensor Wall Mount ..............................13 How to Mount ..................................... 14 Troubleshooting ..................................15 Troubleshooting Continued: ............................... 16 Troubleshooting Continued: ............................... 17 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
Keep These Instructions READ AND FOLLOW ALL SAFETY INSTRUCTIONS Welcome to the Dialight Wireless Occupancy Sensor user manual. This product allows you to customize your entire lighting network using independent Occupancy Sensors throughout your facility by turning lights on when occupancy has been detected.
Push and hold for 5 seconds. Sensor will double blink while trying to join a gateway, Sensor will stop blinking if it doesn’t join a gateway within 30 minutes. 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
To remove the sensor, twist sensor cover counterclockwise to unlock it from the back plate. Once cover has been removed you’re now ready to add or remove the batteries. 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
NOTE: Turning switch to on will cause increase current draw to the batteries and will shorten life based on the amount of motion detection. LED On/Off Switch 3. Twist close the sensor back on to the mounting plate. 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
Page 9
Only replace batteries with same size and type. ____________________________________________________________________________________ Red LED3 Low Bat blinking twice in a second means sensor is looking for a network and battery voltage is under 2.7V. 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
1. When the green LED blinks twice a second on the sensor, the sensor is ready to be discovered/commissioned. 2. Use a Dialight gateway to discover the sensor. (Please refer to the gateway owner’s manual for further instructions under the devices page.) 3.
2.7 meters or 8.8 feet from the floor. Sensor should be mounted 6ft away from any open air vent or strong air supply openings. 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
4. Use the three provided screws and secure sensor to the ceiling. 5. Attach and lock the sensor to the mounting plate. Ceiling Mounting Plate Screws Sensor 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
The long range sensor is best used as a wall mounted sensor. The recommended install for this sensor is 3.2 meters or 10.5 feet from the floor. Avoid placing sensors where obstacles can block the sensor’s line of sight. 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
4. Use the three provided screws and secure sensor to the wall. 5. Attach and lock the sensor to the mounting plate. Wall Sensor Screws Mounting Plate 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
9100-127-2989-99 REV B Troubleshooting Sensor is not discovered by the gateway. NOTE: This section requires the Dialight Gateway and to be connected to a computer using the GUI interface. Steps to solve: 1. On the gateway web page verify that discovery is turned on.
Continue to step 2. i. If it does not blink for motion. j. Confirm the led SW2 is set to on. k. If not then replace the sensor 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...
14. If none show motion present then this sensor is likely part of a different gateway network. Follow steps in this manual to remove the sensor from a different gateway. 1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com...