Download Print this page

Mitsubishi Electric MELSEC FX-1HC User Manual page 4

Special function block
Hide thumbs Also See for MELSEC FX-1HC:

Advertisement

3
3.1 Environmental specifications
The environmental specifications for the FX-1HC are the same as those for your FX series PC.
3.2 Performance specifications
Item
Signal level
MAX. frequency
Input signal
Pulse shape
Format
Range
Counting
specifi-
cation
Comparison Type
Output
Types of outputs
signal
Output capacity
I/O occupation
Power from base
SPECIFICATIONS
1-phase input
1 input
2 inputs
5V, 12V, or 24V ±10% (selected by terminal connection) 7mA
50 kHz
t1
t1
t2
t3
t3
Automatic UP/DOWN (however, when on 1 phase 1 input mode, UP/DOWN is
determined by a PC command or an input terminal.)
When 32-bit is specified: -2,147,483,648 to +2,147,483,647
When 16-bit is specified: 0 to 65,535 (upper limit can be user specified)
Each output is set when the present value of the counter matches with the compare
value (which is transferred from the PC), and is switched OFF by a reset command
from the PC.
YH
: Direct output processed by hardware.
YS
: Software processed output with worst delay time of 300
(Therefore, when the input frequency is 50 kHz, there is a worst case delay of 15 input
pulses.)
YHN
: NPN transistor output for YH output
YHP
: PNP transistor output for YH output
YSN
: NPN transistor output for YH output
YSP
: PNP transistor output for YH output
DC 12V to 24V 0.5A
8 point taken from the FX, FX
DC 5V 70mA
2-phase input
1 edge count
2 edge count
t1 : Rise/fall time is 3
t2 : ON/OFF pulse duration 10
t3 : Phase difference between phase A and phase B
t2
µ
is 3.5
s or more
PRESET (Z phase) input 100
DISABLE (count prohibit) input 100
PNP
expansion bus (can be either inputs or outputs)
2C
4 edge count
25 kHz
12.5 kHz
µ
s or less
µ
s or more
µ
s or more
µ
s or more
µ
s.
+
Output
Output
NPN

Advertisement

loading