Ruud PowerVent 2 AP13370-2 Use And Care Manual page 12

75 gallon
Table of Contents

Advertisement

Installing the water heater.
5
Min. 12" (30,5cm)
Above Roof
Min. 12" (30,5cm) Above
Anticipated Snow Level
4
Max. 24" (61cm) Above
Roof (Without Additional
Support)
4
Not applicable for Canada Installations.
NOTICE: Canadian vent termination/location must follow CSA B149 requirements and may vary from above.
Mortar or
Silicone Caulk
Vent Pipe
From
Water Heater
Pipe Coupling
12
Insert 1/2" Mesh Protective Screen Inside
Terminal Elbow
Short Piece of Vent Pipe
Vent Pipe
Through Roof
Elbows
Recommended 2' x 2'
Sheet Metal Shield
on Brick or Masonry Walls
Vent Terminal with
1
/
" Mesh Protective
2
Screen Inside
12" min
Outside of
(30,5 cm)
Building
above
Wall
grade
Draining the Condensate
In certain conditions, installations in
unconditioned space or having long
horizontal or vertical runs may accumulate
condensate.
In order to prevent condensate from
draining back into the blower, we
recommend a condensate tee and drain to
be installed in a horizontal vent section as
close as practical to the blower vent
connection.
Vertical Vent Termination
Minimum twelve (12) inches (30,5 cm)
Minimum twelve (12) inches (30,5 cm)
anticipated snow level.
Maximum twenty-four (24) inches (61cm)above
roof level without additional support for vent.
Four (4) feet (1.2m) from any gable, dormer or other
roof structure with building interior access (i.e., vent,
window, etc.).
Ten (10) feet (3,05m)
7
building. Any fresh or make-up air inlet such as a
dryer or furnace area is considered to be a forced air
inlet.
5
For installations in Canada 18" (45,7 cm).
6
Not applicable for installations in Canada.
7
For installations in Canada 6´ (1,8 m).
Horizontal Vent Installation
Once the vent terminal location has been determined,
make a hole through the exterior wall to
accommodate the 3" or 4" vent pipe. Vent pipe must
exit exterior wall only.
Insert a small length of 3" or 4" vent pipe through the
wall and connect the coupling as shown.
Place the ½" mesh metal screen inside the terminal
fitting and connect it as shown to the vent pipe on the
exterior of the building.
Seal any opening around the vent pipe or fittings with
mortar or silicone caulk as shown.
Complete the rest of the vent pipe installation to the
water heater's vent connector fitting on the blower
outlet. If necessary support horizontal run as
previously mentioned.
Use silicone sealant at the point the vent connector
joins the blower assembly.
Condensate is known to be acidic; refer to
local, state (provincial) or federal codes
for proper handling methods.
5
above roof.
6
above
from any forced air inlet to the