Pipe installation

Circulation pump

Delivery setting: Constant pressure curve 1.
If parts of the heating system do not get hot,
this can be changed to Constant pressure curve
2. Selecting a higher curve increases energy con-
sumption and operating costs.
Push but-
ton
In operating mode, the first LED lights up green,
and between one and four LEDs light up yellow.
The yellow LEDs indicate the operating capacity
of the pump.
0 - 25 %
25 - 50 %
50 - 75 %
75 - 100 %
Pressing the button displays the pump setting for
2 sec before the pump returns to normal display.
PROP. PRESSURE: CURVE 1
PROP. PRESSURE: CURVE 2
PROP. PRESSURE: CURVE 3
CONST. PRESSURE: CURVE 1
CONST. PRESSURE: CURVE 2
CONST. PRESSURE: CURVE 3
CONST. CURVE: KURVA 1
CONST. CURVE: KURVA 2
CONST. CURVE: KURVA 3
CONST. CURVE: KURVA 4
If the button is depressed for 2 sec, the pump
switches to setup mode and the LEDs flash. In
setup mode, any one of 10 curves can be selected
by turning the button. When the button has been
released for 10 sec, the pump returns to operat-
ing mode, the LEDs stop flashing and the selected
curve becomes active.
A lit red LED indicates an alarm or warning.
Indication
LEDs
fourth
yellow
third yel-
second
yellow
A button lock prevents accidental adjustments to
the pump settings. The button can be locked/un-
locked by depressing the button for 10 seconds.
After 10 seconds, all the LEDs will flash quickly
to indicate that the lock is locked/unlocked.
Pump capacity
p
[kPa]
50
40
30
20
10
0
Fault
Motor
Pump tries
blocked
to restart
Red
at 1.5 sec
+
intervals
Low volt-
Warning
age
only, pump
Red
continues to
+
operate
low
Electrical
Pump
fault
stopped
Red
+
H
[m]
5
4
3
2
1
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8
0.0
0.1
0.2
0.3
0.4
P1
[W]
35
30
25
20
15
10
5
0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8
Status
Measure
Release
motor/
impeller or
wait
Check volt-
age to pump
Check volt-
age/replace
pump
Q [m³/h]
0.5
0.6
0.7
0.8
Q [l/s]
Q [m³/h]
EN.33.C.111.1804