Manual Call Point
1
Installation
Notice!
Unshielded cables can be used with LSN improved addressing mode. Otherwise, shielded
cables must be used. Keep the shield wire as short as possible and insulate it. It is not
permitted to use different addressing modes together.
2
Technical data
Electrical
Operating voltage (VDC)
Current consumption (mA)
Environmental
Degree of protection (EN 60529) Form H
Degree of protection (EN 60529) Form G
Norm
Operating temperature Form H (°C)
Operating temperature Form G (°C)
Mechanics
Dimensions W x H x D (mm)
Housing material
Color
Weight (g)
Bosch Sicherheitssysteme GmbH
Installation Guide
Installation | en
24 (15 to 33)
0.4
IP 54
IP 52
EN 54-11
-25 to 70
-10 to 55
135 x 135 x 40
Plastic ASA
Red RAL 3001
Approx. 235
2017.03 | 9 | F.01U.027.290
5