ON
9. Fully / Semi automatic mode
OFF
(for IR-PD-DALI functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on.
Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-
on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the "S" button input (ON / OFF Dimm).
10. Manual Dimming – Preset / User
(for IR-PD-DALI functions see page 1)
You can dim manually by pressing the pushbutton for
a long time (> 2 sec). When the button is released,
the current dimming value is retained. Upon renewed
dimming, the dimming direction is reversed.
PRESET – the luminance set point is set during start-up
max
operation by the installer and remains unchanged.
The luminance set- point configured through manual
ON
dimming is only applied for the time being.
Caution:
The constant light regulation is now deactivated!
OFF
The currently set artificial light is retained independent
of the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation
is activated.
USER – can only be activated via the remote control!
The luminance set-point is changed upon each manual
dimming and re-adjusted by the user (Conformation
max
through relay clicking!)
The constant light regulation remains activated!
ON
11. Manual Switching
OFF
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the configured
follow up time.
12. Article / Part nr. / Accessory
Type
PD9-M-DALI/DSI – Master
PD9-M-DALI/DSI-GH – Master
PD9-S – Slave
PD9-S-GH – Slave
LUXOMAT
Remote control:
®
IR-PD-DALI (incl. wall bracket)
Accessory:
Wall bracket for remote control as replacement 92100
Blind PD9-GH for 180° detection
Circuit diagram
PD9-M-DALI/DSI
13. Wiring diagram
Standard mode with master DALI occupancy detectors



14. PD9-M-DALI/DSI(-GH) – Connections
50
1500
Lux
Lux
50
1500
Lux
Lux
FC
92920
92938
92905
92928
92094
33207
L
N
up to 50 EBs
S1 S2
For T5 and
T8 fluorescent
SLAVE
lamps




T
S
L
N
L'


R
S
L
N
N
DALI
DSI
D D
EB 1
EB 2
EB 50
15. Technical data PD9-M-DALI/DSI(-GH)
Power supply:
230 V~ ±10 %
Power consumption:
< 1W
Ambient temperature:
-25°C to +50°C
Degree of protection/class:
IP20 / II
Settings:
by remote control

Light values - IR-PD-DALI:
50 - 1500 Lux
Extension of the detection area: with Slaves

Area of coverage:
circular 360°
Range of coverage Ø H 2.50 m / T = 18°C:

PD9-M-DALI/DSI
seated 2.50 m / tangential
10 m / radial 6 m
PD9-M-DALI/DSI-GH
max. Ø 5.40 m
Recommended height for mounting:
PD9-M-DALI/DSI
2 - 3 m
PD9-M-DALI/DSI-GH
5 - 10 m

Light measurement: mixed light, daylight and artificial light

• DALI-Output

digital BUS control wire, 2-core, no polarity
(broadcast only)
Max. no. of series-connected electronic ballasts:
up to 50
Time-settings:
1 - 30 min. / Test
Dimensions H x Ø [mm]:
PD9-M-DALI/DSI
Ø 45 x H 28 mm
PD9-M-DALI/DSI-GH
Ø 45 x H 40 mm
Power supply
L 165 x W 24 x H 24 mm
Declaration of Conformity: The product complies with the
low voltage recommendation 2006/95/EC and the EMV
recommendation 2004/108/EC.
WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED
LIGHTS A 100 h BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES)
FUNCTION TAkES PLACE. THIS CAN BE IGNORED By USING THE
REMOTE CONTROL TO DEACTIVATE.
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN
DOES NOT TAkE PLACE.
16. LED-functional indicators
LED function indicators
Process
Initialisation time
unprogrammed
Initialisation time
programmed
Motion detection
Too bright detected
Too bright / too dark /
undefined in opened state
Switching DALI/DSI
DSI active
Switching DALI/DSI
DALI active
Switching HA/VA
VA active
Switching HA/VA
HA active
Switching Preset/User
Preset active
Switching Preset/User
User active
IR signal valid received
IR signal invalid received
Standard
Double-locked
mode
Green
Red flashes
flashes
Red flashes
Green flashes
quickly
quickly
Red flashes
Green flashes
on each
on each
detected
detected
movement
movement
Red flashes
Green flashes
2x each
2x each
second
second
Red flashes
Green flashes
very quickly
very quickly
Red shines
3 sec.
Green shines
3 sec.
Red shines
3 sec.
Green shines
3 sec.
Red shines
3 sec.
Green shines
3 sec.
Red shines
3 sec.
Red shines
0,5 sec.

Advertisement

loading

This manual is also suitable for:

Pd9-m-dali/dsi-gh-fc